
3.1.3 Supplemental Safeguarding
on page 11, the EZ-SCREEN Type 2 must be properly
positioned
such that an individual cannot reach through the
defined
area and access the hazard point before the machine has
stopped.
Additionally,
the hazard cannot be accessible by reaching around,
under, or over the
defined
area. To accomplish this, supplemental
guarding (mechanical barriers, such as screens or bars), as
described by ANSI B11.19 safety requirements or other
appropriate standards, must be installed. Access will then be
possible only through the
defined
area of the EZ-SCREEN Type 2
System or through other safeguarding that prevents access to the
hazard (see
The mechanical barriers used for this purpose are typically called
"hard
(fixed)
guarding"; there must be no gaps between the hard
(fixed)
guarding and the
defined
area. Any openings in the hard
(fixed)
guarding must comply with the safe opening requirements
of ANSI B11.19 or other appropriate standard.
Figure 4. An example of supplemental safeguarding
on page 15 shows an example of supplemental safeguarding inside a
robotic
work cell. The EZ-SCREEN Type 2, in
conjunction
with the hard
(fixed)
guarding, is the primary safeguard. Supplemental safeguarding (such as a horizontal-mounted safety light screen as
an area guard) is required in areas that cannot be viewed from the reset switch (for example, behind the robot and the conveyor).
Additional
supplemental safeguarding may be required to prevent clearance or trapping hazards (for example, a safety mat as an area
guard between the robot, the turntable, and the conveyor).
WARNING: The Hazard Must Be Accessible Only through the
Defined
Area
The
installation
of the EZ-SCREEN Type 2 must prevent any individual from reaching around, under, over or
through the
defined
area and into the hazard without being detected. Mechanical barriers (for example, hard
(fixed)
guarding) or supplemental safeguarding may be required to comply with this requirement, and is described
by ANSI B11.19 safety requirements or other appropriate standards.
3.1.4 Other
Considerations
Reset Switch
Location
The reset switch must be mounted at a
location
that complies with the warning and guidelines below. If any hazardous areas are not
in view from the switch
location,
additional
means of safeguarding must be provided. The switch should be protected from accidental or
unintended
actuation
(for example, through the use of rings or guards).
A key-actuated reset switch provides some operator or supervisory control, as the key can be removed from the switch and taken into
the guarded area. However, this does not prevent unauthorized or inadvertent resets due to spare keys in the possession of others, or
additional
personnel entering the guarded area
unnoticed.
When considering where to locate the reset switch, follow the guidelines
below.
WARNING: Reset Switch
Location
When considering where to locate the reset switch, you must follow the guidelines outlined in this
section.
If any areas within the guarded area are not visible from the reset switch,
additional
safeguarding must be
provided, as described by the ANSI B11.19 series or other appropriate standards.
Failure to follow these
instructions
could result in serious injury or death.
All reset switches must be:
• Outside the guarded area
• Located to allow the switch operator a full, unobstructed, view of the
entire
guarded area while the reset is performed
• Out of reach from within the guarded area
• Protected against unauthorized or inadvertent
operation
(such as through the use of rings or guards).
EZ-SCREEN
®
Type 2 Light Screen
www.bannerengineering.com - Tel: 763.544.3164
15