2 Features
The following feature callouts refer to the DX80 Gateway and Node models, the GatewayPro, and the DX83 Ethernet Bridge.
The wiring diagrams include information for connection power and sensors using the 5-pin Euro-style connect, the terminal
wiring board, and the Industrial Ethernet connection on the DX83 and GatewayPro.
2.1 DX80 Gateway and Node Components
The DX80 Gateway and Node use the same housing and include the same physical features.
1
2
3
4
5
6
7
1. Port, NPT gland, or plug. If unused, install the provided plug into the
1/2 NPT threaded port. Refer to the Installation section if an IP67 seal
is required.
2. Rotary switch 1 (left). In Rotary Dial Addressing Mode, sets the
Network ID (NID) to a hexidecimal value from 0 to F, for a total of 16
Network IDs. A Gateway and its corresponding Nodes must be
assigned the same Network ID.
Rotary switch 2 (right). On the Gateway, sets the Gateway’s LCD
viewing device address. The Gateway is predefined as Device Address
0. On the Node, sets the Node’s Device Address (hexidecimal 1 to F).
Each Node within a network must have a unique Node Device Address.
3. Push button 1. Single-click to advance across all top-level DX80
menus. Single-click to move down interactive menus, once a top-level
menu is chosen. Button 1 is also used to wake integrated battery
models from the hibernation mode they ship in.
4. Push button 2. Double-click to select a menu and to enter manual
scrolling mode. Double-click to move up one level at a time.
5. LED 1 and 2. Provide real-time feedback to the user regarding RF link status, serial communications activity, and the
error state.
6. LCD Display. Six-character display provides run mode user information and shows enabled I/O point status. This
display allows the user to conduct a Site Survey (RSSI) and modify other DX80 configuration parameters without the use
of a PC or other external software interfaces. On the Node, after 15 minutes of inactivity, the LCD goes blank. Press any
button to refresh the display.
7. 5-Pin M12 Euro-style quick-disconnect serial port
2.2 DX80 Gateway and Node Wiring Chamber
The DX80 Gateway and Node use the same housing and terminal block for wiring.
1
2
3
4
5
1. Housing. The rugged, industrial DX80 housing meets IEC
IP67 standards.
2. Mounting hold, #10/M5 clearance. Mounting Holes accept
metric M5 or UNC/UNF #10 hardware -- DIN rail mount adapter
bracket available.
3. Wiring terminal strip. The 16 spring-clip type wiring terminals
accept wire sizes: AWG 12-28 or 2.5 sq mm.
4. Port, PG-7 gland or blank. The PG-7 threaded ports can
accept provided cable glands or blanks.
5. Ribbon connector. Ribbon cable connects wiring base to
LCD/radio.
Sure Cross
®
Performance DX80 Wireless I/O Networks
www.bannerengineering.com - Tel: + 1 888 373 6767
7