14 / 22
0006081533_201403
ENGLISH
X= Combustion head-disk distance; adjust the distance X following
the indications below:
a) loosen screw 1
b) turn screw 2 to position the combustion head 3, referring to
index 4.
c) adjust the distance X between minimum and maximum
according the indications in the table.
!
The above adjustments are indicative only; position the
combustion head according to the characteristics of the
combustion chamber
BURNER
X
Value indicated by
index 4
TBG 45ME
3 ÷31
0 ÷ 3.2
TBG 60ME
6÷ 34
0 ÷ 3.2
COMBUSTION HEAD ADJUSTMENT DIAGRAM
fig. 1
fig-2
MAINTENANCE
Analyse combustion gases and check that the emission values are
correct at least once a year, in compliance with current law.
Check the fuel filter: if it is dirty, replace it.
Check that all components of the combustion head are in good
condition, have not been deformed by high temperatures and con
-
tain no impurities or deposits from the installation environment or
from poor combustion; check the efficiency of electrodes.
If it is necessary to clean the combustion head, take out its compo
-
nents according to the procedure described below:
1) Loosen the screws 1 and remove the lid 2 (figure 1).
2) Make sure that mobile plate 3 is held in place by screw 4.
Once the maintenance operations have been completed, this
will make it possible to return the mixer assembly to the same
position it was in last time it was adjusted. Loosen screw 5,
which anchors the unit’s forward movement rod to the mobile
plate (figure 2).
3) After having loosened the nut (6) remove the blocking screw
(7) of the mixer unit (figure 3).
4) Completely remove the mixing unit (8) pulling it out in the
direction shown by arrow 9, after pulling the ignition and
ionisation cables 10 out of their electrodes (figure 4).
Having completed the maintenance works, refit the combustion
head, following in reverse order the operations described above,
after having checked the correct position of the ignition and ionisa
-
tion electrodes (see 0002935682).
Summary of Contents for TBG 45 ME
Page 2: ......
Page 20: ...18 22 0006081533_201403 ENGLISH WIRING DIAGRAM TBG 45 ME 60 ME ...
Page 21: ...19 22 0006081533_201403 ENGLISH MINIMUM IONISATION CURRENT 1 4 µA ...
Page 24: ...22 22 0006081533_201403 ...
Page 42: ...18 22 0006081533_201403 ESPAÑOL DIAGRAMA ELÉCTRICO TBG 45 ME 60 ME ...
Page 43: ...19 22 0006081533_201403 ESPAÑOL CORRIENTE MÍNIMA DE IONIZACIÓN 1 4 µA ...
Page 46: ...22 22 0006081533_201403 ...
Page 64: ...18 22 0006081533_201403 FRANÇAIS SCHEMA ELECTRIQUE TBG 45 ME 60 ME ...
Page 65: ...19 22 0006081533_201403 FRANÇAIS COURANT D IONISATION MINIMUM 1 4 µA ...
Page 68: ...22 22 0006081533_201403 ...
Page 86: ...18 22 0006081533_201403 TÜRKÇE ELEKTRİK ŞEMASI TBG 45 ME 60 ME ...
Page 87: ...19 22 0006081533_201403 TÜRKÇE MİNİMUM İYONİZASYON AKIMI 1 4 µA ...
Page 90: ...22 22 0006081533_201403 ...
Page 108: ...18 22 0006081533_201403 PYCCKИИ ЭЛЕКТРИЧЕСКАЯ СХЕМА TBG 45 ME 60 ME ...
Page 109: ...19 22 0006081533_201403 PYCCKИИ МИНИМАЛЬНЫЙ ТОК ИОНИЗАЦИИ 1 4 µA ...
Page 112: ...22 22 0006081533_201403 ...
Page 130: ...18 22 0006081533_201403 中 文 电气连接 TBG 45 ME 60 ME ...
Page 131: ...19 22 0006081533_201403 中 文 最小电离电流是1 4µA ...
Page 132: ...20 22 0006081533_201403 中 文 水温 压力电极 继电器控制输入 控制输入 0 4 20mA 外部温 度探头 燃气温 度探头 可能 控制输入 0 10 V ...
Page 134: ...22 22 0006081533_201403 ...
Page 135: ......