Installation 2-3

MN1221

System Grounding  Continued

Ungrounded Distribution System
With an ungrounded power distribution system it is possible to have a continuous current
path to ground through the MOV devices.  To avoid equipment damage, an Isolation
transformer with a grounded secondary is recommended.  This provides three phase AC
power that is symmetrical with respect to ground.

Input Power Conditioning
The BPS is designed for direct connection to standard three phase lines that are
electrically symmetrical with respect to ground.  Certain power line conditions must be
avoided.  An AC line reactor or an isolation transformer may be required for some power
conditions.

S

If the feeder or branch circuit that provides power to the BPS has permanently
connected power factor correction capacitors, an input AC line reactor or an
isolation transformer must be connected between the power factor correction
capacitors and the BPS.

S

If the feeder or branch circuit that provides power to the BPS has power factor
correction capacitors that are switched on line and off line, the capacitors must
not be switched while the BPS is connected to the AC power line.  If the
capacitors are switched on line while the BPS is still connected to the AC power
line, additional protection is required.  TVSS (Transient Voltage Surge
Suppressor) of the proper rating must be installed between the AC line reactor
or an isolation transformer and the AC input to the BPS.

Line Impedance

The BPS requires a minimum 3% line impedance.  If the impedance of the incoming
power does not meet the requirement for the BPS, a 3 phase line reactor can be used to
provide the needed impedance in most cases. Line reactors are optional and are
available from Baldor.

The input impedance of the power lines can be determined as follows:

Measure the line to line voltage at no load and at full rated load.  
Use these measured values to calculate impedance as follows: 

%Impedance

+

(Volts

No Load Speed

*

Volts

Full Load Speed

)

(Volts

No Load Speed

)

 

100

Line Reactors

Three phase line reactors are available from Baldor.  The line reactor to order is based on
the full load current of the motor (FLA).  If providing your own line reactor, use the
following formula to calculate the minimum inductance required.  

L

+

(V

L

*

L

 

0.03)

(I

 

3

Ǹ  

377)

 Where:

L

Minimum inductance in Henries.

V

L-L

Input volts measured line to line.

0.03

Desired percentage of input impedance.

I

Input current rating of BPS.

377

Constant used with 60Hz power.
Use 314 if input power is 50Hz.

Summary of Contents for BPS 2000 Series

Page 1: ...uy your excess underutilized and idle equipment along with credit for buybacks and trade ins Custom engineering so your equipment works exactly as you specify Critical and expedited services Leasing R...

Page 2: ...BPS Series 2000 3000 Power Supply for DBSC 2000 3000 Installation Operating Manual 5 01 MN1220 AC SERVO DRIVE...

Page 3: ...l Installation 2 2 System Grounding 2 2 Line Impedance 2 3 Line Reactors 2 3 Load Reactors 2 3 Power Disconnect 2 4 Protection Devices 2 4 Power Connections 2 5 VCC and X10 Connections 2 6 Dynamic Bra...

Page 4: ...nd filtering as described in MN1383 Please refer to MN1383 for installation techniques for CE compliance For additional information refer to Sections 3 and 8 of this manual Limited Warranty For a peri...

Page 5: ...structions Safety Notice This equipment contains high voltages Electrical shock can cause serious or fatal injury Only qualified personnel should attempt the start up procedure or troubleshoot this eq...

Page 6: ...ombustible materials and flammable vapors away from brake resistors Caution Suitable for use on a circuit capable of delivering not more than the RMS symmetrical short circuit amperes listed here at r...

Page 7: ...ade performance Several other factors should be carefully evaluated when selecting a location for installation 1 For effective cooling and maintenance the BPS should be mounted on a smooth non flammab...

Page 8: ...Main Supply Safety Ground Driven Earth Ground Rod Plant Ground Four Wire Wye L1 L2 L3 Earth L2 L3 U W Route all 4 wires L1 L2 L3 and Earth Ground together in conduit or cable Route all 4 wires U V W...

Page 9: ...e AC power line If the capacitors are switched on line while the BPS is still connected to the AC power line additional protection is required TVSS Transient Voltage Surge Suppressor of the proper rat...

Page 10: ...s Buss FRN on 230 VAC or Buss FRS on 460 VAC or equivalent Table 2 2 describes the wire size to be used for power connections and the ratings of the protection devices Recommended fuse sizes are based...

Page 11: ...X10 1 2 3 4 X10 Logic Power Notes 1 See Protection Device description in this section 2 Metal conduit or shielded cable should be used Connect conduits so the use of a Reactor or RC Device does not i...

Page 12: ...ation If an optional 24VDC power supply or battery backup is used instead of the BPS the connections to X10 must be made as shown in Figure 2 5 This allows position information and other memory relate...

Page 13: ...BUS Logic Power Input 1 Phase X4 X4 Diagnostic 1 Ready 2 Alarm 3 DB_ON 4 N A 5 Reset 6 CREF 7 Fault 8 Fault 9 CIV 10 CGND See Terminal Tightening Torques in Section 3 of this manual Ready Ready To DB...

Page 14: ...3 have a 100ms delay before activation Note The maximum current draw when all three outputs are active must not exceed 100mA Figure 2 7 Status Monitor Output Connections Ready Alarm DB_ON CIV VDC CGND...

Page 15: ...l Range AMP 2 4A 115 or 1 2 230 Output Logic VDC 24 20 15 Output Logic ADC 6 9 for 3 Controls 8 0 for 5 Controls Mounting Panel or Thru Wall Package Size B Weight lb kg 33 15 Dynamic Brake Switching T...

Page 16: ...27 2 3 3 0 35 46 4 0 5 0 DB Resistor Selection Size RG 3 54 90 5 5 140 for 44 watt 8 9 228 for 100 watt 13 2 337 for 320 640 watt 3 9 100 M4 2 6 65 1 7 45 L L Clearance Requirements all sizes 2 51mm...

Page 17: ...385 13 99 355 13 25 337 0 00 0 57 15 1 16 30 2 38 61 2 97 76 3 54 90 Reference this edge to measure distance to mount next enclosure 8 58 218 4 33 110 Thru Wall Mounting Flange Surface Mount Flange Th...

Page 18: ...a clearance distance between each control and on all sides of each control Mounting and Bus Bar Information Position X Position Y Distance to next Power Bus Bar Position X Size Position Y Size Distan...

Page 19: ...SA 5 01 C J 1500 CH TEL 41 52 647 4700 FAX 41 52 659 2394 D TEL 49 89 90 50 80 FAX 49 89 90 50 8491 UK TEL 44 1454 850000 FAX 44 1454 850001 I TEL 39 11 562 4440 FAX 39 11 562 5660 AU TEL 61 29674 545...

Page 20: ...uipment Have surplus equipment taking up shelf space We ll give it a new home Learn more Visit us at artisantg com for more info on price quotes drivers technical specifications manuals and documentat...

Reviews: