background image

Following a radio link time-out, all outputs linked to the Node in question are set to de-energize (discrete outputs to zero, analog outputs to 0 mA or 4 mA), energize
(discrete outputs to one, analog outputs to 20 mA), or to hold the last stable state/value. Use the DIP switches to select the link loss output state.
Modbus/User Configuration Tool (UCT) or DIP Switch Configured
In Modbus/UCT Configured mode, the device parameters are changed using the User Configuration Tool (UCT) or a Modbus command. All DIP switch positions are
ignored. In DIP Switch Configured mode, use the DIP switches to configure the parameters listed in the table.
Transmit Power Levels
The 900 MHz radios can be operated at 1 watt (30 dBm) or 250 mW (24 dBm). While the radios operate in 1 Watt mode, they cannot communicate with 150 mW DX80
radio devices. To communicate with the 150 mW radio models, operate this radio in 250 mW mode. For 2.4 GHz radios, this DIP switch is disabled. The transmit power for
2.4 GHz is fixed at about 100 mW EIRP (18 dBm), making the 2.4 GHz Performance models automatically compatible with the DX80 2.4 GHz models.

Configuring Universal Analog Inputs for mA or V

To configure inputs to use 0 to10V instead of 0 to 20mA, remove the installed resistors from the marked locations on the wiring board. For example, to make analog input 1
a 0 to 10V input, follow these instructions.

G B − W +

A1

A2

A3

A4

Remove resistor in A1 slot
to make analog IN 1 a 0-10V input.

Step 1. Cut out the resistor installed in the A1 (analog 1) slot. (Your wiring board may differ
slightly from the board shown. Use the board's labels to confirm you have selected the correct
resistor to cut.)
Step 2. Launch the User Configuration Tool software.
Step 3. Change the units parameter for this particular input on this device (Gateway or Node)
to use voltage instead of milliamps. Refer to the Modbus Register table for the I/O number for
each analog input. Writing a four (4) to the Units parameter defines the units as 0 to 10V. Writ-
ing a two (2) to the Units parameter defines the units as 0 to 20 mA.

Note that a 220 ohm 0.1% resistor must be installed for a 0 to 20mA input. The resistor must be removed for an input defined as a 0 to 10V input.

Mixing Performance and Non-Performance Radios in the Same Network

To comply with federal regulations, the 150 mW radios and 1 Watt radios communicate differently. To mix Performance radios with non-Performance radios:

• Performance radios must operate in 250 mW mode, not 1 Watt mode (DIP switch 1 ON)
• Non-Performance radios must be set to use Extended Address Mode (DIP switch 1 ON)

For more detailed instructions about setting up your wireless network, refer to the Quick Start Guide, Banner document number 128185. For more information about using
Performance and non-Performance radios within the same network, refer the technical note titled Mixing Performance Radios and 150 mW Radios in the Same Net-
work
listed on the FAQ/Knowledgebase section of Banner's Wireless Sensor Networks website.

Wiring Your SureCross

®

 Device

Use the following wiring diagrams to first wire the sensors and then apply power to the SureCross devices.

5-pin Euro-Style Hookup

Wiring the 5-pin Euro-style connector depends on the model and power requirements of the device. Connecting dc power to the communication pins will cause permanent
damage.

SureCross Performance Gateway

 

 

P/N 155861 Rev. D

www.bannerengineering.com - tel: 763-544-3164

3

Summary of Contents for DX80G9M6S-P2

Page 1: ...arameters when a host system is not part of the wireless network The UCT requires a special USB to RS 485 model number BWA UCT 900 for 1 Watt radios BWA HW 006 can be used for all other radios converter cable to pass information between your comput er and the Gateway Download the most recent revisions of the UCT software from Banner Engi neering s website http www bannerengineering com wireless Se...

Page 2: ...h Settings Switches Device Settings 1 2 3 4 5 6 7 8 900 MHz transmit power level 1 Watt 30 dBm OFF 900 MHz transmit power level 250 mW 24 dBm DX80 com patibility mode ON Modbus or UCT configured overrides DIP switches 3 8 OFF DIP switch configured ON Inputs sourcing PNP OFF Inputs sinking NPN ON Link loss output zero OFF OFF Link loss output one OFF ON Link loss output hold last state ON OFF Link ...

Page 3: ...m you have selected the correct resistor to cut Step 2 Launch the User Configuration Tool software Step 3 Change the units parameter for this particular input on this device Gateway or Node to use voltage instead of milliamps Refer to the Modbus Register table for the I O number for each analog input Writing a four 4 to the Units parameter defines the units as 0 to 10V Writ ing a two 2 to the Unit...

Page 4: ...0 A B 3 6 to 5 5V dc Connecting dc power to the communication pins will cause permanent damage For FlexPower devices do not apply more than 5 5V to the gray wire Terminal Block IP20 This is the terminal block for the DX80 M6S P2C models G B W DO4 TX RX DO3 V AO2 AO1 DO2 DO1 DI2 DI1 AI2 AI1 V V V DI3 DI4 A1 A2 AIx or Ax Analog IN x AOx Analog OUT x DIx Discrete IN x DOx Discrete OUT x GND Ground dc...

Page 5: ... Pow ered Sensors AIx PWR 10 30V dc GND sensor dc common AIx GND dc common external power sensor AIx SPx GND sensor dc common Only possible in models with switch power SPx out puts Wiring Diagrams for Analog Outputs Connecting dc power to the communication pins will cause permanent damage Do not exceed analog input ratings for analog inputs Only connect sensor outputs to analog inputs Analog Outpu...

Page 6: ...Analog OUT 1 mA 0 0 20 0 0 65535 AO1 14 14 14 Node 16 Analog OUT 2 mA 0 0 20 0 0 65535 AO2 15 15 15 Node 16 Control Message 16 16 16 Node 16 Reserved Specifications Radio General Radio Range 900 MHz 1 Watt Up to 9 6 kilometers 6 miles 2 4 GHz Up to 3 2 kilometers 2 miles Radio Transmit Power 900 MHz 1 Watt 30 dBm conducted up to 36 dBm EIRP 2 4 GHz 18 dBm conducted less than or equal to 20 dBm EIR...

Page 7: ...erproofing instructions Operating the devices at the maximum operating conditions for extended periods can shorten the life of the de vice Ratings Rating for DX80 models IEC IP67 NEMA 6 See UL section below for any applicable UL specifications Rating for DX80 C models IEC IP20 NEMA 1 Operating Temperature 40 to 85 C Electronics 20 to 80 C LCD Operating Humidity 95 max relative non condensing Radia...

Page 8: ...ESS FOR A PARTICULAR PURPOSE AND WHETHER ARISING UNDER COURSE OF PERFORMANCE COURSE OF DEALING OR TRADE USAGE This Warranty is exclusive and limited to repair or at the discretion of Banner Engineering Corp replacement IN NO EVENT SHALL BANNER ENGINEERING CORP BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS EXPENSES LOSSES LOSS OF PROFITS OR ANY INCIDENTAL CONSE QUENTIAL OR SP...

Reviews: