EXPECTED LIFESPAN
The expected lifespan of burners and relevant components depends very much from the type of application on which the burner is installed, from
cycles ,of delivered power, from the conditions of the environment in which it is located, from maintenance frequency and mode, etc.
Standards about safety components provide for a project expected lifespan expressed in cycles and/or years of operation.
Such components ensure the correct operation in standard (*) operating conditions, with periodic maintenance according to the instructions
contained in the manual.
The table below shows the project expected lifespan of the main safety components; approximately, operating cycles correspond to the burner
activations.
When this expected lifespan limit has almost been reached the component must be replaced with an original
spare part
.
IMPORTANT
warranty conditions (laid down in contracts and/or delivery or payment notes, if necessary) are independent and do not refer to the
expected lifespan stated below.
(*) “Normal” operating conditions means applications on water boilers and steam generators or industrial applications compliant with the standard
EN 746, in environments with temperatures within the limits provided for in this manual and with pollution degree 2 in compliance with annex M
of the standard EN 60204-1.
Safety component
Project expected lifespan
Operating cycles
Years of operation
Control box
250 000
10
Flame sensor (1)
n.a.
10,000 operating hours
Air pressure switch
250 000
10
Servomotors
250 000
10
Liquid fuel hoses
n.a.
5 (every year for fuel oil burners or in the presence of
biodiesel in diesel/kerosene)
Liquid fuel valves
250 000
10
Air fan impeller
50,000 activations
10
(1) The characteristics can degrade over time; during the annual maintenance the sensor must be checked and in case of flame signal degradation
must be replaced.
32 / 40
0006160435_202112
ENGLISH
Summary of Contents for 35575410
Page 2: ......
Page 38: ...SCHEMI ELETTRICI TBL 18P TBL 26P 36 40 0006160435_202112 ITALIANO ...
Page 39: ...TBL 35P DACA 37 40 0006160435_202112 ITALIANO ...
Page 40: ...TBL 35P TBL 45P 38 40 0006160435_202112 ITALIANO ...
Page 42: ...40 40 0006160435_202112 ITALIANO ...
Page 78: ...WIRING DIAGRAMS TBL 18P TBL 26P 36 40 0006160435_202112 ENGLISH ...
Page 79: ...TBL 35P DACA 37 40 0006160435_202112 ENGLISH ...
Page 80: ...TBL 35P TBL 45P 38 40 0006160435_202112 ENGLISH ...
Page 82: ...40 40 0006160435_202112 ENGLISH ...
Page 83: ......