OSCILLATING JACK
ADJUSTMENT OF FIRST STAGE AIR DUMPER POSITION
•
To increase the flow rate, turn ring nut (3) anticlockwise using the
counter wrench on the body (1) of the jack to avoid putting excessive
stress on the eyelet pin (9).
•
This operation lowers the body (1) and favours the opening of the
first stage air damper (7).
•
To decrease the air flow rate, turn ring nut (4) clockwise, using
always the counter-wrench on the body of the jack.
•
In this case, the body (1) move upwards and favours air damper
closing (7).
•
Once the first stage air regulation is complete, lock the two ring nuts
(4) and (5).
ADJUSTMENT OF SECOND STAGE AIR DUMPER POSITION
•
Loosen lock nut (6).
•
To increase second stage flow rate, undo the screw (5) so as to
lengthen the hydraulic piston stroke. Perform the operation in the
reverse order to reduce it.
•
After second stage air flow adjustment is completed, tighten nut (6).
DANGER / ATTENTION
To avoid damaging the eyelet (9), carry out all the adjustment
operations with wrench and counter-wrench.
0002935420
9
1
2
3
4
6
5
7
8
26 / 40
0006160435_202112
ENGLISH
Summary of Contents for 35575410
Page 2: ......
Page 38: ...SCHEMI ELETTRICI TBL 18P TBL 26P 36 40 0006160435_202112 ITALIANO ...
Page 39: ...TBL 35P DACA 37 40 0006160435_202112 ITALIANO ...
Page 40: ...TBL 35P TBL 45P 38 40 0006160435_202112 ITALIANO ...
Page 42: ...40 40 0006160435_202112 ITALIANO ...
Page 78: ...WIRING DIAGRAMS TBL 18P TBL 26P 36 40 0006160435_202112 ENGLISH ...
Page 79: ...TBL 35P DACA 37 40 0006160435_202112 ENGLISH ...
Page 80: ...TBL 35P TBL 45P 38 40 0006160435_202112 ENGLISH ...
Page 82: ...40 40 0006160435_202112 ENGLISH ...
Page 83: ......