2.5 Wiring Diagrams
Use the following drawings to correctly wire power and I/O to the SureCross Wireless radio devices. For more information
about wiring sensors to the SureCross devices, refer to
Sensor Connections
.
2.5.1 Apply Power to the Gateway or Node
Integral 5-pin M12/Euro-style quick disconnect wiring depends on the model and power requirements of the device. Not all
models can be powered by 10 to 30 V dc and not all models can be powered by 3.6 to 5.5 V dc. Refer to
Specifications
to
verify the power requirements of your device.
5-pin M12
Pin
Wire Color
Gateway (10 to 30 V dc) Node (10 to 30 V dc)
Node (FlexPower)
1
4
5
3
2
1
brown
10 to 30 V dc input
10 to 30 V dc
2
white
RS485 / D1 / B / +
3
blue
dc common (GND)
dc common (GND)
dc common (GND)
4
black
RS485 / D0 / A / -
5
gray
Comms gnd
3.6 to 5.5 V dc 1
1. Apply power to the Gateway by connecting the 10 to 30 V dc cable as shown.
The Gateway begins in RUN mode, displays the current network ID (NID), then identifies itself as a Gateway.
2. Apply power to the Node by connecting the 10 to 30 V dc cable or the DX81 Battery Supply Module as shown. To
apply power to a FlexPower Node with an integrated battery, install the battery into the housing.
The Node starts in RUN mode, displays the current network ID, then identifies itself as a Node and lists its device ID.
2.5.2 DX80...C Wiring
Wiring power to the DX80...C models varies depending the power requirements of the model. Connecting dc power to the
communication pins (Tx/Rx) causes permanent damage. For
Flex
Power devices, do not apply more than 5.5 V to the B+
terminal.
Terminal Label
Gateway and DX85
10 to 30 V dc Powered Nodes
Battery Powered Nodes
V+
10 to 30 V dc
10 to 30 V dc
Tx/+
RS485 / D1 / B / +
V–
dc common (GND)
dc common (GND)
dc common (GND)
Rx/–
RS485 / D0 / A / -
B+
3.6 to 5.5 V dc
2.5.3 Industrial Ethernet Wiring
Use the 4-pin industrial Ethernet connection to connect the radio network to an Ethernet-based host system.
4-pin Industrial Ethernet Connector
Pin
Wire Color
Description
1
4
3
2
1
White/orange
+ Tx
2
White/blue
+Rx
3
Orange
–Tx
4
Blue
–Rx
1 For FlexPower devices, do not apply more than 5.5 V dc to the gray wire.
Sure Cross
®
Performance DX80 Wireless I/O Networks
www.bannerengineering.com - Tel: + 1 888 373 6767
9