![Baltimore Aircoil Company PT2 Series Rigging & Assembly Instructions Download Page 11](http://html1.mh-extra.com/html/baltimore-aircoil-company/pt2-series/pt2-series_rigging-and-assembly-instructions_3623444011.webp)
9
Unit Rigging & Assembly
Multi-Cell Unit Installation
Positive Closure Plate Installation
Water Baffle Installation
Multi-Cell FM Partition Panels
(Optional)
Motor Installation for
PT2-0709, PT2-0809, PT2-0812,
and PT2-0814
NOTE:
All other PT2 models have
the fan motor mounted and belt
tensioned at the factory.
WARNING:
Ensure that the fan
guard is properly installed prior to
commencing operation.
NOTICE:
Do not remove tappers
from the fan section during the
installation of the external motor.
Removing tappers will cause the
interior mechanical system to fall.
Multi-Cell Factory Mutual (FM) Partition Panels (Optional)
Partition panels are provided for PT2 Cooling Towers with FM approval.
1. Set the base of the panel support into the upper basin flange while positioning the
support bracket as shown in
Figure 13,
Detail A
. Slide the support bracket up behind
the corner gussets on the columns.
2. Secure the panel support to the support bracket with 5/16” self-tapping screws.
3. Secure the partition to the panel support using 5/16” self-tapping screws. The panel
should be flush with the top of the panel support.
Figure 14a.
External Motor Mount Assembly Lift
1/2” washer
1/2” lock washer
1/2” nut
Eyelets
Motor Installation for PT2-0709, PT2-0809, PT2-0812, and PT2-0814
(Figure 14)
1. Attach the lifting strap to the motor base eyelets and remove the motor and the
motor base assembly from the basin. The motor assembly must remain vertical
to maintain proper alignment during installation.
2. Lift the external motor assembly into position next to the access door.
3. Attach the assembly to the unit using the six ½” studs, flatwashers, lock
washers, and nuts.
4. Install the powerband, check sheave alignment, and tension the power band.
For correct sheave alignment and tensioning specifications and procedures,
refer to the
PT2 Operation & Maintenance Manual.
Detail A
Figure 13.
Installation of Partition Panels
Support Bracket
Panel Support
Partition A
Upper Basin Flange
Tapper
DO NOT
REMOVE
Figure 14b.
External Motor Mount Assembly Pattern