background image

Manual 2100-652A
Page 

39 of 42

Manual

2100-522B

Page

36 of 38

TROUBLESHOOTING  GE  ECM

 MOTORS CONT’D.

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove

Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              

Use the shorter 

bolts and 

alignment pin 

supplied when 

replacing an 

ECM 2.0 

control.

Figure 3

ECM 

2.3/2.5

Power Connector

(5-pin)

Control Connector

(16-pin)

Hex-head Screws

Motor Connector

(3-pin)

Motor Connector

(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats

Over Ramp

From Motor

Circuit

Board

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower

motor you need to take the following steps:

1. You MUST have the correct replacement module.  The controls are

factory programmed for specific operating modes.  Even though they look

alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT

WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the furnace or air handler being

serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER

APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect

power and wait at least 5 minutes before opening motor.

3. It is usually not necessary to remove the motor from the blower

assembly.  However, it is recommended that the whole blower assembly,

with the motor, be removed from the furnace/air handler.  (Follow the

manufacturer’s procedures).  Unplug the two cable connectors to the motor.

There are latches on each connector.  

DO NOT PULL ON THE WIRES.

The plugs remove easily when properly released.

4. Locate  the  two  standard  ¼"  hex  head  bolts  at  the  rear  of  the  control

housing  (at  the  back  end  of  the  control  opposite  the  shaft  end).   

Refer  to

Figure  24.   

Remove  these  two  bolts  from  the  motor  and  control  assembly

while  holding  the  motor  in  a  way  that  will  prevent  the  motor  or  control

from  falling  when  the  bolts  are  removed.    If  an  ECM2.0  control  is  being

replaced  (recognized  by  an  aluminum  casting  rather  that  a  deep-drawn

black  steel  can  housing  the  electronics),  remove  only  the  hex-head  bolts.

DO  NOT  REMOVE  THE  TORX-HEAD  SCREWS.

5. The  control  module  is  now  free  of  mechanical  attachment  to  the

motor  endshield  but  is  still  connected  by  a  plug  and  three  wires  inside

the  control.    Carefully  rotate  the  control  to  gain  access  to  the  plug  at

the  control  end  of  the  wires.    With  thumb  and  forefinger,  reach  the

latch  holding  the  plug  to  the  control  and  release  it  by  squeezing  the

latch  tab  and  the  opposite  side  of  the  connector  plug  and  gently  pulling

the  plug  out  of  the  connector  socket  in  the  control.   

DO  NOT  PULL

ON  THE  WIRES.    GRIP  THE  PLUG  ONLY.

6. The  control  module  is  now  completely  detached  from  the  motor.

Verify  with  a  standard  ohmmeter  that  the  resistance  from  each  motor

lead  (in  the  motor  plug  just  removed)  to  the  motor  shell  is  >100K  ohms.

Refer to Figure 25.  

(Measure to unpainted motor end plate.)  If any

motor  lead  fails  this  test,  do  not  proceed  to  install  the  control  module.

THE  MOTOR  IS  DEFECTIVE  AND  MUST  BE  REPLACED.

Installing  the  new  control  module  will  cause  it  to  fail  also.

7. Verify  that  the  replacement  control  is  correct  for  your

application.    Refer  to  the  manufacturer's  authorized  replacement  list.

USING  THE  WRONG  CONTROL  WILL  RESULT  IN

IMPROPER  OR  NO  BLOWER  OPERATION.

    Orient  the  control

module  so  that  the  3-wire  motor  plug  can  be  inserted  into  the  socket  in

the  control.    Carefully  insert  the  plug  and  press  it  into  the  socket  until

it  latches.   

A  SLIGHT  CLICK  WILL  BE  HEARD  WHEN

PROPERLY  INSERTED.

    Finish  installing  the  replacement  control  per

one  of  the  three  following  paragraphs,  8a,  8b  or  8c.

8a. 

IF  REPLACING  AN  ECM  2.0  CONTROL

  (control  in  cast

aluminum  can  with  air  vents  on  the  back  of  the  can) 

WITH  AN  ECM

2.3  CONTROL

  (control  containing  black  potting  for  water  protection  in

black  deep-drawn  steel  case  with  no  vents  in  the  bottom  of  the  can),

locate  the  two  through-bolts  and  plastic  tab  that  are  packed  with  the

replacement  control.    Insert  the  plastic  tab  into  the  slot  at  the  perimeter

of the open end of the can so that the pin is located on the inside of the

perimeter of the can.  Rotate the can so that the tab inserts into the tab

locater  hole  in  the  endshield  of  the  motor.    Using  the  two  through-bolts

provided  with  the  replacement  control,  reattach  the  can  to  the  motor.

THE  TWO  THROUGH-BOLTS  PROVIDED  WITH  THE

REPLACEMENT  ECM  2.3  CONTROL  ARE  SHORTER  THAN

THE  BOLTS  ORIGINALLY  REMOVED  FROM  THE  ECM  2.0

CONTROL  AND  MUST  BE  USED  IF  SECURE  ATTACHMENT

OF  THE  CONTROL  TO  THE  MOTOR  IS  TO  BE  ACHIEVED.

DO  NOT  OVERTIGHTEN  THE  BOLTS.

8b. 

IF  REPLACING  AN  ECM  2.3  CONTROL

 

WITH  AN  ECM  2.3

CONTROL

,  the  plastic  tab  and  shorter  through-bolts  are  not  needed.    The

control  can  be  oriented  in  two  positions  180°  apart.   

MAKE  SURE  THE

ORIENTATION  YOU  SELECT  FOR  REPLACING  THE

CONTROL  ASSURES  THE  CONTROL'S  CABLE  CONNECTORS

WILL  BE  LOCATED  DOWNWARD  IN  THE  APPLICATION  SO

THAT  WATER  CANNOT  RUN  DOWN  THE  CABLES  AND  INTO

THE  CONTROL.

    Simply  orient  the  new  control  to  the  motor's  endshield,

insert bolts, and tighten.  

DO  NOT  OVERTIGHTEN  THE  BOLTS.

8c. 

IF  REPLACING  AN  ECM  2.0  CONTROL  WITH  AN  ECM  2.0

CONTROL 

(It  is  recommended  that  ECM  2.3  controls  be  used  for  all

replacements), 

the  new  control  must  be  attached  to  the  motor  using

through  bolts  identical  to  those  removed  with  the  original  control.   

DO

NOT  OVERTIGHTEN  THE  BOLTS.

9. Reinstall  the  blower/motor  assembly  into  the  HVAC  equipment.

Follow  the  manufacturer's  suggested  procedures.

10.  Plug  the  16-pin  control  plug  into  the  motor.    The  plug  is  keyed.

Make  sure  the  connector  is  properly  seated  and  latched.

11.  Plug  the  5-pin  power  connector  into  the  motor.    Even  though  the

plug  is  keyed, 

OBSERVE  THE  PROPER  ORIENTATION.    DO  NOT

FORCE  THE  CONNECTOR.

    It  plugs  in  very  easily  when  properly

oriented.   

REVERSING  THIS  PLUG  WILL  CAUSE  IMMEDIATE

FAILURE  OF  THE  CONTROL  MODULE.

12.  Final  installation  check.    Make  sure  the  motor  is  installed  as  follows:

a. Unit  is  as  far  INTO  the  blower  housing  as  possible.

b. Belly  bands  are  not  on  the  control  module  or  covering  vent  holes.

c. Motor  connectors  should  be  oriented  between  the  4  o’clock  and  8

o’clock  positions  when  the  blower  is  positioned  in  its  final

location  and  orientation.

d. Add  a  drip  loop  to  the  cables  so  that  water  cannot  enter  the  motor

by  draining  down  the  cables.   

Refer  to  Figure  26.

The  installation  is  now  complete.    Reapply  the  AC  power  to  the  HVAC

equipment  and  verify  that  the  new  motor  control  module  is  working

properly.    Follow  the  manufacturer's  procedures  for  disposition  of  the  old

control  module.

Figure 25

Figure 24

Figure 26

Figure 25

Figure 26

Figure 27

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower 
motor, take the following steps:
1.  The correct replacement module MUST be used.  The controls 

are factory programmed for specific operating modes.  Even 
though they look alike, different modules may have completely 
different functionality.

 

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT 

WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2.  Begin by removing AC power from the furnace or air handler 

being serviced.  

DO NOT WORK ON THE MOTOR WITH AC 

POWER APPLIED. 

 

To avoid electric shock from the motor’s 

capacitors, disconnect power and wait at least 5 minutes before 
opening motor.

3.  It is usually not necessary to remove the motor from the blower 

assembly.  However, it is recommended that the whole blower 
assembly, with the motor, be removed from the furnace/air 
handler.  (Follow the manufacturer’s procedures).  Unplug the 
two cable connectors to the motor.  There are latches on each 
connector.  

DO NOT PULL ON THE WIRES.

  

The plugs remove 

easily when properly released.

4.  Locate the two standard ¼" hex head bolts at the rear of the 

control housing (at the back end of the control opposite the 
shaft end).  

Refer to Figure 25.  

Remove these two bolts from 

the motor and control assembly while holding the motor in a 
way that will prevent the motor or control from falling when 
the bolts are removed.  If an ECM2.0 control is being replaced 
(recognized by an aluminum casting rather that a deep-drawn 
black steel can housing the electronics), remove only the hex-
head bolts.  

DO NOT REMOVE THE TORX-HEAD SCREWS.

5.  The control module is now free of mechanical attachment to the 

motor endshield but is still connected by a plug and three wires 
inside the control.  Carefully rotate the control to gain access 
to the plug at the control end of the wires.  With thumb and 
forefinger, reach the latch holding the plug to the control and 
release it by squeezing the latch tab and the opposite side of the 
connector plug and gently pulling the plug out of the connector 
socket in the control.  

DO NOT PULL ON THE WIRES.  GRIP 

THE PLUG ONLY.

6.  The control module is now completely detached from the motor.  

Verify with a standard ohmmeter that the resistance from each 
motor lead (in the motor plug just removed) to the motor shell is 
>100K ohms.  

Refer to Figure 26.  

(Measure to unpainted motor 

end plate.)  If any motor lead fails this test, do not proceed to 
install the control module.  

THE MOTOR IS DEFECTIVE AND 

MUST BE REPLACED.

  Installing the new control module will 

cause it to fail also.

7.  Verify that the replacement control is correct for the application.  

Refer to the manufacturer's authorized replacement list.  

USING 

THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO 

BLOWER OPERATION.

  Orient the control module so that the 

3-wire motor plug can be inserted into the socket in the control.  
Carefully insert the plug and press it into the socket until it 
latches.  

A SLIGHT CLICK WILL BE HEARD WHEN PROPERLY 

INSERTED.

  Finish installing the replacement control per one of 

the three following paragraphs, 7a, 7b or 7c.

 7a. 

IF REPLACING AN ECM 2.0 CONTROL

 (control in cast 

aluminum can with air vents on the back of the can) 

WITH 

AN ECM 2.3 CONTROL

 (control containing black potting 

for water protection in black deep-drawn steel case with no 
vents in the bottom of the can), locate the two through-
bolts and plastic tab that are packed with the replacement 
control.  Insert the plastic tab into the slot at the perimeter 
of the open end of the can so that the pin is located on the 
inside of the perimeter of the can.  Rotate the can so that 
the tab inserts into the tab locater hole in the endshield of 
the motor.  Using the two through-bolts provided with the 
replacement control, reattach the can to the motor.

 

 

THE TWO THROUGH-BOLTS PROVIDED WITH THE 

REPLACEMENT ECM 2.3 CONTROL ARE SHORTER 

THAN THE BOLTS ORIGINALLY REMOVED FROM THE 

ECM 2.0 CONTROL AND MUST BE USED IF SECURE 

ATTACHMENT OF THE CONTROL TO THE MOTOR 

IS TO BE ACHIEVED.

  

DO NOT OVERTIGHTEN THE 

BOLTS.

 7b. 

IF REPLACING AN ECM 2.3 CONTROL WITH AN ECM 

2.3 CONTROL

, the plastic tab and shorter through-bolts 

are not needed.  The control can be oriented in two 
positions 180° apart.  

MAKE SURE THE ORIENTATION 

SELECTED FOR REPLACING THE CONTROL ASSURES 

THE CONTROL'S CABLE CONNECTORS WILL BE 

LOCATED DOWNWARD IN THE APPLICATION SO THAT 

WATER CANNOT RUN DOWN THE CABLES AND INTO 

THE CONTROL.

  Simply orient the new control to the 

motor's endshield, insert bolts and tighten.  

DO NOT 

OVERTIGHTEN THE BOLTS.

 

7c. 

IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM 

2.0 CONTROL

 

(it is recommended that ECM 2.3 

controls be used for all replacements), 

the new control 

must be attached to the motor using through bolts 
identical to those removed with the original control.  

DO 

NOT OVERTIGHTEN THE BOLTS.

8.  Reinstall the blower/motor assembly into the HVAC 

equipment.  Follow the manufacturer's suggested procedures.

9.  Plug the 16-pin control plug into the motor.  The plug is 

keyed.  Make sure the connector is properly seated and 
latched.

10.  Plug the 5-pin power connector into the motor.  Even though 

the plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  

DO NOT FORCE THE CONNECTOR.

  It plugs in very easily 

when properly oriented.  

REVERSING THIS PLUG WILL 

CAUSE IMMEDIATE FAILURE OF THE CONTROL MODULE.

11.  Final installation check.  Make sure the motor is installed as 

follows:

 

a. 

Unit is as far INTO the blower housing as possible.

 

b.  Belly bands are not on the control module or covering 

vent holes.

 

c. 

Motor connectors should be oriented between the 4 
o’clock and 8 o’clock positions when the blower is 
positioned in its final location and orientation.

 

d.  Add a drip loop to the cables so that water cannot enter 

the motor  by draining down the cables.  

Refer to Figure 

27.

The installation is now complete.  Reapply the AC power to the 
HVAC equipment and verify that the new motor control module 
is working properly.  Follow the manufacturer's procedures for 
disposition of the old control module.

Summary of Contents for Q24H3-A

Page 1: ...Bryan Ohio 43506 www bardhvac com Manual No 2100 652A Supersedes 2100 652 Date 10 11 17 Q TECTM SERIES PACKAGED HEAT PUMP Models Q24H3 A Q24H3 B Q24H3 C Q30H3 A Q30H3 B Q30H3 C Q36H3 A Q36H3 B Q36H3 C Q43H3 A Q43H3 B Q43H3 C Q48H3 A Q48H3 B Q48H3 C Q60H3 A Q60H3 B Q60H3 C ...

Page 2: ...7 Figure 4 Unit on Appliance Cart for Moving 8 Figure 5 Installation With Duct Free Plenum 9 Figure 6 Ducted Application 9 Figure 7 Supply Duct Connections 10 Figure 8 Filter Location 10 Figure 9 Optional Side Drain 12 Figure 10 Standard Rear Drain 12 Figure 11 Rear Drain Top View 12 Figure 12A Optional Rear Drain Kit 13 Figure 12B Optional Rear Drain Kit 14 Figure 12C Optional Rear Drain Kit 15 F...

Page 3: ...and Summer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY...

Page 4: ... A 230 208 60 1 B 230 208 60 3 C 460 60 3 INTERNAL CONTROLS X Standard High Pressure Switch Low Pressure Switch Compressor Time Delay E Low Ambient Control Q Outdoor Thermostat R Low Ambient Control and Outdoor Thermostat CLIMATE CONTROL OPTIONS X None D Electronic Prog Man Auto H Electronic Prog Man Auto with CO2 B Electronic Prog Humidistat BACNet C Electronic Prog Humidistat BACNet CO2 MODEL NU...

Page 5: ...3 C0Z C06 C09 C15 460 3 1 1 1 1 13 22 27 27 15 25 30 30 14 10 10 10 14 10 10 10 Q48H3 A0Z A05 A10 A15 230 208 1 1 1 or 2 1 or 2 1 or 2 35 60 85 85 50 70 90 90 8 6 4 4 10 8 8 8 35 35 35 25 50 50 50 50 50 25 50 50 8 8 8 10 8 8 10 10 10 10 10 10 Q48H3 B0Z B06 B09 B15 230 208 3 1 1 1 1 28 47 56 56 40 50 60 60 8 8 6 6 10 10 10 10 Q48H3 C0Z C06 C09 C15 460 3 1 1 1 1 15 24 28 28 20 25 30 30 12 10 10 10 1...

Page 6: ...Manual 2100 652A Page 6 of 42 FIGURE 1 Unit Dimensions ...

Page 7: ...emoved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid see Figure 3 B The unit can be tipped forward and slid down the edge of the skid until the front wheels touch the ground see Figure 3 C The wheels will not roll They are shipped from the factory locked so they will not roll The back of the skid will have to be h...

Page 8: ...se instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in...

Page 9: ...Manual 2100 652A Page 9 of 42 FIGURE 6 Ducted Application FIGURE 5 Installation with Duct Free Plenum ...

Page 10: ...ucted and either free blow with the use of QPB Plenum Box or a duct supply air system The QPB and QPBHW Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for ducted airflow is used When used with a ducted supply a QCX Cabinet Extension can be used to conceal...

Page 11: ...through the floor or through the wall If the drain is to be routed through an unconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to remove the unit from the wall When the side drain is used the plug must be removed and installed in the rear drain outlet The rear drain can be used with wall thickness of up to 10 where a ...

Page 12: ...dard Rear Drain FIGURE 9 Optional Side Drain Side View Q TEC UNIT Water Trap FIGURE 11 Rear Drain Top View Wall maximum 10 for rear drain Couplings not shown but recommended for ease of removability for service Sleeve Drain Line Wall Bracket Unit ...

Page 13: ...Manual 2100 652A Page 13 of 42 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A ...

Page 14: ...4 PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLUG INSTALLED IN SIDE Q Tec DRAIN MIS 2470 FIGURE 12B IMPORTANT ...

Page 15: ...Manual 2100 652A Page 15 of 42 MIS 2471 A REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR FIGURE 12C If used ...

Page 16: ...MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN BUT AT A SLIGHT COOLING PERFORMANCE REDUCTION OF 2 3 MIS 2472 A FIGURE 12D ...

Page 17: ...E 13B Unit Mounting Method 2 FIGURE 13A Unit Mounting Method 1 Bottom Trim Piece Bottom Trim Extension Mounting Bracket Side Trim 2 PCS Side Trim 2 PCS Cabinet Side Panel Enlarged view of mounting bracket showing sleeve to cabinet attachment Mounting Bracket 8 Screw Provided Light Color Wall Sleeve 10 Hex Head Screw Provided ...

Page 18: ...ides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim up under the rollers with sheets of steel or any substance that is not affected by moisture 5 Make sure the gasket on the rear of the unit is touching the sleeve across the top and down both sides This...

Page 19: ...ic heat there may be two field power circuits required If this is the case the unit serial plate will so indicate All models are suitable only for connection with copper wire Each unit and or wiring diagram will be marked Use Copper Conductors Only These instructions MUST BE adhered to Refer to the National Electrical Code NEC for complete current carrying capacity data on the various insulation g...

Page 20: ... m e f i 2 W G e z i g r e n E n o i t a l i t n e V 1 O G e z i g r e n E t a e H y c n e g r e m E E 2 W B e z i g r e n E CAUTION Do not plug in or unplug blower motor connectors while the power is on Failure to do so may result in motor failure control options If the climate control option is abandoned and connections are made directly to P2 both pins 6 and 1 of P2 must be energized for proper...

Page 21: ...403 084 VT8600U5000B 2 stage Cool 2 stage Heat Programmable Non Programmable Electronic HP or Conventional Auto or Manual changeover with BACnet CSB9E THO 3 stage Cool 3 stage Heat Programmable Non Programmable Electronic HP or Conventional Auto or Manual changeover with Humidity Control BACnet MS TP or Ethernet Connection CSB9E THOC 3 stage Cool 3 stage Heat Programmable Non Programmable Electron...

Page 22: ... B SC W1 W1 E SC A SC 8 9 3 CS9BE THO 1 6 4 Thermostat Bard Part 8403 084 Factory installed jumper Terminal Block 9 10 6 5 3 11 8 Plug 2 1 12 7 2 4 G Low Voltage 1 Jumper E to W2 on the low voltage terminal block when using the 8403 084 thermostat with unit with 15 KW 1 1 2 1 2 FIGURE 17A Remote Thermostat Wiring Diagram X Thermostat Option NOTE On Option X field provided means to control ventilat...

Page 23: ...ontroller 4 2 Terminal Block Plug 2 10 4 COM 3 11 8 1 Out Part 8403 067 5 9 Low Voltage Mount relay in low voltage terminal block compartment 12 7 2 Relay is field installed and required if demand ventilation 3 2 signal O1 is supplied 1 Analog HOT 24 VAC 3 6 5 2 control does not supply blower G signal when ventilation 6 G 1 MIS 2688 C 4 4 Jumper W2 to W3 at terminal block when using 8403 084 with ...

Page 24: ...d White Blue 9 W1 E 10 6 Temp and Humidity Controller PART 8403 060 5 Black White G O B 3 11 8 4102 060 R Y1 Plug 2 C W2 1 Yellow 12 Red Yellow Brown 7 Orange A Brown White 4 FIGURE 18 Unit Mounted Thermostat Wiring Diagram D Thermostat Option ...

Page 25: ...ite G O B 3 11 8 4102 059 A R Y1 Plug 2 C 1 Yellow 12 Red Yellow Brown 7 A Brown White 2 Out 24 VAC Red White Brown White 4 W2 Orange Red White 4 CO2 Controller W1 E 2 1 Red White 6 5 1 4 10 Controller Part 8201 062 COM Part 8403 067 Relay 2 HOT 6 3 3 Black White 5 FIGURE 19 Unit Mounted Thermostat Wiring Diagram H Thermostat Option ...

Page 26: ...low Orange Red White Plug 2 4102 078 Orange 8 12 9 Black White Blue 3 6 Red Yellow Brown 11 10 4 W2 A SC SC W1 E G O B R Y1 C SC Temp and Humidity Controller B CS9BE THO C CS9BE THOC FIGURE 20 Unit Mounted Thermostat Wiring Diagram B or C Thermostat Option ...

Page 27: ...tiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrigerant it must come out of...

Page 28: ...r damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compressor contactor is allowed to energize If phases are reversed the red fault LED will be lit and compressor operation is inhibited If a fault condition occurs reverse two of the supply leads to the unit D...

Page 29: ... the top center screw only from the cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease in pulling unit out from the wall it may be desirable to remove the bottom service door which requires removal of the return air panel Grip the front flange of the base pan and pull straight out 7 Annual maintenanc...

Page 30: ...p and the bottom can be pulled toward the front of the unit and removed VENT OPTIONS Barometric Fresh Air Damper Standard Before starting make sure the power has been turned off The return air grille panel must be removed The fresh air damper assembly can be seen on the back of the unit see Figure 21 1 The fresh air damper is attached to the back of the unit with one screw on either side of the as...

Page 31: ...Manual 2100 652A Page 31 of 42 FIGURE 21 Fresh Air Damper Removal MOUNTING SCREW ...

