Application recommendation for a Port X in the context of
the other designation variables (see Fig. 6-32):
–
d
evice
a
liaS
– name of the device that shows what
function the sensor executes (e.g.
rear left end switch
,
temperature at boiler floor
, etc.)
–
M
Ode
p
in
4
– selection of the actuation (e.g.
Deactivated
,
IO-Link [Manual]
,
IO-Link [Autostart]
or
Digital In/Out
. Depending on the selection, further
dialog fields open, which require an input (e.g. when
the
IO-Link [Manual]
option is selected).
If no backup and validation are required on the
port, the option IO-Link [Autostart] can be
selected for which the validation and backup are
switched off.
–
v
alidatiOn
and
bacKup
– If for the point
Mode Pin 4
the
option
IO-Link [Manual]
has been selected,the following
mandatory fields marked with “*” must be completed.
Selection
Validation
Backup
No device
check
–
–
V1.0
Compatible
Check conformity
between
connected
IO-Link device
(1.0) and default
value using
Device and
Vendor ID
–
V1.1
Compatible
–
V1.1
Backup
and
recovery
Automatic backup
of parameter
values. Changes to
the current
parameter values
are saved.
The parameter
values are restored
when a similar
IO-Link device is
connected.
V1.1
Recovery
No
automatic
backup of
parameter values.
Changes to the
current parameter
values are
not
saved.
The parameter
values are restored
when a similar
IO-Link device is
connected.
–
c
ycle
t
iMe
– if the
IO-Link [Manual]
or
IO-Link
[Autostart]
options are selected for point
Modus Pin 4
,
the desired communication cycle can be set by
selecting the corresponding value from the dropdown
list.
–
M
Ode
p
in
2
– Is defined as
d
igital
in
/
Out
.
6
WebUI/web interface (continued)
Fig. 6-32:
M
OduS
p
in
4
selection options dialog and Port 2:
Configuration dialog of the
iO-l
inK
[M
anual
]
option
The port configuration is not permanently stored.
After a reset, reboot or a deenergized phase, the
settings are lost.
It is not possible to reconfigure a port configured
as an IO-Link directly to another IO-Link mode.
The respective port must be deactivated
beforehand.
It is also not possible to change the validation
information for
IO-Link [Manual]
without first
deactivating the port.
BNI EIP-508-105-Z067
Network interface
Summary of Contents for BNI EIP-508-105-Z067
Page 1: ...deutsch Konfigurationsanleitung english Configuration Guide BNI EIP 508 105 Z067 ...
Page 2: ...www balluff com ...
Page 3: ...BNI EIP 508 105 Z067 Konfigurationsanleitung deutsch ...
Page 4: ...www balluff com ...
Page 45: ...BNI EIP 508 105 Z067 Configuration Guide english ...
Page 46: ...www balluff com ...
Page 87: ......