Figure 50. Online & diagnostics menu and screen
The
Online & diagnostics
windows displays.
13. Select
Assign IP address
under
Functions
.
14. Click
Accessible devices
.
The Select device window searches the network for available devices.
15. Determine the device to be adjusted via the MAC address and select it.
16. Click
Apply
.
The IP address for the device is updated.
17. Click
Assign IP address
to complete the step.
This step is completed for every device.
By default, each DXM shipped from the factory is assigned the IP address 192.168.0.1.
Immediately after the PROFINET protocol is enabled, the DXM has an IP address of 0.0.0.0. We recommend using the TIA
Portal to give the DXM an IP address so that the address is saved in the unit. When the PLC powers up, this IP address is
accessible. The PLC can change the IP address if it is configured to do so.
If the PLC assigns the DXM IP address (for example, using the Set IP address in the project option in Siemens TIA Portal),
the DXM receives the specified address, but only after the program has been loaded into the PLC and is running. If the DXM
is restarted after it was discovered and configured by the PLC, the DXM retains the IP address that was assigned to it using
the LCD or software until after the PLC discovers the DXM and assigns it the specified address again. However, if this
address is different than what is specified in the PLC, the DXM reverts to the address specified in the PLC after the PLC
becomes active again.
These configuration options conform to the PROFINET standard.
9.5.3 Change the Device Name
Follow these instructions to change the name of the DXM using the Siemens TIA Portal (v14) software. Use these
instructions as a basis if you are using another controller (PLC).
1. Open a project and click on
Devices & networks
.
The Network view displays.
2. Right-click on the DXM icon and select
Assign device name
.
The
Assign PROFINET device name
window displays. The software searches for devices of the same type.
Sure Cross
®
DXM700-Bx Wireless Controller