background image

• SureCross Wireless I/O Network Manual: 

132607

• Web Configurator Manual (used with "Pro" and DX83 models): 

134421

• Host Configuration Manual 

132114

Configuring the DIP Switches

Before making any changes to the DIP switch positions, disconnect the power. For devices with batteries integrated into the housing, remove the battery for at least one
minute. DIP switch changes will not be recognized if power isn't cycled to the device.
For parameters not set via DIP switches, use the User Configuration Tool (UCT) to make configuration changes. For parameters set using the DIP switches, the DIP switch
positions override any changes made using the User Configuration Tool.

Accessing the Internal DIP Switches

To access the internal DIP switches, follow these steps:

1. Unscrew the four screws that mount the cover to the bottom housing.
2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.
3. Gently unplug the ribbon cable from the board mounted into the bottom housing. For integrated battery models (no ribbon cable) and Class I, Division 2 certified

devices (ribbon cable is glued down), skip this step.

4. Remove the black cover plate from the bottom of the device's cover.

The DIP switches are located behind the rotary dials.

After making the necessary changes to the DIP switches, place the black cover plate back into position and gently push into place. Plug
the ribbon cable in after verifying that the blocked hole lines up with the missing pin. Mount the cover back onto the housing.

DIP Switch Settings

Switches

Device Settings

1

2

3

4

5

6**

7

8

900 MHz transmit power level: 1 Watt (30 dBm)

OFF*

900 MHz transmit power level: 250 mW (24 dBm), DX80 com-
patibility mode

ON

Modbus or UCT configured (overrides DIP switches 3-8)

OFF*

DIP switch configured

ON

Inputs sourcing (PNP)

OFF*

Inputs sinking (NPN)

ON

Link loss output: zero

OFF*

OFF*

Link loss output: one

OFF

ON

Link loss output: hold last state

ON

OFF

Link loss output: user configuration

ON

ON

0–20 mA scale **

OFF*

4–20 mA scale **

ON

* Default configuration
** Not used when configured for 0-10V I/O.
Analog Input and Output Scale
Use the DIP switch to select which current scale to use for all the device's analog inputs and outputs: 0 to 20 mA or 4 to 20 mA. When using a 4-20 mA sensor with a 0-20
mA input, the sensor uses the 4-20 mA section of the total range. Using a 4-20 mA with a 0-20 mA input allows you to determine when you have an error condition with the
sensor. A normal input reading between 4 and 20 mA indicates a functioning sensor whereas a value below 4 mA indicates an error condition, such as a broken wire or
loose connection. This DIP switch is used only on the 0 to 20 mA models, not the 0 to 10V models.
Discrete Input Type
Select the type of discrete input sensors to use with this device: sourcing (PNP) sensors or sinking (NPN) sensors.
Link Loss Outputs
The SureCross DX80 wireless devices use a deterministic radio link time-out method to address RF link interruption or failure. When a radio link fails, all pertinent wired
outputs are sent to defined states until the link is recovered, ensuring that disruptions in the communications link result in predictable system behavior.

 

 

SureCross Performance Gateway

2

www.bannerengineering.com - tel: 763-544-3164

P/N 155861 Rev. D

Summary of Contents for DX80G9M6S-P2

Page 1: ...arameters when a host system is not part of the wireless network The UCT requires a special USB to RS 485 model number BWA UCT 900 for 1 Watt radios BWA HW 006 can be used for all other radios converter cable to pass information between your comput er and the Gateway Download the most recent revisions of the UCT software from Banner Engi neering s website http www bannerengineering com wireless Se...

Page 2: ...h Settings Switches Device Settings 1 2 3 4 5 6 7 8 900 MHz transmit power level 1 Watt 30 dBm OFF 900 MHz transmit power level 250 mW 24 dBm DX80 com patibility mode ON Modbus or UCT configured overrides DIP switches 3 8 OFF DIP switch configured ON Inputs sourcing PNP OFF Inputs sinking NPN ON Link loss output zero OFF OFF Link loss output one OFF ON Link loss output hold last state ON OFF Link ...

Page 3: ...m you have selected the correct resistor to cut Step 2 Launch the User Configuration Tool software Step 3 Change the units parameter for this particular input on this device Gateway or Node to use voltage instead of milliamps Refer to the Modbus Register table for the I O number for each analog input Writing a four 4 to the Units parameter defines the units as 0 to 10V Writ ing a two 2 to the Unit...

Page 4: ...0 A B 3 6 to 5 5V dc Connecting dc power to the communication pins will cause permanent damage For FlexPower devices do not apply more than 5 5V to the gray wire Terminal Block IP20 This is the terminal block for the DX80 M6S P2C models G B W DO4 TX RX DO3 V AO2 AO1 DO2 DO1 DI2 DI1 AI2 AI1 V V V DI3 DI4 A1 A2 AIx or Ax Analog IN x AOx Analog OUT x DIx Discrete IN x DOx Discrete OUT x GND Ground dc...

Page 5: ... Pow ered Sensors AIx PWR 10 30V dc GND sensor dc common AIx GND dc common external power sensor AIx SPx GND sensor dc common Only possible in models with switch power SPx out puts Wiring Diagrams for Analog Outputs Connecting dc power to the communication pins will cause permanent damage Do not exceed analog input ratings for analog inputs Only connect sensor outputs to analog inputs Analog Outpu...

Page 6: ...Analog OUT 1 mA 0 0 20 0 0 65535 AO1 14 14 14 Node 16 Analog OUT 2 mA 0 0 20 0 0 65535 AO2 15 15 15 Node 16 Control Message 16 16 16 Node 16 Reserved Specifications Radio General Radio Range 900 MHz 1 Watt Up to 9 6 kilometers 6 miles 2 4 GHz Up to 3 2 kilometers 2 miles Radio Transmit Power 900 MHz 1 Watt 30 dBm conducted up to 36 dBm EIRP 2 4 GHz 18 dBm conducted less than or equal to 20 dBm EIR...

Page 7: ...erproofing instructions Operating the devices at the maximum operating conditions for extended periods can shorten the life of the de vice Ratings Rating for DX80 models IEC IP67 NEMA 6 See UL section below for any applicable UL specifications Rating for DX80 C models IEC IP20 NEMA 1 Operating Temperature 40 to 85 C Electronics 20 to 80 C LCD Operating Humidity 95 max relative non condensing Radia...

Page 8: ...ESS FOR A PARTICULAR PURPOSE AND WHETHER ARISING UNDER COURSE OF PERFORMANCE COURSE OF DEALING OR TRADE USAGE This Warranty is exclusive and limited to repair or at the discretion of Banner Engineering Corp replacement IN NO EVENT SHALL BANNER ENGINEERING CORP BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS EXPENSES LOSSES LOSS OF PROFITS OR ANY INCIDENTAL CONSE QUENTIAL OR SP...

Reviews: