Programming

 
The effective bleed set point should be defined by the owner or by its representative (contractor, water treatment 

specialist,...) in function of the following parameters:

Make Up water quality parameters

Materials of construction: refer to the "Water Care" on page 7 and the submittal information of the 

BAC equipment

The water treatment program implemented, including formulation and concentration of biocides and anti-

scale / anti-corrosion inhibitors

The system volume to be treated

 
Anti-scale and anti-corrosion dosing is made in function of the make up water quality. An impulse will be given to 

the dosing during XX minutes / YY seconds after each XXX liters of make up water.
One biocide (Bio 1) will be dosed in shock during X minutes / YY seconds at regular interval (weekly or daily 

mode). Pre-bleed is done before dosing and bleed lock out to be made for X hours / YY minutes after dosing.
The second biocide (Bio2) will be an oxidizing biocide that will be dosed in function of a Redox measurement, 

providing indirect correlation with the remaining oxidizing biocide value in the system.

FOLLOWING VALUES NEED TO BE ADJUSTED / CHECKED PRIOR TO START UP:

Global settings

Date (If required)

Time (If required)

Input Menu

D2 water meter

Output Menu

R1 Bleed Valve - Conductivity Set Point

R2 Inhibitor dosing based on water meter

R3 Time dosing of biocide

R4 Redox based dosing of biocide

Optional - Analog output conductivity 4-20 mA

W W W . B A L T I M O R E A I R C O I L . E U

23

5 Controller Settings

5 Controller Settings

Summary of Contents for BCP3D

Page 1: ...BCP3D Automatic Dosing and Bleed Control Package INSTALLATION OPERATING MAINTENANCE MBCP3Dv01EN...

Page 2: ...gical control 8 Chemical treatment 9 Passivation 9 4 Receiving and Installation 10 Receiving Equipment 10 Piping Interface Connections 11 Design Criteria 11 Installation and Anchoring 11 Electrical Wi...

Page 3: ...xidizing biocide 2 Fluid outlet coupling 12 Pump scale corrosion inhibitor 3 Bleed 13 Pump secondary biocide 4 Controller BACT 600 14 Redox sensor 5 Conductivity probe 15 Chemical drum 6 Sampling poin...

Page 4: ...nd phone number can be found on the website www BACservice eu Safety precautions All electrical mechanical and rotating machinery constitutes a potential hazard particularly for those not familiar wit...

Page 5: ...ipment should be located as far away as possible from occupied areas open windows or air intakes to buildings LOCAL REGULATIONS Installation and operation of cooling equipment may be subject to local...

Page 6: ...all products to be free from manufactured defects in materials and workmanship for a period of 24 months from the date of shipment In the event of any such defect BAC will repair or provide a replace...

Page 7: ...hereafter Moreover there must be an ongoing programme of monitoring in place to ensure the water treatment system is maintaining the water quality within the control guidelines Check and adjustments o...

Page 8: ...culated as follows Blow down Evaporation loss Cycles of concentration 1 The evaporation loss is not only function of the heat load but also depends on climatic conditions the type of equipment used an...

Page 9: ...onthly monitoring of the circulating and make up water quality 5 If it is proposed to operate a treatment programme outside the BAC Water Quality Control Guidelines the BAC factory warranty may be inv...

Page 10: ...g damage Make sure that all required equipment noted on the bill of lading is received Check the model and serial number against the packing list Receiving Inspection check list 1 BCP3D panel 3 chemic...

Page 11: ...open and closed circuit evaporative cooling equipment Determination of these aspects is made by a qualified BAC representative Changes in system load which increase the bleed rate may require an incr...

Page 12: ...ure however sufficient bleed rate can be guaranteed at nominal operation load 4 The BCP3D is designed to handle a maximum water pressure of 60 kPa at 55 C DRUMS AND BUNDS The drums and bunds should be...

Page 13: ...to be installed inside drum Suction head should be installed vertically Adjust tubing length accordingly Mounting detail tubing on pump head Overview pump tubing connection to drum W W W B A L T I M...

Page 14: ...uld be cleaned on a yearly basis Water meter reading information 1 1 rotation 1L 1 graduation 0 1 L 2 1 rotation 10L 1 graduation 1 L 3 1 rotation 1m 1 graduation 100 L 4 1 rotation 100L 1 graduation...

Page 15: ...ing Pumps Dosing pumps are premounted on BCP panel and prewired to the controller Refer to specific dosing pumps operating manual supplied with the submittal package for specific questions regarding d...

Page 16: ...ery low alarm 200 S cm Low Alarm 200 S cm High Alarm 3500 S cm HiHi Alarm Very high alarm 3500 S cm Deadband 25 S cm Alarm suppression none Reset Calibration values Cal Req d Alarm 365 days Smoothing...

Page 17: ...p Type 10K Therm S21 Redox LoLo Alarm Very low alarm 50 0 mV Low Alarm 50 0 mV High Alarm 850 0 mV HiHi Alarm Very high alarm 850 0 mV Deadband 10 0 mV Reset Calibration values Cal Req d Alarm 365 day...

Page 18: ...Name change with language default is English Flow switch Type DI State D2 Water meter Totalizer Alarm 0 Reset flow total Scheduled reset Disabled Volume Contact 1 I Flow units I Name change with lang...

Page 19: ...Name change with language default is English Bleed Mode On Off R2 Inhibitor dosing based in water meter HOA Setting Auto Feed duration 00 02 00 Accum Volume 200 l Reset timer Output Time Limit 1 00 0...

Page 20: ...epetition 1 week Day Friday Start time 8 00 00 Duration 0 15 00 Event 4 10 Inactive Bleed Bleed R1 Prebleed time 0 00 00 Prebleed to 1150 S cm Cond Input Conduct S1 Bleed lockout 1 00 00 Interlock cha...

Page 21: ...t 0 10 00 Input ORP Redox S21 Direction Force Higher Name change with language default is English Bio2 ORP Mode Time Proportional R5 Not used R6 Alarm HOA Setting Auto Alarm mode All Alarms Output Nor...

Page 22: ...ish English Security Settings Controller Log Out Security Disabled Local Password Default is 5555 Display Settings Home 1 Conduct S11 Home 2 Temp S12 Home 3 ORP Redox S21 Home 4 None Adjust Display Ke...

Page 23: ...XX liters of make up water One biocide Bio 1 will be dosed in shock during X minutes YY seconds at regular interval weekly or daily mode Pre bleed is done before dosing and bleed lock out to be made f...

Page 24: ...ll bring up the item s Details screen where you can access calibration and settings menus Arrow icons page up or down to additional inputs if more than three are configured to be viewed Touching the M...

Page 25: ...the Home screen Press the key below the icon to get to the Main Menu selection Alarm Menu Inputs Menu Outputs Menu Configuration Settings Menu HOA Menu Graph Menu Home Page Other icons may appear in...

Page 26: ...s used when making an alphanumeric entry The Make Character Lower key is used when making an alphanumeric entry The Move Cursor key is used to scroll left to right within an alphanumeric entry The Cha...

Page 27: ...alue and go back Choosing from a list Selecting the type of sensor the units of measure of an input or the control mode used for an output the selection is picked from a list of available options Touc...

Page 28: ...o change the date Touch the Confirm icon to accept the change Set time if necessary Touch the Scroll up or Down icon until Time is displayed and then touch it Touch the Move Cursor icon to highlight t...

Page 29: ...Select input screen Select water meter D2 Press the Settings key Press the Scroll Down key until the volume contact is highlighted Press the Enter key Use the screen keypad to change value if required...

Page 30: ...the correct bleed set point with following procedure Select bleed R1 Touch the Settings icon Touch the Scroll Down icon until the Setpoint is highlighted Use the screen key pad to change value if req...

Page 31: ...ale and corrosion inhibitor dosing Touch the Settings icon Touch the Scroll Down icon until the Feed Duration is highlighted Default is 2 minutes Change the duration Hours Minutes seconds Validate Tou...

Page 32: ...Enter the correct values with following procedures The Bio Timer R3 relay output will be highlighted Touch the Settings icon Touch the Scroll Down icon until the Event 1 is highlighted Default is 1 w...

Page 33: ...event to be purged and diluted Program the Pre bleed and Bleed lock out Still in the Bio Timer R3 relay output menu Touch the Settings icon Touch the Scroll Down icon until the Pre bleed is highlighte...

Page 34: ...yboard Validate ANALOG OUTPUT 4 20 MA OPTIONAL EXECUTION WHEN ORDERED This option will allow you to get the output value for the conductivity S11 and the Redox ORP 21 Press the Settings icon view or c...

Page 35: ...B stick Press the Enter key and then press the Confirm key to transfer a file containing the controller s settings to the USB stick Restore Default Config Enter this menu to restore all of the setting...

Page 36: ...to operate The BCP is now ready to control and dose SHUT DOWN To shut down the controller simply turn off the power Programming remains in memory For more details on controller functionality refer to...

Page 37: ...The sensor can normally be cleaned using a cloth or paper towel and a mild detergent If coated with scale clean with a dilute 5 solution of hydrochloric acid solution for at least 1 minute Occasionall...

Page 38: ...on the controller After cleaning if the value deviates from the reading on the handheld device see calibration procedure below CALIBRATE THE CONDUCTIVITY SENSOR To calibrate the sensor from the home...

Page 39: ...Choose your method and follow the steps on the screen One point calibration The sensor stays in the loop so the regulation is not interrupted Take a sample analyze it and then enter the actual value...

Page 40: ...point buffer calibration except that you need two different buffer solutions The sensor is removed from the process so the regulation is stopped during the calibration Remove the sensor from the proce...

Page 41: ...rate Incorrect cable length or wire gauge setting Set to the correct values Faulty electrode Replace electrode ALARM MESSAGES Alarm messages will include the name of the input or output as defined in...

Page 42: ...ee for obstruction Verify flow Change location of electrode Pre bleed set too low Check pre bleed setting Bleed valve stuck open Repair or replace bleed valve Faulty electrode Replace sensor Improper...

Page 43: ...t short Faulty sensor Replace sensor Faulty controller Replace or repair controller Sensor fault This error indicates that the signal from the sensor is no longer valid at all This error condition wil...

Page 44: ...nsterie van de Vlaamse Gemeenschap December 2002 77p Legionnaires Disease The Control of Legionella Bacteria in Water Systems Health Safety Commission 2000 62p Hygienische Anforderungen an raumlufttec...

Page 45: ...W W W B A L T I M O R E A I R C O I L E U...

Page 46: ...AGE EVAPORATIVE CONDENSERS HYBRID PRODUCTS PARTS EQUIPMENTS SERVICES www BaltimoreAircoil eu info BaltimoreAircoil eu Please refer to our website for local contact details Industriepark Zone A B 2220...

Reviews: