www.balluff.com
BTS M30E0-_ _ _-H0001-S04G
Infrared Temperature Sensor
19
9
Configuring the Digital Outputs
english
The digital outputs can be configured independently of each other. The settings options for all the digital outputs are
the same. The submenu
OUT1/OUT2
shows an overview of the settings currently in effect.
How to navigate in the menu:
►
Use [
▲
], [
▼
] to select the desired setting.
►
Use [
↵
] to switch to the submenu.
9.1
Switching Mode
The digital outputs work by default in two-point mode. The state of each digital output is determined by two swit-
ching thresholds, an upper and a lower switching threshold. Both switching thresholds thus define the hysteresis. The
minimum hysteresis is 1% of the detection range.
Lower detection range end value
Upper detection range end value
Detection range
Temperature value
Temperature value
LO
LO
Normally Closed
Normally Open
HI
HI
Upper
switching threshold ≤ 100 %
Hysteresis
≥ 1 %
OUT/BDC
OUT/BDC
0 %
100 %
Lower
switching threshold ≥ 0 %
9.2
Setting the Turn-on and Turn-off Switching Threshold
The values for the turn-on and turn-off switching threshold can be set independently of each other.
1
2
2
3
1 Current setting in effect
2 Select the new desired
setting with [
▲
] or [
▼
]
3 Possible change direc-
tion