TECHNICAL SPECIFICATIONS
MODEL
TBML 50MC
NATURAL GAS MAX. THERMAL POWER
kW
500
NATURAL GAS MIN. THERMAL POWER
kW
100
¹) NATURAL GAS EMISSIONS
mg/kWh
Class III
NATURAL GAS OPERATION
Two-stage progressive / modulating
NATURAL GAS MAX. HEATING CAPACITY
Stm³/h
52.9
NATURAL GAS MIN. HEATING CAPACITY
Stm³/h
10.6
NATURAL GAS MIN. PRESSURE
mbar
22.5
NATURAL GAS MAX PRESSURE
mbar
360
PROPANE GAS MAX. THERMAL POWER
kW
500
PROPANE GAS MIN. THERMAL POWER
kW
120
PROPANE GAS MAX. HEAT CAPACITY
Stm³/h
20.45
PROPANE GAS MIN. HEAT CAPACITY
Stm³/h
4.9
PROPANE GAS MIN PRESSURE
mbar
19.5
PROPANE GAS MAX PRESSURE
mbar
360
2
) PROPANE EMISSIONS
mg/kWh
Classe III
DIESEL OIL MAX. HEATING CAPACITY
kg/h
42.15
DIESEL OIL MIN. HEATING CAPACITY
kg/h
16.9
DIESEL OIL MAX THERMAL POWER
kW
500
DIESEL OIL MIN. THERMAL POWER
kW
200
³) DIESEL EMISSIONS
mg/kWh
Class II
DIESEL VISCOSITY
5.5 cst/20°C - 1.5° E / 20°C
DIESEL OPERATION
Two-stage
50 Hz FAN MOTOR
kW
0.65
50Hz FAN MOTOR RPM
r.p.m.
2830
60Hz FAN MOTOR
kW
0.65
50 Hz IGNITION TRANSFORMER
26 kV - 48 mA - 230 V
60 Hz IGNITION TRANSFORMER
26 kV - 48 mA - 230 V
VOLTAGE 50Hz
3N ~ 400 V ± 10%
VOLTAGE 60Hz
3N ~ 380 V ± 10%
50Hz* ELECTRICAL POWER
kW
1.1
60Hz* ELECTRICAL POWER
kW
1.1
DEGREE OF PROTECTION
IP 40
EQUIPMENT
LME 73
SOUND PRESSURE**
dBA
75
CO emissions, natural gas/propane ≤ 100 mg/kWh
* Total absorption at start with ignition transformer on.
The measurement has been carried out in Baltur's laboratory, in accordance with EN 150361 standard.
** Acoustic pressure measured one meter behind the equipment, with burner operating at maximum rated heat input, it refers to
Baltur's laboratory environment conditions and cannot be compared to measurements carried out in different locations.
*** Acoustic pressure was obtained characterizing Baltur's laboratory with a sample source, this measurement has an accuracy
of class 2 (engineering class) with a standard deviation f 1.5 dB(A).
Calorific power lower than reference conditions 15° C, 1013 mbar:
Diesel oil: Hi = 11.86 kWh/kg = 42.70 Mj/kg
Natural gas: Hi = 9.45 kWh/Stm³ = 34.02 Mj/Stm³
Lower calorific power:
Propane gas: Hi = 24.44 kWh/Stm³ = 88.00 Mj/Stm³
For different types of gas and pressure values, please contact our sales department.
Summary of Contents for TBML 50MC
Page 2: ......
Page 43: ...ITALIANO 41 44 0006160003_201510 SCHEMI ELETTRICI ...
Page 44: ...ITALIANO 42 44 0006160003_201510 ...
Page 45: ...ITALIANO 43 44 0006160003_201510 ...
Page 87: ...ENGLISH 41 44 0006160003_201510 WIRING DIAGRAMS ...
Page 88: ...ENGLISH 42 44 0006160003_201510 ...
Page 89: ...ENGLISH 43 44 0006160003_201510 ...
Page 91: ......