14 / 18
0006081362_200806
E
N
G
L
I
S
H
ELECTRODES/IONISATION PROBE ADJUSTMENT DIAGRAM
Legend:
1- Ionisation electrode
2- Ignition electrode
3- Deflector disk
4- Mixer
5- Gas outlet pipe
Mod.
A
B
C
TBG 45 - 45P
4
5
4
TBG 60P
4
10
-
TBG 60
4
11
4
COMBUSTION HEAD AIR ADJUSTMENT
The combustion head has an adjustment device so that the air
passage between the disk and the combustion head is opened
or closed. You are thus able to obtain, closing the passage, high
pressure upstream of the disk even at low capacity. The high
speed and turbulence of the air provides for its greater penetration
into the fuel and therefore an excellent mixture and flame stability.
It may be necessary to have high air pressure before the disk to
prevent flame fluctuations, particularly essential when the burner
works on the combustion chamber that is pressurized and/or at a
high thermal load.
It is clear from the above that the device that closes the air to the
blast-pipe must be set at a position such as to always obtain very
high air pressure behind the disk. It is advisable to adjust in such
a way as to obtain a closure of the air at the combustion head that
will require a significant opening of the air damper that regulates
the aspiration flow from the burner fan. This must of course be the
case when the burner is working at maximum desired supply.
In practice you have to start the adjustment with the device that
closes the air at the combustion head in an intermediate position,
switching on the burner for approximate adjustment as explained
previously.
When the maximum desired supply has been reached, the
position of the device that closes the air at the combustion head is
corrected, moving it forward and backwards, until the right amount
of air is flowing to the supply, with the air damper in significantly
open.
0002935680