R4 - Redox based dosing of biocide
HOA Setting
Auto
Setpoint
200,0 mV
Proportional Band
100,0 mV
Sample period
0:02:00
Duty Cycle
100,0 %
Output Time Limit
0:00:00
Reset Output Timeout
Interlock channels
D1
Activate with channels
None
Min Relay Cycle
0 sec
Hand Time Limit
0:10:00
Input
ORP Redox (S21)
Direction
Force Higher
Name (change with language - default is English)
Bio2 ORP
Mode
Time Proportional
R5 - Not used
R6 - Alarm
HOA Setting
Auto
Alarm mode
All Alarms
Output
Normally open
Interlock channels
None
Activate with channels
None
Min Relay Cycle
0 sec
Hand Time Limit
0:10:00
Name (change with language - default is English)
Alarm
Mode
Alarm Output
W W W . B A L T I M O R E A I R C O I L . E U
21
5 Controller Settings
5 Controller Settings