SERVOMOTOR CAMS ADJUSTMENT SQN72.6E5A20BT
Use the corresponding rings to modify the adjustment of the uti-
lized cams (I - II - III....).The index of the ring indicate on the
respective reference scale the rotation angle taken up for each
cam.
A Reference scale.
B Position indicator.
C Camshaft-motor coupling enabling/disabling pin.
I Maximum air opening regulation cam (130°)
II Total air closure (burner stopped) (0°)
III Air regulation cam for minimum gas setting (30°)
IV 1st diesel flame air regulation cam (50°)
V Cam for the activation of 2nd flame diesel oil valve (greater
than cam IV) (80°)
0002937920
A
B
C
D