background image

LED 1

LED 2

Gateway Status

 (flashing yellow)

Modbus Communication Active

 (flashing red)

Modbus Communication Error

For Gateway and Ethernet Bridge systems, active Modbus communication refers to the communication between the Gateway and the Ethernet Bridge. For GatewayPro
systems, the Modbus communication LEDs refer to the communication internal to the GatewayPro. For Gateway only systems, the Modbus communication LEDs refer to
the communication between the Gateway and its host system (if applicable).

Modbus Register Table

I/O

Modbus Holding Register

I/O Type

Units

I/O Range

Holding Register Rep-
resentation

Terminal

Block Labels

Gateway or

DX85

Any Node

Min. Value Max. Val-

ue

Min.
(Dec.)

Max.
(Dec.)

1

1

1 + (Node# × 16)

Discrete IN 1

-

0

1

0

1

DI1

2

2

2 + (Node# × 16)

Discrete IN 2

-

0

1

0

1

DI2

3

3

3 + (Node# × 16)

Discrete IN 3

-

0

1

0

1

DI3

4

4

4 + (Node# × 16)

Discrete IN 4

-

0

1

0

1

DI4

5

5

5 + (Node# × 16)

Analog IN 1

mA
V

0.0
0.0

20.0
10.0

0

65535

AI1

6

6

6 + (Node# × 16)

Analog IN 2

mA
V

0.0
0.0

20.0
10.0

0

65535

AI2

7

7

7 + (Node# × 16)

Reserved

8

8

8 + (Node# × 16)

Device Message

9

9

9 + (Node# × 16)

Discrete OUT 1

-

0

1

0

1

DO1

10

10

10 + (Node# × 16)

Discrete OUT 2

-

0

1

0

1

DO2

11

11

11 + (Node# × 16)

Discrete OUT 3

-

0

1

0

1

DO3

12

12

12 + (Node# × 16)

Discrete OUT 4

-

0

1

0

1

DO4

13

13

13 + (Node# × 16)

Analog OUT 1

mA

0.0

20.0

0

65535

AO1

14

14

14 + (Node# × 16)

Analog OUT 2

mA

0.0

20.0

0

65535

AO2

15

15

15 + (Node# × 16)

Control Message

16

16

16 + (Node# × 16)

Reserved

Specifications

Radio

General

Radio Range

900 MHz (1 Watt): Up to 9.6 kilometers (6 miles) *
2.4 GHz: Up to 3.2 kilometers (2 miles) *

Radio Transmit Power

900 MHz (1 Watt): 30 dBm conducted (up to 36 dBm EIRP)
2.4 GHz: 18 dBm conducted, less than or equal to 20 dBm EIRP

900 MHz Compliance (1 Watt Radios)

FCC ID UE3RM1809: This device complies with FCC Part 15, Subpart
C, 15.247
IC: 7044A-RM1809

2.4 GHz Compliance

FCC ID UE300DX80-2400 - This device complies with FCC Part 15,
Subpart C, 15.247
ETSI/EN: In accordance with EN 300 328: V1.7.1 (2006-05)
IC: 7044A-DX8024

Power*

Requirements: +10 to 30V dc (For European applications: +10 to 24V dc,
± 10%). (See UL section below for any applicable UL specifications)
900 MHz Consumption: Maximum current draw is <100 mA and typical
current draw is <50 mA at 24V dc. (2.4 GHz consumption is less.)

