MAINTENANCE
Analyse combustion gases and check that the emission values are
correct at least once a year, in compliance with current law.
•
Clean air dampers, the air pressure switch with pressure port and
the relevant pipe, if any.
•
Check the electrode condition. Replace them, if necessary.
•
Have the burner and the chimney cleaned by specialised personnel
(stove repairer); a clean burner is more efficient, lasts longer and
is quieter.
•
Check that the fuel filter is clean. Replace it, if necessary.
•
Check that all components of the combustion head are in good
condition, have not been deformed and are free from impurities
or deposits deriving from the installation environment and/or from
combustion.
•
Be careful during the reassembly operations to exactly centre the
gas diffuser with respect to the electrodes, making sure that they
are not earthed, which would result in the locking of the burner.
•
Analyse combustion gases and check emissions values.
If it is necessary to clean the outside of the combustion head, take out
its components according to the procedure described:
•
Undo the fastening screws (12) and remove the lid (11).
•
Make sure that the mobile plate (23) is fastened by the screw (8).
Once the maintenance operations have been completed, this will
make it possible to return the mixer assembly to the same position
it was in last time it was adjusted.Loosen the screw (24), which
anchors the unit’s forward movement rod to the mobile plate.
•
After having loosened the nut (9) remove the blocking screw (32)
of the mixer unit.