Wire No.
Wire Color
Description
1
2
3
4
5
1
Brown
10 to 30V dc
2
White
RS485 / D1 / B / +
3
Blue
dc common (GND)
4
Black
RS485 / D0 / A / –
5
Gray
Comms Gnd
Terminal Block (IP67)
This is the terminal block for the DX80**M6S-P2 models.
G B − W +
A1
A2
GND
PWR
PWR
GND
AO2
AO1
DO4
DO3
DO2
DO1 DI1
DI2
DI3
DI4
AI1
AI2
AIx or Ax. Analog IN x.
AOx. Analog OUT x.
DIx. Discrete IN x.
DOx. Discrete OUT x.
GND. Ground/dc common connection.
PWR. Power, 10 to 30V dc power connection.
DX80...C Wiring
Wiring power to the DX80...C models varies depending the power requirements of the model.
Terminal Label
Gateway, DX85 *
10 to 30V dc Powered Nodes
Battery Powered Nodes **
V+
10 to 30V dc
10 to 30V dc
Tx/+
RS485 / D1 / B / +
V-
dc common (GND)
dc common (GND)
dc common (GND)
Rx/-
RS485 / D0 / A / -
B+
3.6 to 5.5V dc
* Connecting dc power to the communication pins will cause permanent damage.
** For FlexPower devices, do not apply more than 5.5V to the gray wire.
Terminal Block (IP20)
This is the terminal block for the DX80**M6S-P2C models.
G
B
−
W
+
DO4
TX/+
RX/
−
DO3
V+
AO2
AO1
DO2
DO1
DI2
DI1
AI2
AI1
V
−
V+
V
−
DI3
DI4
A1
A2
AIx or Ax. Analog IN x.
AOx. Analog OUT x.
DIx. Discrete IN x.
DOx. Discrete OUT x.
GND. Ground/dc common connection.
PWR. Power, 10 to 30V dc power connection.
RX/-. Serial comms line
TX/+. Serial comms line
V+. Power, 10 to 30V dc power connection.
V-. Ground/dc common connection.
Wiring Diagrams for Discrete Inputs
Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram refers to V+ on the wiring board and
GND in the wiring diagram refers to V- on the wiring board.
SureCross Performance Gateway
4
www.bannerengineering.com - tel: 763-544-3164
P/N 155861 Rev. D