Important:
The software only loads a file to the DXM. Internal parameter settings that are changed in the
tool but not saved to the file will not be sent to the device.
Modify Multiple Registers
Modify a range of registers from the
Local Registers
>
Local Registers in Use
>
Modify Multiple Registers
screen.
Select which parameter fields to modify. Most parameters have three selections.
•
Unchanged—no changes
•
Default—change to default settings
•
Set—modify parameter. Other selections will appear based on the parameter.
Figure 9. Modify Multiple Registers screen
1. Enter the
Starting register
and
Ending register
.
2. Select the value to change using the drop-down list next to each value.
3. Enter the new value in the field provided.
4. To push register values to the web server, set
Cloud Permissions
to read.
If the
Cloud Permissions
are set to Read, the web server only views data from the device and cannot write data to
the device. If the permissions are set to Write, the web server only writes to the device and cannot read the data. If
the permissions are set to Read/Write, the web server can read the data from the device and write to the device from
the web.
5. Click
Modify Registers
to save and apply the changes.
Define an RTU Read Rule
Follow these steps to create a new read rule.
This example screen shows a read rule created to read six registers (address 1 through 6), from Modbus Slave 4. The results
are stored in the Local Registers 1 through 6.
Figure 10. Read Rules - Configuration Example
1. From the
Register Mapping
>
RTU
>
RTU Read
screen, click
Add Read Rule
.
2. Click the arrow next to the name to display the parameters.
3. Name your rule.
4. Select the slave ID.
5. Select how many registers to read, and the beginning register.
6. Define the register type, how often to read the register, and any other appropriate parameters.
7. If necessary, select the error condition. For this example, if the read function fails after three attempts, the read rule
writes 12345 to the DXM local registers. Notice the list of local register names this read rule is using.
Sure Cross
®
DXM700-Bx Wireless Controller
www.bannerengineering.com - Tel: + 1 888 373 6767
15