15
Optional Accessory
Installation
Fan Cowl Extensions
Discharge Sound
Attenuation
Motor Removal Davit
PT2-0709, PT2-0809, PT2-
0812, and PT2-0814
PT2-1009, PT2-1012,
PT2-1212, and PT2-1218
Motor Removal Davit (Optional)
PT2-0709, PT2-0809, PT2-0812, and PT2-0814 (see Figure 21a)
1. Remove the cover plate from the upper support channel.
2. Rotate the davit assembly to align the bolt head on the davit with the keyway in the
upper support channel and lower into position. The davit must pass through the upper
and lower support channel and rest on support base.
PT2-1009, PT2-1012, PT2-1212, PT2-1214, and PT2-1218 (see Figure 21b)
1. Verify the davit support is factory installed next to the access door. If not installed,
remove the bolts next to the access door (refer to
Figure 21c
).
DO NOT REMOVE
TAPPERS
. Secure the davit support by re-installing the bolts.
2. Rotate the davit assembly to align the bolt head on the davit with the keyway in the
upper support channel and lower into position. The davit must pass through the upper
and lower support channels and rest on the support base.
Cover Plate
(Remove)
Upper Support
Chanel
Lower Support
Chanel
Lower Into
Position
Figure 21a.
Motor Removal Davit Installation for
PT2-0709, PT2-0809, PT2-0812, and PT2-0814
NOTE
: The maximum weight load
capacity of the motor removal davit
is 630 lbs for PT2-0709, PT2-0809,
PT2-0812, and PT2-0814 units.
NOTE
: The maximum weight load
capacity of the motor removal davit
is 830 lbs for PT2-1009, PT2-1012,
PT2-1212, PT2-1214, and PT2-1218
units.
Figure 21c.
Davit Support Detail
Figure 21b.
Motor Removal Davit Installation for
PT2-1009, PT2-1012, PT2-1212, PT2-1214, and PT2-1218
Bolt, Nut,
and Washer
Tapper
DO NOT
REMOVE
Access Door
NOTICE:
Do not remove tappers
during installation of motor removal
davit support. Removing tappers
will cause the interior mechanical
system to fall.