Housing

Polycarbonate housing and rotary dial cover; polyester labels; EDPM
rubber cover gasket; nitrile rubber, non-sulphur cured button covers
Weight: 0.26 kg (0.57 lbs)
Mounting: #10 or M5 (SS M5 hardware included)
Max. Tightening Torque: 0.56 N·m (5 lbf·in)

Antenna Connection

Ext. Reverse Polarity SMA, 50 Ohms
Max Tightening Torque: 0.45 N·m (4 lbf·in)

Interface

Indicators: Two bi-color LEDs

 

 

SureCross Performance Gateway

6

www.bannerengineering.com - tel: 763-544-3164

P/N 155861 Rev. D

Summary of Contents for DX80G9M6S-P2

Page 1: ...arameters when a host system is not part of the wireless network The UCT requires a special USB to RS 485 model number BWA UCT 900 for 1 Watt radios BWA HW 006 can be used for all other radios converter cable to pass information between your comput er and the Gateway Download the most recent revisions of the UCT software from Banner Engi neering s website http www bannerengineering com wireless Se...

Page 2: ...h Settings Switches Device Settings 1 2 3 4 5 6 7 8 900 MHz transmit power level 1 Watt 30 dBm OFF 900 MHz transmit power level 250 mW 24 dBm DX80 com patibility mode ON Modbus or UCT configured overrides DIP switches 3 8 OFF DIP switch configured ON Inputs sourcing PNP OFF Inputs sinking NPN ON Link loss output zero OFF OFF Link loss output one OFF ON Link loss output hold last state ON OFF Link ...

Page 3: ...m you have selected the correct resistor to cut Step 2 Launch the User Configuration Tool software Step 3 Change the units parameter for this particular input on this device Gateway or Node to use voltage instead of milliamps Refer to the Modbus Register table for the I O number for each analog input Writing a four 4 to the Units parameter defines the units as 0 to 10V Writ ing a two 2 to the Unit...

Page 4: ...0 A B 3 6 to 5 5V dc Connecting dc power to the communication pins will cause permanent damage For FlexPower devices do not apply more than 5 5V to the gray wire Terminal Block IP20 This is the terminal block for the DX80 M6S P2C models G B W DO4 TX RX DO3 V AO2 AO1 DO2 DO1 DI2 DI1 AI2 AI1 V V V DI3 DI4 A1 A2 AIx or Ax Analog IN x AOx Analog OUT x DIx Discrete IN x DOx Discrete OUT x GND Ground dc...

Page 5: ... Pow ered Sensors AIx PWR 10 30V dc GND sensor dc common AIx GND dc common external power sensor AIx SPx GND sensor dc common Only possible in models with switch power SPx out puts Wiring Diagrams for Analog Outputs Connecting dc power to the communication pins will cause permanent damage Do not exceed analog input ratings for analog inputs Only connect sensor outputs to analog inputs Analog Outpu...

Page 6: ...Analog OUT 1 mA 0 0 20 0 0 65535 AO1 14 14 14 Node 16 Analog OUT 2 mA 0 0 20 0 0 65535 AO2 15 15 15 Node 16 Control Message 16 16 16 Node 16 Reserved Specifications Radio General Radio Range 900 MHz 1 Watt Up to 9 6 kilometers 6 miles 2 4 GHz Up to 3 2 kilometers 2 miles Radio Transmit Power 900 MHz 1 Watt 30 dBm conducted up to 36 dBm EIRP 2 4 GHz 18 dBm conducted less than or equal to 20 dBm EIR...

Page 7: ...erproofing instructions Operating the devices at the maximum operating conditions for extended periods can shorten the life of the de vice Ratings Rating for DX80 models IEC IP67 NEMA 6 See UL section below for any applicable UL specifications Rating for DX80 C models IEC IP20 NEMA 1 Operating Temperature 40 to 85 C Electronics 20 to 80 C LCD Operating Humidity 95 max relative non condensing Radia...

Page 8: ...ESS FOR A PARTICULAR PURPOSE AND WHETHER ARISING UNDER COURSE OF PERFORMANCE COURSE OF DEALING OR TRADE USAGE This Warranty is exclusive and limited to repair or at the discretion of Banner Engineering Corp replacement IN NO EVENT SHALL BANNER ENGINEERING CORP BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS EXPENSES LOSSES LOSS OF PROFITS OR ANY INCIDENTAL CONSE QUENTIAL OR SP...

Reviews: