Manual 2100-652A
Page
42 of 42
MODEL
RETURN
AIR
TEMP.
PRESSURE
AIR TEMPERATURE ENTERING OUTDOOR COIL
0°
5°
10°
15°
20°
25°
30°
35°
40°
45°
50°
55°
60°
Q24H3
70
Low Side
High Side
35
284
42
290
49
297
57
304
64
313
72
322
79
331
86
342
94
353
101
365
109
378
117
392
124
406
Q30H3
70
Low Side
High Side
28
279
38
284
47
289
55
296
63
303
71
311
78
320
85
329
91
339
97
350
103
362
108
375
112
388
Q36H3
70
Low Side
High Side
34
275
41
276
47
278
54
281
61
285
68
289
74
295
81
303
88
311
95
320
101
330
108
341
115
353
Q43H3
70
Low Side
High Side
22
256
33
264
43
272
52
281
61
289
69
298
78
307
85
317
92
327
99
337
106
347
112
358
117
369
Q48H3
70
Low Side
High Side
171
241
123
254
85
266
56
278
36
289
26
300
25
310
34
320
52
329
80
338
117
346
163
354
219
362
Q60H3
70
Low Side
High Side
38
253
40
262
42
271
46
280
50
288
56
297
62
305
69
313
78
321
87
329
97
337
109
344
121
352
TABLE 10
Heating Pressure
(All Temperatures in Degrees F)
Low side pressure ± 4 psig
High side pressure ± 10 psig
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the
system, the charge should be removed, system evacuated and recharged to serial plate instructions.
75°F outdoor temperature condenser fan motor is running on low speed.