BTS M30E0-_ _ _-H0001-S04G
Infrared Temperature Sensor
40
15
IO-Link Interface
english
Teach Instructions
Two Value Teach is explained using SP1. The same sequence is applied for SP2 with the corresponding commands.
Prerequisite:
The sensor is installed, aligned and in IO-Link mode.
How to proceed:
1.
Position the object within the beam path.
2.
Select Teach-In-Channel as follows:
Access Index
Value
Meaning
W
0x003A
0x00
Standard BDC (BDC1)
0x01…0x02
BDC1…BDC2
0xFF
All BDC
3.
Teach in teach point 1 (TP1): Send system command 0x43 to the sensor.
Access Index
Value
Meaning
W
0x0002
0x43
SP1 Two Value Teach TP1
4.
Verify whether TP1 has been taught in successfully:
Read out and check the Teach-In-Status parameter using index 0x003B.
Access Index
Value
Meaning
Result
R
0x003B 0x14
TP1 for SP1 was successfully taught
Teach-In State = WAIT FOR COMMAND
Go to step 5
0x07
Teach-In State = ERROR
Return to step 3
5.
Remove object from detection range.
6.
Teach in teach point 2 (TP2): Send system command 0x44 to the sensor.
Access Index
Value
Meaning
W
0x0002
0x44
SP1 Two Value Teach TP2
7.
Verify whether TP2 has been taught in successfully:
Read out and check the Teach-In-Status parameter using index 0x003B.
Access
Index
Value
Meaning
Result
R
0x003B
0x34
TP1 and TP2 successfully taught in from SP1
Teach-In State = WAIT FOR COMMAND
Go to step 8
0x07
Teach-In State = ERROR
Return to step 3
8.
Save and apply switch point SP1:
Send system command 0x40 to the sensor.
Access Index
Value
Meaning
W
0x0002
0x40
Teach Apply
9.
Verify whether SP1 has been applied successfully:
Read out and check the Teach-In-Status parameter using index 0x003B.
Access
Index
Value
Meaning
Result
R
0x003B
0x01
SP1 successfully applied
Teach-In State = SP1 SUCCESS
Teach-in ended successfully
0x07
Teach-In State = ERROR
Return to step 3