GENERAL DIAGRAM FOR INSTALLATION OF
GATE-FILTER-STABILIZER-ANTI-VIBRATION JOINT-
OPENABLE PITTING
GAS SUPPLY LINE
The general gas supply situation is illustrated here alongside The gas
train is EN 676 certified and is supplied separately from the burner.
A manual stop valve and a damper joint must be installed as indicated
in the diagram.
If the gas train has a pressure regulator not incorporated in a
monoblock valve, we recommend you following this practical
advice on the installation of accessories on the gas piping close
to the burner:
1) To prevent large pressure drops on ignition it is best if there is
a 1.5 to 2 m length of piping between the point of application
of the stabilizer or pressure reducer and the burner. This pipe
must have a diameter equal to or greater than the connector to
the burner.
2) For the better working of the pressure regulator it is advisable
to attach it to horizontal piping after the filter. The gas pressure
regulator must be adjusted while working at the maximum
capacity actually used by the burner. The delivery pressure must
be adjusted to a figure slightly lower than the maximum obtainable.
(that which is obtained when the regulation screw is turned
almost to the end); in the specific case, tightening the regulation
screw the regulator delivery pressure increases and when it is
loosened it decreases.
DOOR
BURNER
VIBRATION-PROOF
JOINT
UNION
DOOR OPENING
DIRECTION
FILTER
BALL COCK
PRESSURE STABILIZER
VIEW FROM ABOVE
SIDE VIEW
BOILER
Summary of Contents for COMIST 180
Page 2: ......
Page 36: ...34 36 0006080095_201207 ITALIANO SCHEMA ELETTRICO...
Page 38: ...36 36 0006080095_201207 ITALIANO...
Page 72: ...34 36 0006080095_201207 ENGLISH WIRING DIAGRAM...
Page 74: ...36 36 0006080095_201207 ENGLISH...
Page 108: ...34 36 0006080095_201207 ESPA OL ESQUEMA ELECTRICO...
Page 110: ...36 36 0006080095_201207 ESPA OL...
Page 144: ...34 36 0006080095_201207 FRAN AIS SCH MA LECTRIQUE...
Page 146: ...36 36 0006080095_201207 FRAN AIS...
Page 147: ......