Page 32: ...Manual 2100 652A Page 32 of 42 FIGURE 22 QERV Removal MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS ...

Page 33: ... and starting compressor and outdoor motor R G also makes starting indoor blower motor PRESS UP AND DOWN ARROWS TO ENTER CONFIGURATION MODE USE ARROWS TO SELECT SETTING PUSH MIDDLE BUTTON TO CHANGE CONTROLLER WILL SHOW SET NOTE MENU JUMPER MUST BE SET TO ON TO CHANGE ANY SETTINGS WITH THE FRONT BUTTONS TO LOCK THE CO2 CONTROLLER MOVE JUMPER TO OFF AFTER IT HAS BEEN CONFIGURED Settings Recommended ...

Page 34: ...the first 30 60 120 or 180 seconds of Y operation After this period expires the control will then monitor the low pressure switch input normally to make sure that the switch is closed during Y operation PRESSURE SERVICE PORTS High and low pressure service ports are installed on all units so that the system operating pressures can be observed Pressure tables covering all models can be found on page...

Page 35: ...o reset which at that point then allows the compressor to be restarted as long as the 5 minute short cycle timer has run out If the high pressure switch trips a third time within 1 hour the unit is in hard lockout indicating something is wrong and it will not restart itself 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACC...

Page 36: ... Check for 24V between RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not go into defrost heating only Temperature sensor or heat pump control defective Disconnect temperature sensor from board and jumper across SPEEDUP terminals and SEN JMP terminals This should cause th...

Page 37: ...74 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0 13820 102 0 5570 11 0 122089 27 0 37652 65 0 13474 103 0 5446 10 0 118108 28 0 36583 66 0 13137 104 0 5326 9 0 114272 29 0 35548 67 0 12810 105 0 5208 8 0 110575 30 0 34545 68 0 12492 106 0 5094 7 0 1070...

Page 38: ...if it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop filter Check correct duct restrictions Symptom Cause Procedure Noisy blower or cabinet Check for loose blower housing panels etc High static creating high blower speed...

Page 39: ...inal location and orientation d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVAC equipment and verify that the new motor control module is working properly Follow the manufacturer s procedures for disposition of the old control module Figure 25 Figure 24 Figure 26 Figu...

Page 40: ...NSION A INCHES All Q H3 Models 750 Model Rated ESP Max ESP Rated CFM Optional CFM Continuous CFM CFM Max ESP Q24H3 n 10 0 5 800 N A 800 700 Q30H3 15 0 8 1000 N A 1000 910 Q36H3 15 0 8 1200 1000 1000 1175 Q43H3 15 0 8 1200 1000 1000 1175 Q48H3 15 0 8 1400 1100 1100 1175 Q60H3 20 0 5 1550 1250 1100 1400 NOTE These units are equipped with a variable speed ECM indoor motor that automatically adjusts i...

Page 41: ...de 124 333 127 353 130 374 133 397 135 420 137 446 138 471 139 498 140 527 141 557 80 DB 67 WB Low Side High Side 133 342 136 362 139 384 142 407 144 431 146 457 148 483 149 511 150 541 151 571 85 DB 72 WB Low Side High Side 138 354 141 375 144 397 147 421 149 446 151 473 153 500 154 529 155 560 156 591 Q48H3 75 DB 62 WB Low Side High Side 120 337 122 362 123 385 125 410 128 436 130 461 132 488 13...

Page 42: ...6 33 264 43 272 52 281 61 289 69 298 78 307 85 317 92 327 99 337 106 347 112 358 117 369 Q48H3 70 Low Side High Side 171 241 123 254 85 266 56 278 36 289 26 300 25 310 34 320 52 329 80 338 117 346 163 354 219 362 Q60H3 70 Low Side High Side 38 253 40 262 42 271 46 280 50 288 56 297 62 305 69 313 78 321 87 329 97 337 109 344 121 352 TABLE 10 Heating Pressure All Temperatures in Degrees F Low side p...

Reviews: