background image

Section 1
General Information

Receiving & Installation 3-13

MN715

Single Phase Input Power Considerations  Single phase operation of G and H size controls is not possible.

Single phase AC input power can be used to power the control instead of three phase for
control sizes A, B, B2, C, C2, D, D2, E and F.  The specifications and control sizes are
listed in Section 6 of this manual.  If single phase power is to be used, the rated
Horsepower of the control may have to be reduced (derated).  In addition, power wiring
and jumper changes are required.  Single phase 3 wire connections are standard in the
USA.  However, single phase 2 wire  connection is used in most of the world.  Both
connections types are shown.

Single phase rating wire size and protection devices are listed in Tables 3-6 and 3-7.

Single Phase Control Derating:  Single phase power derating requires that the continuous and peak current ratings

of the control be reduced by the following percentages:

1.

1-2 hp 230 and 460VAC controls:
No derating required.

2.

3-25 hp (Size B, B2 and C2) 230 and 460VAC controls:
Derate hp by 40% of the nameplate rating.

3.

15 hp (Size C, D2) and Larger 230 and 460VAC controls:
Derate hp by 50% of the nameplate rating.

Size A, B and B2 Single Phase Power Installation

  (See Figure 3-6).

Jumper Configuration

Size A, B and B2 controls, no jumper changes required.

Figure 3-6  Size A, B & B2 Single Phase 230/460VAC Power and Motor Connections

L1

L2

L1

L2

L3

* Circuit
Breaker

Earth

See Recommended Tightening Torques in Section 6.

Note 3

Baldor

Series 15H

Control

*Optional

Line 

Reactor

Note 1

Note 3

A1

B1

A2

B2

Note 4

Notes:

1.

See “Protective Devices” described previously in this section.

2.

Use same gauge wire for Earth ground as is used for L1, L2 and L3.

3.

Metal conduit should be used.  Connect conduits so the use of a
Reactor or RC Device does not interrupt EMI/RFI shielding.

4.

See Line/Load Reactors described previously in this section.

Note 2

L1

L2

Fuse

Connection

Note 1

*

Optional components 
not provided with control.

A1

B1

L1 Neutral

* Circuit
Breaker

*Line 

Reactor

A1

A2

Single phase 2 wire Connections

Single phase 3 wire Connections

Summary of Contents for 15H SERIES 15H

Page 1: ...SERIES 15H Inverter Control Installation Operating Manual 2 01 MN715 ADJUSTABLE SPEED DRIVE...

Page 2: ...5 Line Reactors 3 5 Load Reactors 3 5 AC Main Circuit 3 6 Power Disconnect 3 6 Protective Devices 3 6 Wire Size and Protection Devices 3 6 AC Line Connections 3 10 Reduced Input Voltage Derating 3 10...

Page 3: ...utputs 3 37 Relay Outputs 3 38 Pre Operation Checklist 3 39 Power Up Procedure 3 39 Section 4 Programming and Operation 4 1 Overview 4 1 Display Mode 4 2 Adjusting Display Contrast 4 2 Display Screens...

Page 4: ...onsiderations 5 9 Relay and Contactor Coils 5 9 Wires between Controls and Motors 5 9 Special Drive Situations 5 10 Control Enclosures 5 10 Special Motor Considerations 5 10 Analog Signal Wires 5 10 S...

Page 5: ...Size D Control 6 20 Size D2 Control 6 21 Size D2 Control Through Wall Mounting 6 22 Size E Control 6 23 Size E Control Through Wall Mounting 6 24 Size F Control 6 26 Size F Control Through Wall Mount...

Page 6: ...Location procedure 3 Connect AC power Refer to Section 3 AC Line Connections 4 Connect the motor Refer to Section 3 Motor Connections 5 Install Dynamic brake hardware if required Refer to Section 3 O...

Page 7: ...Zone parameter as desired STD CONST TQ STD VAR TQ QUIET CONST TQ or QUIET VAR TQ 6 Set the Level 2 Output Limits block MIN Output FREQ parameter 7 Set the Level 2 Output Limits block MAX Output FREQ p...

Page 8: ...ing the rated current of the motor The Baldor Series 15H control may be used in many different applications It may be programmed by the user to operate in four different operating zones standard const...

Page 9: ...installation and removal inconvenience or consequential damage including injury to any person or property caused by items of our manufacture or sale Some states do not allow exclusion or limitation of...

Page 10: ...ARNING Do not use motor overload relays with an automatic reset feature These are dangerous since the process may injure someone if a sudden or unexpected automatic restart occurs If manual reset rela...

Page 11: ...quires no external power to operate Caution Disconnect motor leads T1 T2 and T3 from control before you perform a Megger test on the motor Failure to disconnect motor from the control will result in e...

Page 12: ...cation for installation 1 For effective cooling and maintenance the control should be mounted on a smooth non flammable vertical surface Table 3 1 lists the Watts Loss ratings for enclosure sizing 2 A...

Page 13: ...To mount a control through the wall a Through the Wall mounting kit must be purchased except for B2 C2 and D2 sizes These kits are Kit No Description KT0000A00 Size A control through the wall mountin...

Page 14: ...he 4 mounting holes marked A and the large knockout marked B 4 Drill four 29 mounting holes A Thread each hole using an 8 32 tap 5 Locate the 1 1 4 knockout center B and punch using the manufacturers...

Page 15: ...rounding disconnects and other current protection System Grounding Baldor Controls are designed to be powered from standard three phase lines that are electrically symmetrical with respect to ground S...

Page 16: ...r an isolation transformer and the AC input to the control Line Impedance The Baldor control requires a minimum line impedance If the impedance of the incoming power does not meet the requirement for...

Page 17: ...se thermal magnetic Equal to GE type THQ or TEB for 230VAC or Equal to GE type TED for 460VAC and 575VAC Fast Action Fuses 230VAC Buss KTN 460VAC Buss KTS to 600A KTU for 601 to 1200A 575VAC Buss FRS...

Page 18: ...6 13 3 65 50 90 100 90 4 21 2 77 60 100 125 100 3 26 7 96 75 125 150 125 2 33 6 124 100 175 200 175 1 0 53 5 156 125 200 250 200 2 0 67 4 180 150 225 300 250 3 0 85 0 240 200 300 350 300 2 2 0 2 67 4...

Page 19: ...1 40 60 60 50 8 8 37 52 50 70 80 70 6 13 3 62 60 80 100 80 6 13 3 77 75 100 125 100 4 21 2 99 100 125 150 125 3 26 7 125 125 175 200 175 1 0 53 5 144 150 200 225 200 2 0 67 4 192 200 250 300 250 4 0 1...

Page 20: ...1 2 3 1 22 44 JP3 JP4 39 40 41 42 43 44 Opto Out 2 Return Relay Out 1 Return Relay Out 2 Return 24VDC Opto In Power Opto Out 1 Return Note J4 18 and 41 are connected together on the control circuit b...

Page 21: ...se requires a 15hp Control 380 400VAC Operation Be sure all power to the control is disconnected before proceeding Size A B B2 C2 and D2 controls may be used directly with a 380 400VAC power source co...

Page 22: ...rminal Block for 380 400VAC Size G 460VAC 380 400VAC 3 Phase Installation The AC power and motor connections are shown in Figure 3 5 Figure 3 5 3 Phase AC Power Connections L1 L2 L3 Alternate Fuse Con...

Page 23: ...53 5 176 40 225 250 250 3 0 85 0 216 50 275 350 300 2 1 0 2 53 5 Table 3 7 Single Phase Rating Wire Size and Protection Devices 460 VAC Controls Control Rating Input Breaker Input Fuse Amps Wire Gauge...

Page 24: ...1 1 2 hp 230 and 460VAC controls No derating required 2 3 25 hp Size B B2 and C2 230 and 460VAC controls Derate hp by 40 of the nameplate rating 3 15 hp Size C D2 and Larger 230 and 460VAC controls D...

Page 25: ...h See Recommended Tightening Torques in Section 6 Note 3 Baldor Series 15H Control Optional Line Reactor Note 1 Note 3 A1 B1 A2 B2 Note 4 Notes 1 See Protective Devices described previously in this se...

Page 26: ...ingle Phase 230 460VAC Power Connections L1 L2 L1 L2 L3 Circuit Breaker Earth See Recommended Tightening Torques in Section 6 Note 3 Baldor Series 15H Control Optional Line Reactor Note 1 Note 3 B1 C1...

Page 27: ...Section 6 Note 3 Baldor Series H Control Optional Line Reactor Note 1 Note 3 A1 B1 A2 B2 Note 4 Notes 1 See Protective Devices described previously in this section 2 Use same gauge wire for Earth gro...

Page 28: ...Series 15H Control Optional Line Reactor Note 1 Note 3 A1 B1 A2 B2 Note 4 Notes 1 See Protective Devices described previously in this section 2 Use same gauge wire for Earth ground as is used for L1 L...

Page 29: ...es 15H Control Optional Line Reactor Note 1 Note 3 B1 C1 B2 C2 Note 4 Notes 1 See Protective Devices described previously in this section 2 Use same gauge wire for Earth ground as is used for L1 L2 an...

Page 30: ...T2 T3 G Note 2 Notes 1 Metal conduit should be used Connect conduits so the use of Load Reactor or RC Device does not interrupt EMI RFI shielding 2 See Line Load Reactors described previously in this...

Page 31: ...ls DB Terminals R2 R1 May be labeled GND or See recommended Terminal Tightening Torques in Section 6 Note Although not shown metal conduit should be used to shield all power wires and motor leads Figu...

Page 32: ...ontact with other components Failure to disconnect the internal resistor may result in equipment damage Table 3 8 Terminal Torques Wire Size for RUA Assemblies Braking B and B Terminals S and S Termin...

Page 33: ...AWG mm2 Volt 230 2 000 16 1 31 600 20 22 0 5 600 230 2 100 5 000 14 2 08 600 20 22 0 5 600 230 5 100 10 000 10 6 600 20 22 0 5 600 230 10 000 8 10 600 20 22 0 5 600 460 4 000 16 1 31 600 20 22 0 5 600...

Page 34: ...mode all connections are optional The J4 terminal strip is shown in Figure 3 24 The connection of each input or output signal is described in the following pages Figure 3 24 Control Signal Connection...

Page 35: ...2 Process Control block Setpoint Source Potentiometer When using Analog Input 1 the respective parameter must be set to POTENTIOMETER Note A potentiometer value of 5kW to 10kW 0 5 watt may be used 1...

Page 36: ...ound Each output function is programmed in the Level 1 Output block Analog Out 1 or 2 parameter values The scaling of each output is programmable in the Level 1 Output block Analog Scale 1 or 2 Serial...

Page 37: ...l Trip input J4 16 must be connected and the External Trip parameter in the Level 2 Protection block must be set to ON When J4 16 is opened the motor will coast to a stop and an External Trip fault wi...

Page 38: ...ontrol and motor coasts to a stop J4 9 MOMENTARY CLOSED starts motor operation in the Forward direction In JOG mode J4 12 CLOSED continuous CLOSED jogs motor in the Forward direction J4 10 MOMENTARY C...

Page 39: ...p mode J4 10 CLOSED operates motor in the Reverse direction with J4 9 open OPEN motor decels to stop depending on Keypad Stop mode J4 11 14 Selects programmed preset speeds as defined in Table 3 10 J4...

Page 40: ...to stop depending on Keypad Stop mode Note J4 9 and J4 10 are both closed Fault Reset J4 11 CLOSED selects Analog Input 1 if J4 13 J4 14 and J4 15 are closed OPEN selects command select Level 1 Input...

Page 41: ...ill reset a fault condition J4 10 MOMENTARY CLOSED starts motor operation in the Reverse direction Note Closing both J4 9 and J4 10 at the same time will reset a fault condition J4 11 OPEN motor decel...

Page 42: ...op depending on Keypad Stop mode Note Closing both J4 9 and J4 10 at the same time will reset a fault condition J4 11 CLOSED selects Analog Input 1 OPEN selects Level 1 Input block Command Select para...

Page 43: ...ration in the Reverse direction J4 11 When OPEN motor decels to stop depending on Keypad Stop mode J4 12 CLOSED selects STOP START and Reset commands from terminal strip OPEN selects STOP START and Re...

Page 44: ...ction OPEN motor decels to stop depending on Keypad Stop mode J4 10 CLOSED starts motor operation in the Reverse direction OPEN motor decels to stop depending on Keypad Stop mode Note Closing both J4...

Page 45: ...stop depending on Keypad Stop mode J4 12 CLOSED selects the Level 1 Input Command Select parameter value OPEN selects EPOT J4 13 CLOSED selects ACC DEC S CURVE group 2 OPEN selects ACC DEC S CURVE gro...

Page 46: ...ccel Decel group 1 parameters J4 12 CLOSED causes the control to JOG in the reverse direction J4 13 CLOSED to enable the Process Mode J4 14 CLOSED causes the control to JOG in the forward direction J4...

Page 47: ...tion Block must be set to ON Figure 3 36 Motor Temperature Relay T1 T2 T3 G Motor 16 17 J4 External Trip Do not run these wires in same conduit as motor leads or AC power wiring Customer Provided Sour...

Page 48: ...Figure 3 39 However both must be configured the same The maximum voltage from opto output to common when active is 1 0 VDC TTL compatible The equivalent circuit for the opto isolated outputs is shown...

Page 49: ...Each output can be individually configured as normally open N O or normally closed N C contacts Jumpers JP3 and JP4 select the N O or N C contacts These outputs may be wired as shown in Figure 3 41 E...

Page 50: ...ter is OFF and the Level 2 Protection block External Trip parameter is OFF 5 Set the Level 2 Output Limits block Operating Zone parameter as desired STD CONST TQ STD VAR TQ QUIET CONST TQ or QUIET VAR...

Page 51: ...3 40 Receiving Installation MN715...

Page 52: ...tus and advances to the next display menu item SHIFT Press SHIFT in the program mode to control cursor movement Pressing the SHIFT key once moves the blinking cursor one character position to the righ...

Page 53: ...or Key Adjusts display intensity Press ENTER Saves level of contrast and exits to display mode Display Screens Note The order of display is as shown scroll through order However the first display aft...

Page 54: ...e the motor is operating If the parameter is displayed with an L the setting is locked and the security access code must be entered before any changes can be made Parameter Blocks Access for Programmi...

Page 55: ...ation Display mode Stop LED on Press PROG key Access programming mode Press or key Scroll to Level 1 Input Block Press ENTER to access INPUT block parameter Press ENTER key Access Input Block Keypad m...

Page 56: ...top LED on Press PROG key Enter program mode Press or key Scroll to Level 2 Blocks Press ENTER key Select Level 2 Blocks Press or key Scroll to the Miscellaneous block Press ENTER key Select Miscellan...

Page 57: ...key Scroll to the Miscellaneous block Press ENTER key Select Miscellaneous block Press key Scroll to Factory Settings parameter Press ENTER key Access Factory Settings parameter represents blinking c...

Page 58: ...Trip input Local Enable Input or STOP input The control can operate the motor in three 3 different ways from the keypad 1 JOG Command 2 Speed adjustment with Keypad entered values 3 Speed adjustment u...

Page 59: ...key Motor runs FWD or REV at commanded speed FWD REV LED on Press STOP key Motor stop command issued Display mode Stop LED on Speed Adjustment Using Arrow Keys Action Description Display Comments App...

Page 60: ...he Access Code parameter Press ENTER key The Access Code parameter can be changed represents blinking cursor Press key Use key to change value Example 8999 represents blinking cursor Press ENTER key S...

Page 61: ...ues cannot be changed Press key Enter the Access Code Example 8999 represents blinking cursor Press ENTER key Press or key Scroll to make your selection Press ENTER Save selected parameter P will chan...

Page 62: ...ress key Use key to change value Example 8999 Note Ignore the 5 digit number to the right example 23956 Press ENTER key Save Access Code parameter Security code entered is correct All parameters may b...

Page 63: ...Command Analog Out 1 Set PT ADJ Limit Accel Decel Rate Analog Out 2 Protection At Setpoint Band Accel Time 1 Analog Scale 1 External Trip Process PROP Gain Decel Time 1 Analog Scale 2 Local Enable INP...

Page 64: ...te Accel 1 Decel 1 and S Curve 1 are associated together Likewise Accel 2 Decel 2 and S Curve 2 are associated together These associations can be used to control any Preset frequency or External Speed...

Page 65: ...lected when the input signal is applied to J4 4 and J4 5 4 20mA selection should be considered if long distance is required between the external device and the control Current loop allows longer cable...

Page 66: ...n control is Ready and is being commanded to operate the motor Reverse Active when control is running in the reverse direction Process Error Active when the PID control loop process is outside the ran...

Page 67: ...re 0VDC 0 VAC and 5VDC Control Input Voltage Torque Represents load torque where 0V 100 torque rated torque and 5V 100 torque rated torque Power Represents motor power where 0V 100 rated power and 5V...

Page 68: ...normal operation This parameter sets the maximum allowable variation in output frequency under varying load conditions changes of output current As motor current increases toward 100 of Motor Rated A...

Page 69: ...the Keypad display This value will be automatically reduced for large values The output rate display is only available if the Value At Speed parameter value is non zero Sets the desired output rate v...

Page 70: ...n be applied The run command refers to the enable plus direction FWD or REV lines Restart Fault Hr The maximum number of automatic restart attempts before requiring a manual restart After one hour wit...

Page 71: ...his value BRAKE ADJUST Resistor Ohms The dynamic braking resistor value in ohms Refer to MN701 dynamic braking manual or call Baldor for additional information If dynamic braking is not installed ente...

Page 72: ...mple if the setpoint source is 0 10VDC and the at setpoint band value is 10 the at setpoint opto output will turn on if the process is within 10 x 10 1 1VDC of the setpoint The PID loop proportional g...

Page 73: ...percentage value is multiplied by the Max Output Volts Base Frequency value If this value is too high the inverter may fault on Over current The time for the inverter to ramp the output voltage from...

Page 74: ...rvice technician experienced in the area of high power electronics It is important to familiarize yourself with the following information before attempting any troubleshooting or service of the contro...

Page 75: ...ess DISP key Display mode showing real time opto inputs outputs states 0 Open 1 Closed Opto Inputs states Left Opto Outputs states Right Press DISP key Display mode showing actual drive running time s...

Page 76: ...Press DISP to scroll to the Fault Log entry point Press ENTER key Display first fault type and time fault occurred Typical display Press key Scroll through fault messages If no messages the fault log...

Page 77: ...Hardware Protect A general hardware fault was detected but cannot be isolated 1 MIN Overload Peak output current exceeded the 1 minute rating value 3 SEC Overload Peak output current exceeded the 3 s...

Page 78: ...210 W 82E 410 W A4A 515 E E2A 210L E 82B 410L E A3F 515 W E2A 215 E 82F 415 E A4B 515L E0A 215 W 82F 415 W A4B 520 E E2B 210L ER 80C 410L ER A08 520L EOB 215V 808 415V A0E 525 E E2C 215L 80D 415L A0F...

Page 79: ...ations with date and time imprint to isolate power problem Disconnect dynamic brake hardware and repeat operation External Trip Motor ventilation insufficient Clean motor air intake and exhaust Check...

Page 80: ...e Current Limit setting Start Motor overloaded Check for proper motor loading Check couplings for binding Verify proper sizing of control and motor Motor may be commanded to run below minimum frequenc...

Page 81: ...Speed in the Level 2 Output Limits block Increase Speed PROP Gain in the Level 1 block Param Checksum Memory fault occurred Press RESET key on keypad Restore parameter values to factory settings If fa...

Page 82: ...e spikes of several hundred volts in the control circuit These spikes can induce several volts of noise in an adjacent wire that runs parallel to a control circuit wire Figure 5 1 illustrates noise su...

Page 83: ...as a ground conductor for motor power wires or signal conductors Special Motor Considerations Motor frames must also be grounded As with control enclosures motors must be grounded directly to the con...

