Module
Notes
Output Integer 128
Allowed in slots 7-9, Module Identifier= 0x42
Output Integer 64
Allowed in slots 7-9, Module Identifier= 0x43
Example Configuration
Table 28: Example configuration for slots and modules
Slot
Module
Description
Slot 1
Input Integer 512
The two input integer modules have a total of 640 bytes (320 Modbus registers)
The data will come from DXM Local Registers 1 through 320
Slot 2
Input Integer 128
Slot 4
Input Float 128
The input Floating register module has a total of 128 byes (64 Modbus registers)
Since it takes two Modbus registers to make a 32-bit floating value, there will be 32
floating point values coming from Local Registers 1001-1064
Slot 7
Output Integer 64
The output integer 64 module has a total of 64 bytes (32 Modbus registers).
The data will come from the PLC and be put into DXM Local Registers 5001 through
5032
9.5 Configuration Instructions
9.5.1 Install the GSD File
Although these instructions are specific for the Siemens TIA Portal (v14) software, you may use these instructions as a basis
for installing the GSD file into another controller.
2. Launch the Siemens TIA Portal (v14) software.
3. Click
Open existing project
.
4. Select a project and open it.
5. After the project is uploaded, click
Devices & networks
.
Figure 45. Devices and networks screen
6. Click
Configure networks
.
Sure Cross
®
DXM700-Bx Wireless Controller
60
www.bannerengineering.com - Tel: + 1 888 373 6767