4 Electrical
Installation
and
Testing
WARNING: Read this
Section
Carefully Before Installing the System
If all
mounting,
installation,
interfacing, and checkout procedures are not followed properly, the Banner device
cannot provide the
protection
for which it was designed. The user has the responsibility to ensure that all local,
state, and
national
laws, rules, codes, or
regulations
relating
to the
installation
and use of this control system in
any
particular
application
are
satisfied.
Ensure that all legal requirements have been met and that all technical
installation
and maintenance
instructions
contained in this manual are followed.
The user has the sole responsibility to ensure that this Banner device is installed and interfaced to the guarded
machine by
Qualified
Persons
3
, in accordance with this manual and applicable safety
regulations.
The following are the main steps to electrically install the EZ-SCREEN Type 2 components and interface with the guarded machine:
1. Apply power to each
emitter/receiver
pair (see
on page 23)
2. Perform and
Initial
on page 25)
3. Make all electrical interface
connections
to the guarded machine (see
29)
4. Perform a commissioning checkout procedure (see
on page 41)
4.1
Routing
Cordsets
Connect the QD connectors and route the sensor cables to the
junction
box, electrical panel, or other enclosure in which the Interface
Module, the redundant mechanically linked interposing relays, FSDs, or other safety-related parts of the control system are located. This
must be done per local wiring code for low-voltage dc control cables and may require
installation
of electrical conduit. See
page 46 for
selection
of Banner-supplied cordsets.
The EZ-SCREEN Type 2 is designed and manufactured to be highly resistant to electrical noise and to operate reliably in industrial
settings.
However, extreme electrical noise may cause a random Trip or Latch
condition;
in extreme cases, a Lockout is possible.
Emitter
and receiver wiring is low voltage;
routing
the sensor wires alongside power wires, motor/servo wires, or other high-voltage wiring may
inject noise into the EZ-SCREEN Type 2 System. It is good wiring
practice
(and may be required by code) to isolate
emitter
and receiver
cables from high-voltage wires, avoid
routing
cables close to “noisy” wiring, and provide a good
connection
to earth ground.
Sensor QD cabling and any interconnect wiring should meet the following
specifications.
The wires used should have an
insulation
temperature
rating
of at least 90 °C (194 °F).
Table 1: Maximum Machine Interface cable length versus total current draw (including both OSSD loads)
Cable Size
Current Draw
0.5 A
0.75 A
1.0 A
1.25 A
0.823 mm2 (18 AWG)
375
ft
250
ft
188
ft
148
ft
0.518 mm2 (20 AWG)
240
ft
160
ft
120
ft
95
ft
0.326 mm2 (22 AWG)*
150
ft
100
ft
75
ft
59
ft
Note: Cable length includes power (+24 V dc) and return (0 V dc) wires at +25 °C, and is intended to ensure that adequate power
is available to the EZ-SCREEN Type 2 System when the supply is
operating
at +24 V dc - 10%.
4.2
Initial
Electrical
Connections
WARNING: Proper Electrical Hookup
Electrical hookup must be made by
Qualified
Personnel and must comply with NEC
(National
Electrical Code) and
local standards. Make no more
connections
to the EZ-SCREEN Type 2 System than are described in this manual.
Connection
of other wiring or equipment to the EZ-SCREEN Type 2 System could result in serious bodily injury or
death.
Lockout/tagout procedures may be required (refer to OSHA1910.147, ANSI Z244-1, ISO 14118, or the appropriate standard for
controlling hazardous energy). Following relevant electrical standards and wiring codes, such as the NEC, NFPA79 or IEC60204-1, always
connect the earth ground (green/yellow wire). Do not operate the EZ-SCREEN Type 2 without an earth ground
connection.
Make the electrical
connections
in the order described in this
section.
Do not remove end-caps; no internal
connections
are to be made.
All
connections
are made through the M12 Euro-style quick-disconnects.
3
A person who, by possession of a recognized degree or
certificate
of professional training, or who, by extensive knowledge, training and experience, has
successfully demonstrated the ability to solve problems
relating
to the subject
matter
and work.
EZ-SCREEN
®
Type 2 Light Screen
www.bannerengineering.com - Tel: 763.544.3164