WARNING NOTES FOR THE USER HOW TO USE THE BURNER SAFELY

ELECTRICAL SUPPLY

•  The equipment is electrically safe only when it is correctly connected to an efficient ground connection carried out in accordance with current 

safety regulations. It is necessary to check this essential safety requirement. If in doubt, call for a careful electrical check by a qualified 
technicians, since the manufacturer will not be liable for any damage caused by a poor ground connection. 

•  Have qualified technicians check that the wiring is suitable for the maximum power absorption of the equipment, as indicated in the technical 

plate, making sure in particular that the diameter of cables is sufficient for the equipment’s power absorption. 

•  Adapters, multiple plugs and extension cables may not be used for the equipment’s power supply. 

•  An ominpolar switch in accordance with current safety regulations is required for the mains supply connection. 

•  The electrical supply to the burner must have neutral to ground connection. If the ionisation current has control with neutral not to ground 

it is essential to make a connection between terminal 2 (neutral) and the ground for the RC circuit. 

•  The use of any components that use electricity means that certain fundamental rules have to followed, including the following: 

  - do not touch the equipment with parts of the body that are wet or damp or with damp feet 

  - do not pull on electrical cables 
  - do not leave the equipment exposed to atmospheric agents (such as rain or sun etc.) unless there is express provision for this. 

  - do not allow the equipment to be used by children or inexpert persons. 

•  The power supply cable for the equipment not must be replaced by the user. If the cable gets damaged, switch off the equipment, and call 

only on qualified technicians for its replacement. 

•  If you decide not to use the equipment for a while it is advisable to switch off the electrical power supply to all components in the system 

that use electricity (pumps, burner, etc.).

GAS, LIGHT OIL, OR OTHER FUEL SUPPLIES 

General warning notes 

•  Installation of the burner must be carried out by qualified technicians and in compliance with current law and regulations, since incorrect 

installation may cause damage to person, animals or things, for which damage the manufacturer shall not can be held responsible. 

•  Before installation it is advisable to carry out careful internal cleaning of all tubing for the fuel feed system to remove any residues that 

could jeopardise the  proper working of the burner. 

•  For first start up of the equipment have qualified technicians carry out the following checks:

•  If you decide not to use the burner for a while, close the tap or taps that supply the fuel. 

Special warning notes when using gas 

•  Have qualified technicians check the following:

 

a) that the feed line and the train comply with current law and regulations.

 

b) that all the gas connections are properly sealed.

•  Do not use the gas pipes to ground electrical equipment. 

•  Do not leave the equipment on when it is not in use and always close the gas tap.

•  If the user of is away for some time, close the main gas feed tap to the burner.

•  If you smell gas:

 

a) do use any electrical switches, the telephone or any other object that could produce a spark;

 

b) immediately open doors and windows to create a current of air that will purify the room;

 

c) close the gas taps;

 

d) ask for the help of qualified technicians. 

•  Do not block ventilation openings in the room where there is gas equipment or dangerous situations may arise with the build up of toxic 

and explosive mixtures.

FLUES FOR HIGH EFFICIENCY BOILERS AND SIMILAR 

It should be pointed out that high efficiency boilers and similar discharge  combustion products (fumes) at relatively low temperatures into the 
flue. In the above situation, traditional flues (in terms of their diameter and heat insulation) may be suitable because the significant cooling 
of the combustion products in these permits temperatures to fall even below the condensation point. In a flue that works with condensation 
there is soot at the point the exhaust reaches the atmosphere when burning light oil or heavy oil or the presence of condensate water along 
the flue itself when gas is being burnt (methane, LPG, etc.). Flues connected to high efficiency boilers and similar must therefore be of a size 
(section and heat insulation) for the specific use to avoid such problems as those described above.

Summary of Contents for SPARKGAS 20P - 20PW

Page 1: ...truzioni per bruciatori modello Instruction for burners model Instrucci nes para quemadores modelos Mode d emploi brule r SPARKGAS20P 20PW SPARKGAS30P 30PW SPARKGAS35P 35PW 0006080480_200710 IT GB SP...

Page 2: ......

Page 3: ...rous accidents SP Antes de empezar a usar el quemador lea detenidamente el folleto ADVERTENCIAS DIRIGIDAS AL USUARIO PARA USAR CON SEGURIDAD EL QUEMADOR que va con el manual de instruc ciones y que co...

Page 4: ...ram with vaporisation 58 Adjustment diagram for servomotor 59 Air regulation principle Electrodes adjustment 60 Electric diagram 62 SOMMAIRE PAGE Caracteristiques techniques 15 Application du br leur...

Page 5: ...997 A1 2001 EN 55014 1 2000 A1 2001 A2 2002 EN 55014 2 1997 A1 2001 EN 50366 2004 A1 2006 EN 61000 3 2 2000 A2 2005 Organo di Sorveglianza secondo la Direttiva Gas 90 396 CEE CE0085 DVGW Statement of...

Page 6: ...55014 1 2000 A1 2001 A2 2002 EN 55014 2 1997 A1 2001 EN 50366 2004 A1 2006 EN 61000 3 2 2000 A2 2005 rgano de Vigilancia seg n la Directiva Gas 90 396 CEE CE0085 DVGW D claration de conformit Nous d...

Page 7: ...e si dovesse traslocare e lasciare l apparecchio assicurarsi sempre che il libretto accompagni l apparecchio in modo che possa essere consultato dal nuovo proprietario e o dall installatore Per tutti...

Page 8: ...compromettere il buon funzionamento del bruciatore Per la prima messa in funzione dell apparecchio far effettuare da personale professionalmente qualificato le seguenti verifiche a il controllo della...

Page 9: ...equipment is sold or transferred to another owner or if the owner moves and leaves the equipment make sure that the booklet always goes with the equipment so it can be consulted by the new owner and o...

Page 10: ...by qualified technicians and in compliance with current law and regulations since incorrect installation may cause damage to person animals or things for which damage the manufacturer shall not can b...

Page 11: ...sted se muda de casa y deja el aparato hay que asegurarse siempre de que el libro de instrucciones est siempre con el aparato para que pueda ser consultado por el nuevo propietario y o instalador Para...

Page 12: ...n comprometer el buen funcionamiento del quemador La primera vez que se pone en funcionamiento el aparato el personal cualificado profesionalmente tiene que controlar a la estanqueidad en el tramo int...

Page 13: ...appareil doit tre vendu ou transf r un autre propri taire ou si celui ci doit d m nager et laisser ce dernier toujours v rifier que la notice accompagne l appareil afin qu il puisse tre consulter par...

Page 14: ...le bon fonctionnement du br leur Lors de la premi re mise en service de l appareil faire effectuer les v rifications suivantes par du personnel qualifi a le contr le de l tanch it de la partie interne...

Page 15: ...PRESSURE PRESSION METANO PRESION GAZ NATUREL mbar 15 23 13 19 13 21 PRESSIONE G P L L P G PRESSURE PRESSION G P L PRESION G P L mbar 30 MOTORE MOTOR MOTEUR 230V 50Hz 250 W 2800 Giri min r p m 370 W 2...

Page 16: ...AS 20W 475 230 245 562 5 262 5 300 170 740 120 280 126 95 3 4 105 M8 130 SPARKGAS 30 490 245 245 637 275 362 200 860 170 300 135 135 1 1 4 140 175 M12 150 SPARKGAS 30W 475 230 245 625 262 5 362 200 83...

Page 17: ...bustion 11 Joint isolant 12 Bride de fixation br leur 13 Couvercle br leur 14 Vis de r glange de disque t te 15 Electrovanne gaz 1 Control box 2 Reset button 3 Fan motor 4 Manual switch 5 Connectors 6...

Page 18: ...one del gas all esterno della centrale termica un adatto riduttore di pressione Consigliamo di installare una curva direttamente sulla rampa gas del bruciatore prima di applicare il raccordo smontabil...

Page 19: ...ion pipeline Only if the gas pressure were above the maximum value allowed by regulations 400 mm W C would it be necessary to install a pressure reducer on the gas pipeline outside the heating plant W...

Page 20: ...r 2 Open the combustion air regulator to the appropriate level see air shutter control servo regulation type STA 5 B 0 36 8 3N23 and open the air passage between the head and the flame disk diffuser t...

Page 21: ...2932171 The combustion head is equipped with a regulating device which closes and opens the air passage between the disk and the head By closing the passage it s possible to achieve high pressure upst...

Page 22: ...combustion in let gate very closed The block positionisasafetyposition reached by the burner automatically when some of the components of the burners or the plant do not work pro perly It is necessar...

Page 23: ...32 63 0006080480_200710...

Page 24: ...33 63 0006080480_200710...

Page 25: ...ple valve 1st and 2nd flame 9 Regulating ring 1st flame delivery 10 Regulating knob 2nd flame delivery 11 Protective cover can be used as a knob of regulating device for the initial rapid release Note...

Page 26: ...e 8 Regulating the initial rapid release effects the 1st and 2nd opening positions of the valve Regulation of the rapid release andof the hydraulic brake modify the 1st and 2nd positions of the valve...

Page 27: ...s area and a minimum of 0 5 m2 At least one third of the entire surface of these inlets must be located in the lower part of the external wall flush with the floor 3 Requirements for liquid gas plant...

Page 28: ...e position of the electrodes ends 3 Check the setting and operation of the air pressure switch 1 Check the position of the control electrode Check the valve of the ionisation current TYPE OF IRREGULAR...

Page 29: ...aggio aria tra disco e testa svitare per chiudere 1 Elettrodo ionizzatore 2 Elettrodo accensione B head disk adjustment screw tighten to open the head disk air passage loosen to shut 1 Ionizing electr...

Page 30: ...CONEXI N V LVULA 2a LLAMA HAY QUE REGULARLA ENTRE LA LEVA DE 1a LLAMA Y DE LA 2a LLAMA 5 LEVA CLAPETA AIRE CERRADACON QUEMADOR PARADO 6 LEVA DE REGULACI N AIRE 2a LLAMA 7 CONEXIONES EL CTRICAS 8 NDIC...

Page 31: ...61 63 0006080480_200710...

Page 32: ...62 63 0006080480_200710...

Page 33: ...63 63 0006080480_200710...

Page 34: ...La Casa por lo tanto se reserva cualquier posibilitad de modificati n de datos t cnicos y otras anotaciones Ce manuel rev t caract re purement indicatif La maison se reserve la possibilit de modifier...

Reviews: