Power
–
LED / Error messages
The device has a green LED on its front foil. This lights up permanently as soon as the supply
voltage of the device has been applied. If an error occurs, the LED flashes at 1 Hz.
The analog output is also controlled with 0 V or 0/4 mA. If the error no longer exists, the
LED automatically lights up again permanently and the analogue output responds to the
current result.
If the error no longer exists, the LED will automatically light up again permanently.
The exact error can be read out via the serial interface via the user interface.
(
→
Variable: Error_Status, Code: "; 3")
The individual error codes are explained below:
Errorcode:
(Error_Status)
Error identification:
Error description:
0x00000001
Maximum Value
Measured value is greater than
99999999
0x00000002
Minimum Value
Measured value is less than -
99999999
0x00000008
Encoder Fault
For internal test purposes only!
0x00000040
Start/Stop Encoder Error
No "start" and no "stop" pulse
detected between two "init" pulses.
Check sensor connections!
0x00000080
Position Encoder Outside
the Limit
No "start" and no "stop" pulse
detected between two "init" pulses.
Possible cause: No position sensor or
position sensor outside the limits.