background image

OVERALL DIMENSIONS

Ø E

Ø F

D

C

B1

B2

B

A2

A1

A

I

Ø N

I

Ø L

M

45°

45°

356901

10N2

Ø E

Ø F

D

C

B1

B2

B

A2

A1

A

TBL 18P

TBL 26P

Model

A

A1

A2

B

B1

B2

C

TBL 18P

474

248

226

343

258

85

690

TBL 26P

474

248

226

343

258

85

700

Model

D

E Ø

F Ø

I

I1

TBL 18P

100 ÷ 240

114

114

185

185

TBL 26P

100 ÷ 255

135

114

185

185

Model

M

N

TBL 18P

170 ÷ 210

M10

115

TBL 26P

170 ÷ 210

M10

115

13 / 40

0006160435_202112

ENGLISH

Summary of Contents for 35575410

Page 1: ...L BURNERS ITALIANO Manuale istruzioni per l installazione l uso e la manutenzione IT Instruction manual for installation use and maintenance EN TBL 18P TBL 26P TBL 35P TBL 35P DACA ISTRUZIONI ORIGINALI IT ORIGINAL INSTRUCTIONS IT 0006160435_202112 ...

Page 2: ......

Page 3: ...nea alimentazione combustibile liquido 16 Linea di alimentazione 16 Pompa ausiliaria 18 Primo riempimento circuito idraulico 19 Collegamenti elettrici 20 Descrizione del funzionamento 21 Accensione e regolazione 22 Controlli 23 Regolazione aria sulla testa di combustione 23 Schema di regolazione distanza disco elettrodi 24 Martinetto oscillante 26 Regolazione camme servomotore SQN72 2B4A20 27 Appa...

Page 4: ...ni standard di temperatura 25 C e 55 C Il periodo di stoccaggio è di 3 anni AVVERTENZE GENERALI Il bruciatore deve essere utilizzato in caldaie per applicazioni civili quali riscaldamento degli edifici e produzione di acqua calda sanitaria Il bruciatore NON deve essere utilizzato in cicli produttivi e processi industriali disciplinati questi ultimi dallo Standard EN 746 2 Contattare gli uffici com...

Page 5: ...seguenti operazioni Disinserire l alimentazione elettrica staccando il cavo di alimentazione dell interruttore generale Chiudere l alimentazione del combustibile attraverso la valvola manuale di intercettazione e asportare i volantini di comando dalla loro sede Rendere innocue quelle parti che potrebbero essere potenziali fonti di pericolo AVVERTENZE PER L AVVIAMENTO IL COLLAUDO L USO E LA MANUTEN...

Page 6: ...gia elettrica comporta l osservanza di alcune regole fondamentali quali non toccare l apparecchio con parti del corpo bagnate o umide e o a piedi umidi non tirare i cavi elettrici non lasciare esposto l apparecchio ad agenti atmosferici pioggia sole ecc a meno che non sia espressamente previsto non permettere che l apparecchio sia usato da bambini o da persone inesperte ll cavo di alimentazione de...

Page 7: ...ivo può essere abilitata la funzionalità di ripristino automatico rimuovendo in modo irreversibile il relativo talloncino in plastica sul dispositivo termico posto a protezione del motore ventola Nel collegamento dei cavi ai morsetti dell equipaggiamento elettrico prevedere una lunghezza maggiore del conduttore di terra in modo da garantire che non sia soggetto in alcun modo alla disconnessione ac...

Page 8: ...za Fotoresistenza Fotoresistenza Regolazione portata d aria martinetto idraulico martinetto idraulico martinetto idraulico Servomotore Temperatura aria ambiente di funzionamento C 15 40 15 40 15 40 15 40 Pressione sonora dBA 76 3 76 3 74 1 74 1 Potenza sonora dBA 88 1 88 1 85 9 85 9 Peso con imballo kg 23 5 24 29 5 28 Peso senza imballo kg 18 5 19 24 5 23 Potere calorifico inferiore Gasolio Hi 11 ...

Page 9: ...N 2 1 4 x 1 4 x 25 N 2 1 4 x 1 4 x 25 Ugelli 1 1 2 2 Connettore 7 poli 1 1 1 1 Connettore 4 poli 1 1 1 1 TARGA IDENTIFICAZIONE BRUCIATORE 1 2 3 4 5 6 7 11 14 12 Targa_descr_bru 8 9 10 13 15 1 Logo aziendale 2 Ragione sociale azienda 3 Codice prodotto 4 Modello bruciatore 5 Matricola 6 Potenza combustibili liquidi 7 Potenza combustibili gassosi 8 Pressione combustibili gassosi 9 Viscosità combustib...

