19
FIGURE 10 - MOTOR
HORSEPOWER SELECTION
6
SETTING SELECTABLE JUMPERS
WARNING! ELECTRICAL SHOCK CAN CAUSE SERIOUS OR FATAL
INJURY. BE SURE THAT ALL POWER IS DISCONNECTED FROM DRIVE BEFORE THE
COVER IS OPENED. OPENING OF THE COVER IS REQUIRED TO MAKE
INSTALLATION CONNECTIONS. ELECTRICAL SHOCK CAN CAUSE SERIOUS OR
FATAL INJURY IF THE COVER IS REMOVED AND POWER IS STILL APPLIED.
The drive has customer selectable jumpers which must be set before the drive can be used.
For an overview, see Table 4, on page 5. For location of jumpers, see Figure 3, on page 12.
6.1 AC LINE INPUT VOLTAGE (J1):
The drive is factory set for 208/230 Volt AC line input
(Jumper J1 not installed). For 115 Volt AC line input, install Jumper J1. See Figure 9.
FIGURE 9 – AC LINE INPUT VOLTAGE SELECTION¹
208/230 Volt AC Line Input
(J1 not Installed (Factory Setting))
115 Volt AC Line Input
(J1 Installed)
2
115VAC
J1
A B
J1-A
J1
-B
115
VAC
J1
-A
A B
J
1
-B
J1
Notes: 1. The drive is factory set for 208/230 Volt AC line input (Jumper J1 not installed). For
115 Volt AC line input, install Jumper J1 (supplied). 2. Jumper J1 is supplied in the hardware
bag.
6.2 MOTOR
HORSEPOWER
(J2):
Set Jumper J2 to
the corresponding position for the motor being
used. See Figure 10.
6.3
AUTOMATIC OR MANUAL START AND
RESET SELECTION (J3):
See Figure 11, on
page 20.
WARNING! AUTOMATIC START
AND RESET: JUMPER J3 IS FACTORY SET TO THE “AUTO” POSITION TO
AUTOMATICALLY START THE DRIVE WHEN THE POWER IS APPLIED
AND THE
ON/OFF AC LINE SWITCH IS SET TO THE “ON” POSITION.
WARNING! THE DRIVE WILL AUTOMATICALLY RESTART AFTER FAULT
HAS CLEARED. IF AN I
2
T OR SHORT CIRCUIT FAULT OCCURS, THE DRIVE MUST
BE RESTARTED BY SETTING THE ON/OFF AC LINE SWITCH TO THE “OFF”
POSITION FOR A MINIMUM OF 5 SECONDS.