• SureCross Wireless I/O Network Manual:
132607
• Web Configurator Manual (used with "Pro" and DX83 models):
134421
• Host Configuration Manual
132114
Configuring the DIP Switches
Before making any changes to the DIP switch positions, disconnect the power. For devices with batteries integrated into the housing, remove the battery for at least one
minute. DIP switch changes will not be recognized if power isn't cycled to the device.
For parameters not set via DIP switches, use the User Configuration Tool (UCT) to make configuration changes. For parameters set using the DIP switches, the DIP switch
positions override any changes made using the User Configuration Tool.
Accessing the Internal DIP Switches
To access the internal DIP switches, follow these steps:
1. Unscrew the four screws that mount the cover to the bottom housing.
2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.
3. Gently unplug the ribbon cable from the board mounted into the bottom housing. For integrated battery models (no ribbon cable) and Class I, Division 2 certified
devices (ribbon cable is glued down), skip this step.
4. Remove the black cover plate from the bottom of the device's cover.
The DIP switches are located behind the rotary dials.
After making the necessary changes to the DIP switches, place the black cover plate back into position and gently push into place. Plug
the ribbon cable in after verifying that the blocked hole lines up with the missing pin. Mount the cover back onto the housing.
DIP Switch Settings
Switches
Device Settings
1
2
3
4
5
6**
7
8
900 MHz transmit power level: 1 Watt (30 dBm)
OFF*
900 MHz transmit power level: 250 mW (24 dBm), DX80 com-
patibility mode
ON
Modbus or UCT configured (overrides DIP switches 3-8)
OFF*
DIP switch configured
ON
Inputs sourcing (PNP)
OFF*
Inputs sinking (NPN)
ON
Link loss output: zero
OFF*
OFF*
Link loss output: one
OFF
ON
Link loss output: hold last state
ON
OFF
Link loss output: user configuration
ON
ON
0–20 mA scale **
OFF*
4–20 mA scale **
ON
* Default configuration
** Not used when configured for 0-10V I/O.
Analog Input and Output Scale
Use the DIP switch to select which current scale to use for all the device's analog inputs and outputs: 0 to 20 mA or 4 to 20 mA. When using a 4-20 mA sensor with a 0-20
mA input, the sensor uses the 4-20 mA section of the total range. Using a 4-20 mA with a 0-20 mA input allows you to determine when you have an error condition with the
sensor. A normal input reading between 4 and 20 mA indicates a functioning sensor whereas a value below 4 mA indicates an error condition, such as a broken wire or
loose connection. This DIP switch is used only on the 0 to 20 mA models, not the 0 to 10V models.
Discrete Input Type
Select the type of discrete input sensors to use with this device: sourcing (PNP) sensors or sinking (NPN) sensors.
Link Loss Outputs
The SureCross DX80 wireless devices use a deterministic radio link time-out method to address RF link interruption or failure. When a radio link fails, all pertinent wired
outputs are sent to defined states until the link is recovered, ensuring that disruptions in the communications link result in predictable system behavior.
SureCross Performance Gateway
2
www.bannerengineering.com - tel: 763-544-3164
P/N 155861 Rev. D