Page 10: ...one portata aria comburente Oblò visualizzazione fiamma Circuito di alimentazione del combustibile composto da pompa ad ingranaggi con regolazione della pressione e valvola e di intercettazione Presa a 7 poli per l alimentazione elettrica e termostatica del bruciatore Apparecchiatura automatica di comando e controllo del bruciatore secondo normativa europea EN298 Display visualizzatore della seque...

Page 11: ...i lavoro sono ottenuti su caldaie di prova rispondenti alla norma EN267 e sono orientativi per gli accoppiamenti bruciatore caldaia Per il corretto funzionamento del bruciatore le dimensioni della camera di combustione devono essere rispondenti alla normativa vigente in caso contrario vanno consultati i costruttori Il bruciatore non deve operare al di fuori del campo di lavoro dato 9 40 0006160435...

Page 12: ...ompa combustibile liquido 11 Quadro elettrico pannello di comando 12 Motore ventola 13 Targa identificazione bruciatore QUADRO ELETTRICO 1 Apparecchiatura 2 Trasformatore d accensione 3 Contattore motore Solo con alimentazione trifase 4 Relè termico Solo con alimentazione trifase 5 Connettore 7 poli 6 Connettore 4 poli 7 Led bruciatore acceso 8 Led bruciatore in blocco 9 Pulsate di sblocco TBL 18P...

Page 13: ...one aria 10 Pompa combustibile liquido 11 Quadro elettrico pannello di comando 12 Motore ventola 13 Targa identificazione bruciatore QUADRO ELETTRICO 1 Apparecchiatura 2 Trasformatore d accensione 3 Contattore motore Solo con alimentazione trifase 4 Relè termico Solo con alimentazione trifase 5 Connettore 7 poli 6 Connettore 4 poli 7 Led bruciatore acceso 8 Led bruciatore in blocco 9 Pulsate di sb...

Page 14: ...ibile liquido 11 Quadro elettrico pannello di comando 12 Motore ventola 13 Targa identificazione bruciatore QUADRO ELETTRICO 1 Apparecchiatura 2 Trasformatore d accensione 3 Contattore motore Solo con alimentazione trifase 4 Relè termico Solo con alimentazione trifase 5 Connettore 7 poli 6 Connettore 4 poli 7 Led bruciatore acceso 8 Led bruciatore in blocco 9 Pulsate di sblocco 10 Interruttore MAR...

Page 15: ... A2 A1 A TBL 18P TBL 26P Modello A A1 A2 B B1 B2 C TBL 18P 474 248 226 343 258 85 690 TBL 26P 474 248 226 343 258 85 700 Modello D E Ø F Ø I I1 TBL 18P 100 240 114 114 185 185 TBL 26P 100 255 135 114 185 185 Modello LØ M N TBL 18P 170 210 M10 115 TBL 26P 170 210 M10 115 13 40 0006160435_202112 ITALIANO ...

Page 16: ...P DACA Modello A A1 A2 B B1 B2 C TBL 35P 460 235 225 365 260 105 795 TBL 35P DACA 460 235 225 365 260 105 795 Modello D E Ø F Ø I I1 TBL 35P 120 350 135 135 215 215 TBL 35P DACA 120 350 135 135 215 215 Modello LØ M N TBL 35P 200 245 M12 136 TBL 35P DACA 200 245 M12 136 14 40 0006160435_202112 ITALIANO ...

Page 17: ...eratore Posizionare sul canotto la guarnizione isolante 13 interponendo la corda 2 tra la flangia e guarnizione Fissare il bruciatore alla caldaia 1 tramite i prigionieri le rondelle e i relativi dadi in dotazione 7 PERICOLO ATTENZIONE Sigillare completamente con materiale idoneo lo spazio tra il cannotto del bruciatore e il foro sul refrattario all interno del portellone caldaia 15 40 0006160435_...

Page 18: ...la il filtro si collega il flessibile con l eventuale nipplo di raccordo all aspirazione della pompa del bruciatore tutti forniti a corredo del bruciatore La pompa è provvista di appositi attacchi per l inserzione degli strumenti di controllo manometro e vuotometro Per un funzionamento sicuro e silenzioso la depressione in aspirazione non deve superare i 35 cm Hg pari a 0 46 bar Le prescrizioni da...

