background image

Radio

General

Spread Spectrum Technology

FHSS (Frequency Hopping Spread Spectrum)

Link Timeout

Gateway: Configurable
Node: Defined by Gateway

* With the 2 dB antenna that ships with the product. High-gain antennas are availa-
ble, but the range depends on the environment and line of sight. To determine the
range of your wireless network, perform a Site Survey.

Buttons: Two
Display: Six character LCD

Wiring Access

DX80 models: Four PG-7, One 1/2-inch NPT, One 5-pin Euro-style male
connector
DX80...C models: External terminals

* For European applications, power the DX80 from a Limited Power Source as de-
fined in EN 60950-1.

Inputs

Outputs

Discrete Inputs

Four, DIP switch selectable between sourcing/PNP and sinking/NPN
Rating: 3 mA max current at 30V dc
Sample Rate: 62.5 milliseconds
Report Rate: On change of state

Discrete Input ON Condition

PNP: Greater than 8V
NPN: Less than 0.7V

Discrete Input OFF Condition

PNP: Less than 5V
NPN: Greater than 2V or open

Analog Inputs

Two, 0 to 20mA (default) or 0 to 10V (user configurable)
Rating (mA): 24 mA
Rating (V): 10V
Impedance: 220 Ohms
Sample Rate: 62.5 milliseconds
Report Rate: 1 second or On Change of State (1% change in value)
Accuracy: 0.2% of full scale +0.01% per °C
Resolution: 12-bit

Discrete Outputs

Four sourcing/PNP
Update Rate: 125 milliseconds
ON Condition: Supply minus 2V
OFF Condition: Less than 2V
Output State Following Timeout: OFF

Discrete Output Rating (PNP)

100 mA max current at 30V dc
ON-State Saturation: Less than 3V at 100 mA
OFF-state Leakage: Less than 10 μA

Analog Outputs

Two, 0 to 20 mA
Update Rate: 125 milliseconds
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit

Communication

Environmental

Hardware (RS-485)

Interface: 2-wire half-duplex RS-485
Baud rates: 9.6k, 19.2k (default), or 38.4k
Data format: 8 data bits, no parity, 1 stop bit

Protocol

Modbus RTU

Refer to the SureCross

®

 DX80 Wireless I/O Network product manual, Banner p/n

132607, for installation and waterproofing instructions. Operating the devices at the
maximum operating conditions for extended periods can shorten the life of the de-
vice.

Ratings

Rating for DX80 models: IEC IP67; NEMA 6; (See UL section below for
any applicable UL specifications)
Rating for DX80...C models: IEC IP20; NEMA 1
Operating Temperature: −40 to +85° C (Electronics); −20 to +80° C
(LCD)
Operating Humidity: 95% max. relative (non-condensing)
Radiated Immunity: 10 V/m, 80-2700 MHz (EN61000-6-2)

Shock and Vibration

IEC 68-2-6 and IEC 68-2-7
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz

Included with Model

The following items ship with the DX80 radios.

• BWA-HW-002: DX80 Access Hardware Kit, containing four PG-7 plastic threaded plugs, four PG-7 nylon gland fittings, four PG-7 hex nuts, one 1/2-inch NPT plug, and

one 1/2-inch nylon gland fitting. (Not included with IP20 DX80...C models)

• BWA-HW-001: Mounting Hardware Kit, containing four M5-0.8 x 25mm SS screws, four M5-0.8 x 16mm SS screws, four M5-0.8mm SS hex nuts, and four #8-32 x 3/4"

SS bolts

• BWA-HW-003: PTFE tape
• BWA-9O2-C (900 MHz) or BWA-2O2-C (2.4 GHz): Antenna, 2 dBd Omni, Rubber Swivel RP-SMA Male. (Not included with Internal antenna models)
• Quick Start Guide (128185 for DX80 Gateways or 152653 for MultiHop models)
• MQDC1-506: 5-Euro (single ended) straight cable, 2m (Not included with FlexPower devices)
• BWA-HW-011: IP20 Screw Terminal Headers (2 pack) (Included only with the IP20 DX80...C models)

Warnings

The manufacturer does not take responsibility for the violation of any warning listed in this document. Make no modifications to this product. Any modifications to this
product not expressly approved by Banner Engineering could void the user’s authority to operate the product. All specifications published in this document are subject
to change.
 Banner reserves the right to modify product specifications or to update documentation at any time. For the most recent version of any documentation, refer to: 

www.bannerengineering.com

©

 2006-2013 Banner Engineering Corp. All rights reserved.

SureCross Performance Gateway

 

 

P/N 155861 Rev. D

www.bannerengineering.com - tel: 763-544-3164

7

Summary of Contents for DX80G9M6S-P2

Page 1: ...arameters when a host system is not part of the wireless network The UCT requires a special USB to RS 485 model number BWA UCT 900 for 1 Watt radios BWA HW 006 can be used for all other radios converter cable to pass information between your comput er and the Gateway Download the most recent revisions of the UCT software from Banner Engi neering s website http www bannerengineering com wireless Se...

Page 2: ...h Settings Switches Device Settings 1 2 3 4 5 6 7 8 900 MHz transmit power level 1 Watt 30 dBm OFF 900 MHz transmit power level 250 mW 24 dBm DX80 com patibility mode ON Modbus or UCT configured overrides DIP switches 3 8 OFF DIP switch configured ON Inputs sourcing PNP OFF Inputs sinking NPN ON Link loss output zero OFF OFF Link loss output one OFF ON Link loss output hold last state ON OFF Link ...

Page 3: ...m you have selected the correct resistor to cut Step 2 Launch the User Configuration Tool software Step 3 Change the units parameter for this particular input on this device Gateway or Node to use voltage instead of milliamps Refer to the Modbus Register table for the I O number for each analog input Writing a four 4 to the Units parameter defines the units as 0 to 10V Writ ing a two 2 to the Unit...

Page 4: ...0 A B 3 6 to 5 5V dc Connecting dc power to the communication pins will cause permanent damage For FlexPower devices do not apply more than 5 5V to the gray wire Terminal Block IP20 This is the terminal block for the DX80 M6S P2C models G B W DO4 TX RX DO3 V AO2 AO1 DO2 DO1 DI2 DI1 AI2 AI1 V V V DI3 DI4 A1 A2 AIx or Ax Analog IN x AOx Analog OUT x DIx Discrete IN x DOx Discrete OUT x GND Ground dc...

Page 5: ... Pow ered Sensors AIx PWR 10 30V dc GND sensor dc common AIx GND dc common external power sensor AIx SPx GND sensor dc common Only possible in models with switch power SPx out puts Wiring Diagrams for Analog Outputs Connecting dc power to the communication pins will cause permanent damage Do not exceed analog input ratings for analog inputs Only connect sensor outputs to analog inputs Analog Outpu...

Page 6: ...Analog OUT 1 mA 0 0 20 0 0 65535 AO1 14 14 14 Node 16 Analog OUT 2 mA 0 0 20 0 0 65535 AO2 15 15 15 Node 16 Control Message 16 16 16 Node 16 Reserved Specifications Radio General Radio Range 900 MHz 1 Watt Up to 9 6 kilometers 6 miles 2 4 GHz Up to 3 2 kilometers 2 miles Radio Transmit Power 900 MHz 1 Watt 30 dBm conducted up to 36 dBm EIRP 2 4 GHz 18 dBm conducted less than or equal to 20 dBm EIR...

Page 7: ...erproofing instructions Operating the devices at the maximum operating conditions for extended periods can shorten the life of the de vice Ratings Rating for DX80 models IEC IP67 NEMA 6 See UL section below for any applicable UL specifications Rating for DX80 C models IEC IP20 NEMA 1 Operating Temperature 40 to 85 C Electronics 20 to 80 C LCD Operating Humidity 95 max relative non condensing Radia...

Page 8: ...ESS FOR A PARTICULAR PURPOSE AND WHETHER ARISING UNDER COURSE OF PERFORMANCE COURSE OF DEALING OR TRADE USAGE This Warranty is exclusive and limited to repair or at the discretion of Banner Engineering Corp replacement IN NO EVENT SHALL BANNER ENGINEERING CORP BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS EXPENSES LOSSES LOSS OF PROFITS OR ANY INCIDENTAL CONSE QUENTIAL OR SP...

Reviews: