MN1919
C.1.7 Wiring of shielded (screened) cables
Remove the outer insulation
to expose the overall shield.
Clamp should provide 360°
contact with the cable.
Flat or p-type
conductive clamp
Figure 54 - Earthing/grounding cable shields
1
9
2
10
3
11
12
13
MicroFlex
X8
Encoder Connector
Housing
Cable
Twisted pairs
Connect overall shield
to connector backshell.
Connect overall shield
to connector backshell.
CHA+
CHA-
CHB+
CHB-
CHZ+
CHZ-
+5V
DGND
Figure 55 - Encoder signal cable grounding