Page 19: ...llo fra minimo livello combustibile in serbatoio e asse pompa H Diametro interno del tubo Ø 14 mm Lunghezza totale di ogni tubazione m m 1 30 1 5 35 2 35 2 5 40 3 40 IMPIANTO DI ALIMENTAZIONE IN ASPIRAZIONE 3 7 10 4 H 6 1 0002900740N3 IMPORTANTE Per eventuali organi mancanti nelle tubazioni attenersi alle norme vigenti IMPORTANTE Lunghezza totale di ogni tubazione compreso il tratto verticale Per ...

Page 20: ...are La prevalenza deve essere adeguata all impianto in questione Consigliamo una portata almeno pari alla portata della pompa del bruciatore Le tubazioni di collegamento devono essere dimensionate in funzione della portata della pompa ausiliaria Evitare assolutamente il collegamento elettrico della pompa ausiliaria direttamente al teleruttore del bruciatore SCHEMA DI PRINCIPIO CIRCUITO IDRAULICO T...

Page 21: ...del teleruttore del motore per mettere in funzione il motore stesso e quindi la pompa Attendere che la pompa abbia aspirato una quantità di lubrificante pari a uno o due bicchieri quindi fermare CON BRUCIATORE MONOFASE Chiudere l interruttore generale i termostati caldaia e sicurezza mettere quindi in funzione il motore e il trasformatore d accensione All inserzione dell elettrovalvola esporre la ...

Page 22: ...e con distanza d apertura dei contatti uguale o superiore a 3 mm per l allacciamento alla rete elettrica come previsto dalle normative di sicurezza vigenti Per i collegamenti elettrici linea e termostati vedere il relativo schema elettrico Sguainare l isolante esterno del cavo di alimentazione nella misura strettamente necessaria al collegamento evitando così che il filo possa venire a contatto co...

Page 23: ...curezza previsto dall apparecchiatura questa inserisce l elettrovalvola chiusa a riposo del 2 stadio Nel caso sia utilizzato il servomotore regolazione aria vedere regolazione camma 2 stadio nel capitolo regolazione camme servomotore L apertura della valvola di 2 stadio consente al combustibile di raggiungere l ugello del secondo stadio Contemporaneamente il pistone di comando del regolatore d ari...

Page 24: ...e la quantità di aria per il primo stadio sia leggermente scarsa in modo da assicurare un accensione perfetta anche nei casi più impegnativi Dopo aver regolato l aria per il primo stadio togliendo corrente all interruttore generale chiudere il circuito elettrico che comanda l inserzione del secondo stadio e posizionare l interruttore del quadro elettrico sul secondo stadio Nel caso il quadro elett...

Page 25: ...rmostato facendola corrispondere a quella del termometro REGOLAZIONE ARIA SULLA TESTA DI COMBUSTIONE La testa di combustione è dotata di un dispositivo di regolazione che permette di aprire o chiudere il passaggio dell aria tra il disco e la testa Chiudendo il passaggio aria si riesce così ad ottenere un elevata pressione a monte del disco anche con basse portate L elevata velocità e turbolenza de...

Page 26: ...FOSS B 60 4 50 GPH TBL 26P DANFOSS B 60 4 00 GPH TBL 26P DANFOSS B 60 2 50 GPH TBL 35P P DACA DANFOSS B 60 4 00 GPH TBL 35P P DACA DANFOSS B 60 2 50 GPH PERICOLO ATTENZIONE L utilizzo di ugelli con angolo di polverizzazione a 45 è consigliato su camere di combustione strette A B C D E TBL 18P 1 19 5 4 5 7 TBL 26P 1 19 5 4 5 7 35P P DACA 1 5 7 4 6 5 Controllare dopo ogni intervento sulla testa di c...

Page 27: ...atore alta pressione 2 fiamma 6 Aspirazione 7 Ritorno con all interno grano di by pass 8 Uscita in pressione attacco manometro e sfogo aria 1 8 9 Attacco vuotometro 1 8 10 Uscita all ugello CAUTELA AVVERTENZE La pompa viene pre regolata ad una pressione di 10 bar 1 fiamma e 18 bar 2 fiamma POMPA SUNTEC AS 47 A 7432 3 TBL 35P TBL 35P DACA 1 Elettrovalvola normalmente aperta 2 Attacco manometro e sf...

Page 28: ...o del martinetto In questo caso il corpo 1 si alza e favorisce la chiusura della serranda aria 7 Terminata la regolazione dell aria nel primo stadio bloccare le due ghiere 4 e 5 REGOLAZIONE POSIZIONE DELLA SERRANDA ARIA SECONDO STADIO Allentare il dado di bloccaggio 6 Per aumentare la portata d aria erogata nel secondo stadio agire sulla vite 5 svitandola in tal modo si allunga la corsa del piston...

Page 29: ...otazione impostato per ogni camma 1 Perno inserzione ed esclusione accoppiamento motore albero camme 2 Scala di riferimento 3 Indicatore di posizione 4 Camme regolabili I Camma regolazione aria 2 stadio 80 II Chiusura totale aria bruciatore fermo 0 III Camma regolazione aria 1 stadio 20 IV Camma inserzione valvola 2 stadio 40 III II I IV III II I IV SQN 72 2B4A20 1 2 3 4 0002935210 27 40 000616043...

Page 30: ...ificato Per attivare la funzione di diagnosi premere per almeno 3 secondi il pulsante di sblocco un lampeggio veloce di colore rosso indicherà che la funzione è attiva analogamente per disattivare la funzione basterà premere per almeno 3 secondi il pulsante di sblocco la commutazione verrà indicata con luce gialla lampeggiante EK xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx 3 s 7101z03e03...

Page 31: ...mpeggi On Assenza del segnale di fiamma alla fine del tempo di sicurezza TSA Malfunzionamento valvole combustibile Malfunzionamento rilevatore fiamma Difettosità nella taratura del bruciatore assenza di combustibile Mancata accensione difettosità trasformatore di accensione 3 lampeggi On Disponibile 4 lampeggi On Luce estranea durante la fase di accensione 5 lampeggi On Disponibile 6 lampeggi On D...

Page 32: ...nti seguendo la procedura sotto indicata Scollegare i tubini gasolio 24 dai raccordi posti sotto il gruppo testa attenzione al gocciolamento IMPORTANTE Memorizzare la posizione delle tacche della piastrina mobile 23 rispetto al riferimento presente sulla chiocciola bruciatore Una volta terminate le operazioni di manutenzione riposizionare il gruppo miscelazione nella stessa posizione a cui era sta...

Page 33: ...ANICA VERIFICA USURA E FUNZIONALITÁ INGRASSAGGIO PATTINO E VITI ANNO LEVE TIRANTI SNODI SFERICI CONTROLLO EVENTUALI USURE LUBRIFICAZIONE COMPONENTI ANNO KIT ESTRAZIONE TESTA COMBUSTIONE VERIFICA USURA E FUNZIONALITÁ ANNO LINEA COMBUSTIBILE TUBI FLESSIBILI SOSTITUZIONE 5 ANNI FILTRO POMPA PULIZIA ANNO FILTRO DI LINEA PULIZIA SOSTITUZIONE ELEMENTO FILTRANTE ANNO PARAMETRI DI COMBUSTIONE CONTROLLO CO...

Page 34: ...ualmente fissate in contratti e o note di consegna o di pagamento sono indipendenti e non fanno riferimento alla vita attesa di seguito indicata Per condizioni operative normali si intendono applicazioni su caldaie ad acqua e generatori di vapore oppure applicazioni industriali conformi alla norma EN 746 in ambienti con temperature nei limiti previsti dal presente manuale e con grado di inquinamen...

Page 35: ... combustibile 3 Eccesso di aria comburente 4 Passaggio d aria tra disco fiamma e diffusore eccessivamente chiuso 5 Ugello logoro o sporco 1 Termostati caldaia o ambiente o pressostati aperti 2 Sensore fiamma in corto circuito 3 Mancanza di tensione in linea interruttore generale aperto interruttore del contatore scattato o mancanza di tensione in linea 4 La linea dei termostati non è stata eseguit...

Page 36: ...30 C per gasolio 1 Eccessivo raffreddamento dei fumi indicativamente al di sotto dei 130 C in canna fumaria per camino esterno non sufficientemente coibentato oppure per infiltrazioni di aria fredda RIMEDIO 1 Ripristinarla al valore previsto 2 Diminuire l aria comburente 3 Pulire o sostituire 4 Scaricare l acqua dalla cisterna servendosi di una pompa adatta Non usare mai per questo lavoro la pompa...

Page 37: ... 04 28 81 29 56 30 29 31 00 31 70 32 38 33 05 33 70 5 5 6 00 17 66 19 00 20 40 21 63 22 80 23 92 24 98 26 00 26 98 27 93 28 84 29 73 30 59 31 43 32 25 33 04 33 82 34 58 35 33 36 05 36 77 6 00 6 50 19 13 20 67 22 10 23 44 23 70 25 91 27 06 28 17 29 23 30 26 31 25 32 21 33 14 34 05 34 94 35 80 36 64 37 46 38 27 39 06 39 83 6 50 7 00 20 60 22 26 23 79 25 24 26 60 27 60 29 14 30 33 31 48 32 58 33 65 3...

Page 38: ...SCHEMI ELETTRICI TBL 18P TBL 26P 36 40 0006160435_202112 ITALIANO ...

Page 39: ...TBL 35P DACA 37 40 0006160435_202112 ITALIANO ...

Page 40: ...TBL 35P TBL 45P 38 40 0006160435_202112 ITALIANO ...

Page 41: ...PIA FUNZIONAMENTO 2 STADIO MV MOTORE VENTOLA P1 CONTAORE S2 PULSANTE SBLOCCO T2 TERMOSTATO 2 STADIO TA TRASFORMATORE D ACCENSIONE TC TERMOSTATO CALDAIA TS TERMOSTATO DI SICUREZZA X1B S CONNETTORE ALIMENTAZIONE X2B S CONNETTORE 2 STADIO Y1 Y2 ELETTROVALVOLE 1 2 STADIO YS YS1 ELETTROVALVOLA DI SICUREZZA 39 40 0006160435_202112 ITALIANO ...

Page 42: ...40 40 0006160435_202112 ITALIANO ...

Page 43: ...er to the liquid fuel supply line 16 Supply line 16 Auxiliary pump 18 First hydraulic circuit filling 19 Electrical connections 20 Operating description 21 Starting up and regulation 22 Controls 23 Air regulation on the combustion head 23 Diagram for regulating the electrode disk distance 24 Oscillating jack 26 Servomotor cams adjustment SQN72 2B4A20 27 Control and command equipment LMO 28 Mainten...

Page 44: ...be placed in closed rooms with enough air circulation in standard temperature conditions 25 C and 55 C The storage time is 3 years GENERAL WARNINGS The burner must be used in boilers for civil applications such as building heating and domestic hot water production The burner must NOT be used in production cycles and industrial processes the latter governed by the Standard EN 746 2 Contact sales of...

Page 45: ...the fume disposal system is NOT obstructed If it is decided not to use the burner any more the following procedures must be performed by qualified technicians Switch off the electrical supply by disconnecting the power cable from the main switch Cut off the fuel supply using the shut off valve and remove the control wheels from their position Render harmless any potentially dangerous parts WARNING...

Page 46: ...ch the equipment with parts of the body that are wet or damp or with damp feet do not pull on electrical cables do not leave the equipment exposed to atmospheric agents such as rain or sun etc unless there is explicit provision for this do not allow the equipment to be used by children or inexpert persons The power supply cable for the equipment must not be replaced by the user If the cable is dam...

Page 47: ... of protection devices The automatic reset function on the thermal device which protects the fan motor cannot be enabled by irreversibly removing the relevant plastic label for any reason As for the connection of cables to the terminals of the electrical equipment make sure that the earth conductor length is such as to ensure that it is not subject in any way to accidental disconnection following ...

Page 48: ...or Photoresistor Photoresistor Photoresistor Air flow rate regulation hydraulic jack hydraulic jack hydraulic jack Servomotor Operating ambient air temperature C 15 40 15 40 15 40 15 40 Sound pressure dBA 76 3 76 3 74 1 74 1 Sound power dBA 88 1 88 1 85 9 85 9 Weight with packaging kg 23 5 24 29 5 28 Weight without packaging kg 18 5 19 24 5 23 Lower calorific power Diesel fuel Hi 11 86 kWh kg 42 7...

Page 49: ... 2 1 4 N 2 3 8 N 2 1 4 N 2 3 8 N 2 1 4 x 1 4 x 25 N 2 1 4 x 1 4 x 25 Nozzles 1 1 2 2 7 pole connector 1 1 1 1 4 pole connector 1 1 1 1 BURNER IDENTIFICATION PLATE 1 2 3 4 5 6 7 11 14 12 Targa_descr_bru 8 9 10 13 15 1 Company logo 2 Company name 3 Product code 4 Burner model 5 Serial number 6 Liquid fuel power 7 Gaseous fuel power 8 Gaseous fuel pressure 9 Liquid fuel viscosity 10 Fan motor power 1...

Page 50: ... alloy Conveyor with combustion air flow regulation dampers Flame inspection glass Fuel supply circuit comprising gear pump with pressure regulation and shut off valve s 7 pole socket for burner power and thermostatic supply Automatic command equipment and burner control according to European regulation EN298 Display showing the operating sequence and error code in the event of a lockout Protectio...

Page 51: ...5 IMPORTANT The operating ranges are obtained from test boilers corresponding to Standard EN267 and are indicative of the burner boiler combination For correct working of the burner the size of the combustion chamber must correspond to current regulations if not the manufacturers must be consulted The burner shall not operate outside its specific operating range 9 40 0006160435_202112 ENGLISH ...

Page 52: ... 10 Liquid fuel pump 11 Control panel electrical switchboard 12 Fan motor 13 Burner identification plate ELECTRICAL PANEL 1 Control box 2 Ignition transformer 3 Motor contactor only with three phase power supply 4 Thermal relay only with three phase power supply 5 7 pole connector 6 4 pole connector 7 Burner on LED 8 Burner lock out LED 9 Reset button TBL 18P TBL 26P 1 4 9 8 11 12 1 4 5 7 8 9 10 5...

Page 53: ...on servomotor 10 Liquid fuel pump 11 Control panel electrical switchboard 12 Fan motor 13 Burner identification plate ELECTRICAL PANEL 1 Control box 2 Ignition transformer 3 Motor contactor only with three phase power supply 4 Thermal relay only with three phase power supply 5 7 pole connector 6 4 pole connector 7 Burner on LED 8 Burner lock out LED 9 Reset button 1 2 3 4 5 6 7 8 9 10 11 12 9 TBL ...

Page 54: ...uid fuel pump 11 Control panel electrical switchboard 12 Fan motor 13 Burner identification plate ELECTRICAL PANEL 1 Control box 2 Ignition transformer 3 Motor contactor only with three phase power supply 4 Thermal relay only with three phase power supply 5 7 pole connector 6 4 pole connector 7 Burner on LED 8 Burner lock out LED 9 Reset button 10 START STOP switch TBL 35P DACA 1 2 3 4 5 6 7 8 9a ...

Page 55: ...B A2 A1 A TBL 18P TBL 26P Model A A1 A2 B B1 B2 C TBL 18P 474 248 226 343 258 85 690 TBL 26P 474 248 226 343 258 85 700 Model D E Ø F Ø I I1 TBL 18P 100 240 114 114 185 185 TBL 26P 100 255 135 114 185 185 Model LØ M N TBL 18P 170 210 M10 115 TBL 26P 170 210 M10 115 13 40 0006160435_202112 ENGLISH ...

Page 56: ...L 35P DACA Model A A1 A2 B B1 B2 C TBL 35P 460 235 225 365 260 105 795 TBL 35P DACA 460 235 225 365 260 105 795 Model D E Ø F Ø I I1 TBL 35P 120 350 135 135 215 215 TBL 35P DACA 120 350 135 135 215 215 Model LØ M N TBL 35P 200 245 M12 136 TBL 35P DACA 200 245 M12 136 14 40 0006160435_202112 ENGLISH ...

Page 57: ...ufacturer Position the insulating gasket 13 on the sleeve by inserting the cord 2 between the flange and the gasket Fasten the burner to the boiler 1 by means of the stud bolts washers and the nuts provided 7 DANGER ATTENTION Seal the space between the burner sleeve and the hold on the refractory material inside the boiler door completely with suitable material 15 40 0006160435_202112 ENGLISH ...

Page 58: ...he hose to the burner pump s suction coupling nipple all parts are supplied with the burner The pump is provided with specific connections to fit control instruments pressure gauge and vacuum gauge For a safe and silent operation the suction vacuum cannot exceed 35 cm Hg corresponding to 0 46 bar The anti pollution prescriptions as well as the provisions set forth by the local authorities refer to...

Page 59: ... 3 5 m H Measurement between minimum oil level and pump axis H Inner pipe diameter Ø 14 mm Total length of each pipe m m 1 30 1 5 35 2 35 2 5 40 3 40 INTAKE SUPPLY SYSTEM 3 7 10 4 H 6 1 0002900740N3 IMPORTANT For any components missing in the pipes comply with current regulations IMPORTANT Total length of pipeline including vertical length Deduct 0 25 m for each elbow or gate 1 Fuel tank 3 Mesh fi...

Page 60: ...ed The head must be suitable for the relative plant We recommend a flow rate equal at least to that of the burner pump The connection pipes must be dimensioned based on the flow rate of the auxiliary pump Avoid electrically connecting the auxiliary pump directly to the remote control switch of the burner BLOCK DIAGRAM OF HYDRAULIC CIRCUIT TBL 18P TBL 26P 1 Foot valve 2 Hydraulic air control jack 3...

Page 61: ...s such as diesel petrol kerosene Press on the mobile part of the motor remote control switch in order to start up the motor and therefore the pump Wait until the pump has sucked in an amount of lubricant equal to 1 or 2 glassfuls then stop WITH A SINGLE PHASE BURNER Switch off the master switch and the boiler and safety thermostats and then start up the motor and ignition transformer On inserting ...

Page 62: ...ar switch with a contact opening gap equal or above 3 mm is required for the mains supply connection in accordance with current safety regulations Refer to the wiring diagram for electrical connections line and thermostats Strip the outer insulation of the power cable just as necessary for the connection preventing the cable to touch metal parts and provide a longer length for the earth conductor ...

Page 63: ...rmal manner once the safety time foreseen by the control box has passed it activates the 2nd stage solenoid valve closed in stand by If an air regulation servomotor is used see the 2st stage cam adjustment in the chapter on servomotor cam adjustment NT At the same time the piston that controls the combustion air regulator moves downward opening further the regulator The piston stroke can be adjust...

Page 64: ... the amount of air necessary for ensuring efficient combustion We recommend keeping the air quantity at a low level when working in the first stage output to ensure perfect ignition even in the most difficult conditions After adjusting the first stage air disconnecting the current from the main switch close the electric circuit commanding the second stage activation and move the switch on the elec...

Page 65: ...cale to match that of the thermometer AIR REGULATION ON THE COMBUSTION HEAD The combustion head is equipped with a regulation device that makes it possible to open or close the air passage between the disk and the head Closing the air passage increases the pressure upstream of the disk also with low flow rates The high speed and turbulence of the air provides for its greater penetration into the f...

Page 66: ...0 3 00 GPH TBL 18P DANFOSS B 60 4 50 GPH TBL 26P DANFOSS B 60 4 00 GPH TBL 26P DANFOSS B 60 2 50 GPH TBL 35P P DACA DANFOSS B 60 4 00 GPH TBL 35P P DACA DANFOSS B 60 2 50 GPH DANGER ATTENTION For narrow combustion chambers it is recommended to use nozzles with a 45 atomisation angle A B C D E TBL 18P 1 19 5 4 5 7 TBL 26P 1 19 5 4 5 7 35P P DACA 1 5 7 4 6 5 After any operation on the combustion hea...

Page 67: ... 2nd flame 6 Suction 7 Return with inner by pass dowel 8 Pressurized outlet pressure gauge and air vent connection 1 8 9 Vacuum gauge connection 1 8 10 Delivery to nozzle CAUTION WARNINGS The pump is pre set at a pressure of 10 bar 1st flame and 18 bar 2nd flame SUNTEC AS 47 A 7432 3 PUMP TBL 35P TBL 35P DACA 1 Solenoid valve normally open 2 Pressure gauge and air vent connection R 1 8 3 Pressure ...

Page 68: ...e jack In this case the body 1 move upwards and favours air damper closing 7 Once the first stage air regulation is complete lock the two ring nuts 4 and 5 ADJUSTMENT OF SECOND STAGE AIR DUMPER POSITION Loosen lock nut 6 To increase second stage flow rate undo the screw 5 so as to lengthen the hydraulic piston stroke Perform the operation in the reverse order to reduce it After second stage air fl...

Page 69: ...of the rotation angle set for each cam 1 Motor camshaft coupling On Off pin 2 Reference scale 3 Position indicator 4 Adjustable camshaft I 2nd stage air regulation cam 80 II Total air closure burner stopped 0 III 1st stage air regulation cam 20 IV 2nd stage valve activation cam 40 III II I IV III II I IV SQN 72 2B4A20 1 2 3 4 0002935210 27 40 0006160435_202112 ENGLISH ...

Page 70: ...e diagnostics function hold the reset button down for at least 3 seconds A quick red flashing indicates that the function is active Likewise hold the reset button down for at least 3 seconds to deactivate the function the switching will be indicated with a flashing yellow light EK xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx 3 s 7101z03e0305 Operating position PC interface diagnostic anal...

Page 71: ...ics Operating position Operating position Visual indication AL to terminal 10 Possible causes 2 blinks On No flame at the end of the safe ignition time TSA Fuel valves malfunctioning Flame detector malfunctioning Incorrect burner calibration no fuel No ignition faulty ignition transformer 3 blinks On Available 4 blinks On Extraneous light during the ignition phase 5 blinks On Available 6 blinks On...

Page 72: ...d below Disconnect the diesel hoses 24 from the connectors beneath the head unit mind the dripping IMPORTANT Store in memory the exact position of the mobile plate marks 23 with respect to the reference on the burner scroll Once the maintenance operations have been completed return the mixer assembly to the same position it was the last time it was adjusted Undo the screws 11 and remove the lid 13...

Page 73: ...SENSOR CLEANING YEAR VARIOUS COMPONENTS MECHANICAL CAM CHECK OF WEAR AND OPERATION GREASING OF SLIDING BLOCK AND SCREWS YEAR LEVERS TIE RODS BALL JOINTS CHECK OF ANY WEAR COMPONENT LUBRICATION YEAR COMBUSTION HEAD EXTRACTION KIT CHECKING WEAR AND OPERATION YEAR FUEL LINE HOSES REPLACEMENT 5 YEARS PUMP FILTER CLEANING YEAR LINE FILTER FILTERING ELEMENT CLEANING REPLACEMENT YEAR COMBUSTION PARAMETER...

Page 74: ...RTANT warranty conditions laid down in contracts and or delivery or payment notes if necessary are independent and do not refer to the expected lifespan stated below Normal operating conditions means applications on water boilers and steam generators or industrial applications compliant with the standard EN 746 in environments with temperatures within the limits provided for in this manual and wit...

Page 75: ...ump pressure is not regular 2 Water in the fuel 3 Too much combustion air 4 Air passage between flame disk and diffuser excessively closed 5 Nozzle worn out or dirty 1 Thermostats boiler or room or pressure switches are open 2 Flame sensor short circuit 3 Absence of line voltage main switch open meter switch tripped or absence of line voltage 4 Thermostat line not wired according to diagram or ope...

Page 76: ... temperature too low approximately below 130 C for diesel 1 Excessive cooling of smoke approximately below 130 C in the chimney for an outside chimney not adequately heat insulated or cold air infiltration REMEDY 1 Restore it at the required value 2 Reduce combustion air 3 Clean or replace 4 Drain water from the tank using a suitable pump Never use the burner pump for this purpose 1 Increase combu...

Page 77: ...26 44 27 25 28 04 28 81 29 56 30 29 31 00 31 70 32 38 33 05 33 70 5 5 6 00 17 66 19 00 20 40 21 63 22 80 23 92 24 98 26 00 26 98 27 93 28 84 29 73 30 59 31 43 32 25 33 04 33 82 34 58 35 33 36 05 36 77 6 00 6 50 19 13 20 67 22 10 23 44 23 70 25 91 27 06 28 17 29 23 30 26 31 25 32 21 33 14 34 05 34 94 35 80 36 64 37 46 38 27 39 06 39 83 6 50 7 00 20 60 22 26 23 79 25 24 26 60 27 60 29 14 30 33 31 48...

Page 78: ...WIRING DIAGRAMS TBL 18P TBL 26P 36 40 0006160435_202112 ENGLISH ...

Page 79: ...TBL 35P DACA 37 40 0006160435_202112 ENGLISH ...

Page 80: ...TBL 35P TBL 45P 38 40 0006160435_202112 ENGLISH ...

Page 81: ...TOR LIGHT H18 2ND STAGE OPERATION LIGHT MV FAN MOTOR P1 HOUR METER S2 RELEASE BUTTON T2 2ND STAGE THERMOSTAT TA IGNITION TRANSFORMER TC BOILER THERMOSTAT TS SAFETY THERMOSTAT X1B S POWER SUPPLY CONNECTOR X2B S 2nd STAGE CONNECTOR Y1 Y2 1st 2nd STAGE SOLENOID VALVES YS YS1 SAFETY SOLENOID VALVE 39 40 0006160435_202112 ENGLISH ...

Page 82: ...40 40 0006160435_202112 ENGLISH ...

Page 83: ......

Page 84: ...t Il presente catalogo riveste carattere puramente indicativo La casa pertanto si riserva ogni possibilità di modifica dei dati tecnici e di quant altro in esso riportato Information contained in this catalogue is not binding The manufacturer reserves the right to change the technical data and any other data it contains ...

Reviews: