Enter the correct values with following procedures:
Select the Bio2 ORP R4 relay when highlighted
•
Program the setting for the oxidizing biocide dosing
•
Touch the Settings icon
•
Touch the Scroll Down icon until the "Set point" is highlighted (default is 200 mV)
•
Select and edit set point as defined using the screen keyboard
•
Validate
ANALOG OUTPUT 4 - 20 MA (OPTIONAL EXECUTION WHEN ORDERED)
This option will allow you to get the output value for the conductivity (S11) and the Redox (ORP-21).
Press the Settings icon view or change the settings related to the analog output.
4 mA Value
Enter the value of the conductivity to correspond to 4 mA output signal (default 0
MicroSiemens)
20 mA Value
Enter the value of the conductivity to correspond to 20 mA output signal (default
3600 MicroSiemens)