RED
YELLOW
GREEN
The reset button «EK...» is the main element to access all diagnostic fun-
ctions (activation and deactivation), and serves to unlock the command
and control device.
Both «LED» and «EK...» are positioned under the transparent button. Pressing this button, you can reset the control box.
Possibility of two diagnostic functions:
1. Visual indication directly on the reset button: operation and diagnostics of device status.
2. Diagnostics with interface: in this case the OCI400 connecting cable is necessary and it can be connected to a PC with ACS400 softwa-
re, or to gas analysers of different manufacturers
Visual indication.
During operation, the command and control equipment phase is indicated on the reset button. The table lists all colour sequences and
their meaning. To activate the diagnostics function, hold the reset button down for at least 3 seconds. A quick red flashing indicates that
the function is active. Likewise, hold the reset button down for at least 3 seconds to deactivate the function (the switching will be indicated
with a flashing yellow light).
EK
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
> 3 s
7101z03e0305
Operating position
PC interface/diagnostic
analyser
Colour code table
Diagnostics
Operating position
COMMAND AND CONTROL DEVICE STATUS INDICATION.
Condition
Colour sequence
Colours
Waiting conditions TW, other intermediate statuses
. . . . . . . .
No light
Ignition phase
Intermittent yellow
Correct operation, current strength of flame detector above the mini
-
mum allowed
Green
Incorrect operation, current strength of flame detector below the mini
-
mum allowed
Intermittent green
Decrease in power supply voltage
Alternating Yellow
and Red
Burner in lock condition
Red
Fault indication (see colour legend)
Intermittent red
Extraneous light upon burner start-up
Alternating Green
and Red
Quick flashing for diagnostics
Quick flashing red
NO LIGHT.
RED. YELLOW.
GREEN.
Summary of Contents for TBML 50MC
Page 2: ......
Page 43: ...ITALIANO 41 44 0006160003_201510 SCHEMI ELETTRICI ...
Page 44: ...ITALIANO 42 44 0006160003_201510 ...
Page 45: ...ITALIANO 43 44 0006160003_201510 ...
Page 87: ...ENGLISH 41 44 0006160003_201510 WIRING DIAGRAMS ...
Page 88: ...ENGLISH 42 44 0006160003_201510 ...
Page 89: ...ENGLISH 43 44 0006160003_201510 ...
Page 91: ......