Basic Installation 3-9
MN1902
3.4.1 Single-phase connection to package sizes A, B, C, D
Location
Connector X1
(Mating connector: Phoenix COMBICON MVSTBW 2,5/9-ST, 5mm pitch)
Part number
FDH
1
A... / FPH
1
A...
FDH
2
A... / FPH
2
A...
Nominal input
voltage
115VAC, 1
Φ
line to neutral
(U.S. single phase supply)
230VAC, 1
Φ
line to neutral
(European single phase supply)*
Range
75-125VAC
75-250VAC
*
The required 230VAC supply may also be derived from two phases of a U.S. 230VAC
3-phase supply, i.e. 230VAC line to line. Connect one phase to L and the other phase to N.
For single-phase connection, the voltage ripple on the DC-bus is 25Vp-p for 5A peak current
rising to 50Vp-p for 10A peak current. This can limit the maximum speed of the motor.
Tightening torque for terminal block connections is 0.5-0.6Nm (4.4-5.3 lb-in).
The threaded hole in the top of the enclosure is for protective earth/ground connections.
The threaded hole in the bottom of the enclosure may be used as an additional functional
earth/ground connection for signals on connector X3. It may also be used to attach strain relief
clamps. The holes are threaded for M4 bolts no longer than 12mm (0.47 in) in length. Longer
bolts may short circuit the electrical components inside the FlexDrive
II
.
AC
Supply
Line (L)
Neutral (N)
Route L, N, and
earth/ground together
in conduit or cable
Circuit breaker or fuse.
See section 3.4.4
AC filter.
See section
3.4.5
STAR POINT
Incoming safety
earth/ground (PE)
Isolating switch
* If filter has no
output
earth/ground
terminal, earth
wire may be
connected directly
to star point.
*
If AC power wires
are shielded,
earth/ground
outer shield using
360º clamps
connected to
backplane.
Figure 2 - Earthing/grounding for single-phase installations
Note:
For CE compliance, a filter must be connected between the AC power supply and
the FlexDrive
II
. If local codes do not specify different regulations, use at least the
same gauge wire for earth/ground as is used for L and N.