Page 84: ...dels 575 VAC Models 180 264 VAC 3f 60Hz 180 230 VAC 3f 50Hz 340 528 VAC 3f 60Hz 340 457 VAC 3f 50Hz 495 660 VAC 3f 60Hz Input Line Impedance 3 Minimum Required A B C D E Sizes 1 B2 C2 D2 F G G2 G H Si...

Page 85: ...JOG S Curve Time 0 to 100 Base Frequency 10 to 400Hz Regenerative Braking Torque 20 Minimum E W 100 with optional external braking resistor EO MO ER Jog Frequency 0 to Maximum frequency Skip Frequenc...

Page 86: ...A Maximum Digital Outputs 4 Opto Isolated Outputs Rated Voltage 5 to 30VDC Maximum Current 60 mA Maximum ON Voltage Drop 2 VDC Maximum OFF Leakage Current 0 1 mA Maximum Output Conditions 10 Condition...

Page 87: ...200 129 100 75 125 144 ID15H4100 EO 460 E 129 100 75 125 220 165 125 93 160 184 ID15H4150V EO 460 E 185 150 112 180 300 185 150 112 180 207 ID15H4150 EO 460 F 196 150 112 190 380 247 200 149 240 276 I...

Page 88: ...15 11 2 21 24 ID15H420 E W 460 B2 22 15 11 2 21 42 28 20 14 9 27 31 ID15H425 E 460 B2 22 15 11 2 21 42 28 20 14 9 27 31 ID15H430 EO 460 C2 36 25 18 7 35 61 41 30 22 4 40 46 ID15H440 EO 460 C2 41 30 22...

Page 89: ...D 77 50 37 75 190 82 60 45 80 92 ID15H460L ER 460 D 93 60 45 90 215 103 75 56 100 115 ID15H475L EO 460 E 113 75 56 110 270 129 100 75 125 144 QUIET 8 0 kHz PWM CONSTANT TORQUE VARIABLE TORQUE CATALOG...

Page 90: ...44 40 30 41 47 ID15H540 ER 575 D 44 40 29 8 41 75 56 50 37 2 52 60 ID15H550 ER 575 D 56 50 37 52 92 67 60 45 62 71 ID15H560 ER 575 D 67 60 45 62 109 QUIET 8 0 kHz PWM CONSTANT TORQUE VARIABLE TORQUE C...

Page 91: ...5 6 4 5 0 5 35 4 ID15H215L ER 35 4 50 5 6 4 5 0 5 35 4 ID15H220 EO 50 5 6 50 5 6 4 5 0 5 50 5 6 32 3 6 ID15H220 ER 35 4 22 26 2 5 3 4 5 0 5 35 4 ID15H220L ER 35 4 22 26 2 5 3 4 5 0 5 35 4 ID15H225V EO...

Page 92: ...5 6 4 5 0 5 35 4 ID15H425V EO 35 4 50 5 6 4 5 0 5 35 4 3 5 0 4 ID15H425V ER 35 4 50 5 6 4 5 0 5 35 4 ID15H425 EO 50 5 6 50 5 6 4 5 0 5 50 5 6 32 3 6 ID15H425 ER 35 4 50 5 6 4 5 0 5 35 4 ID15H425L ER...

Page 93: ...EO 275 31 50 5 6 4 5 0 5 275 31 3 5 0 4 ID15H4200 EO 275 31 50 5 6 4 5 0 5 275 31 3 5 0 4 ID15H4250 EO 375 42 375 42 4 5 0 5 375 42 3 5 0 4 ID15H4300 EO 375 42 375 42 4 5 0 5 375 42 3 5 0 4 ID15H4350...

Page 94: ...4 3 5 0 4 ID15H515 ER 35 4 20 2 5 4 5 0 5 35 4 ID15H520 EO 35 4 20 2 5 4 5 0 5 35 4 3 5 0 4 ID15H520 EO 35 4 50 5 6 4 5 0 5 35 4 3 5 0 4 ID15H525 EO 35 4 50 5 6 4 5 0 5 35 4 3 5 0 4 ID15H525 ER 35 4 5...

Page 95: ...ta MN715 Mounting Dimensions Size A Control 11 50 292 1mm 7 20 182 9mm 25 6 4mm LOCAL SHIFT DISP RESET PROG ENTER JOG STOP REV FWD 7 20 182 9mm 0 25 6 4mm 12 00 304 8mm 7 120 180 8mm 7 70 195 6mm Air...

Page 96: ...Specifications and Product Data 6 13 MN715 Dimensions Continued Size A Control Through Wall Mounting Gasket Steel Plate Standoffs 1 2 x 2 1 2 10 32 x 0 75 Truss screw washer...

Page 97: ...sions Continued Size B Control 28 TYP 7 1mm 14 65 372 1mm 9 25 235 0mm 9 25 225 0mm 0 28 TYP 7 1mm 15 40 391 2mm 7 120 180 9mm 10 00 254 0mm Air Inlet Air Outlet 1 12 Dia 28 45 mm 0 88 Dia 22 35 mm LO...

Page 98: ...Specifications and Product Data 6 15 MN715 Size B Control Through Wall Mounting Gasket Steel Plate Standoffs 1 2 x 2 1 2 10 32 x 0 75 Truss screw washer...

Page 99: ...8 TYP 7 1mm 12 15 308 6mm 8 73 221 7mm 8 70 221 0mm Air Inlet 1 12 Dia 28 45 mm LOCAL SHIFT DISP RESET PROG ENTER JOG STOP REV FWD Cutout for through wall mounting 0 280 7mm Dia hole through wall 4 Pl...

Page 100: ...28 7 0mm 2 Places Air Inlet One or Two Fan s 119mm 28 7 0mm 2 Places 10 75 273 0 mm 11 50 292 0 mm 38 9 5 mm 38 9 5 mm 17 00 433 0 mm 17 75 451 mm 18 50 470 0 mm 9 50 241 5 mm 9 50 241 5 mm 1 734 Dia...

Page 101: ...0 0 916 8 675 9 340 0 250 Dia 2 Places 0 280 Dia 2 Places 15 665 16 075 16 568 0 000 0 916 8 675 4 95 125 7 4 71 119 6 9 66 245 4 Wall Mount Mtg Flange Through Wall Mtg Flange 16 98 431 3 10 50 266 7...

Page 102: ...33 8 4 0 00 1 00 25 4 2 75 69 8 7 01 178 0 8 76 222 5 0 00 1 00 25 4 9 76 247 9 8 76 222 5 15 50 393 7 A B A B Control Assembly 1 4 20 or M6 self sealing bolt and nut 4 places each holes coded A Custo...

Page 103: ...USTOMER POWER CONNECTIONS AIR INLET 13 50 343 0mm 14 50 368 5mm 25 00 635 0mm 10 20 259 0mm 10 00 254 0mm 31 8 0mm 23 12 587 0mm 24 25 616 0mm Air Outlet 0 875 Dia 22 23 mm 0 50 Dia 12 70 mm 1 734 Dia...

Page 104: ...330 9 50 241 0 375 Dia 4 Places 23 00 585 24 00 607 21 00 535 10 33 263 10 00 254 3 09 78 11 035 280 11 91 303 9 09 231 6 09 155 6 885 175 7 864 200 8 464 215 9 114 232 12 24 311 0 875 Dia 2 Places 0...

Page 105: ...5 Dimensions Continued Size D2 Control Through Wall Mounting Cutout for thru wall mounting 00 21 50 546 00 Mounting hole locations for Thru Wall or surface mounting Recommended 31 18 Tap 4 Places 22 2...

Page 106: ...inued Size E Control 5 75 146mm 6 25 159mm 30 00 762mm 38 38 9 5mm 2 Places 17 70 450mm Thru wall Mounting Flange Surface Mounting Flange 9 5mm 2 Places Air Inlet Air Outlet 2 469 Dia 62 71 mm 0 50 Di...

Page 107: ...0mm 445mm 00 1 00 1 19 56 5 25 13 50 21 75 26 44 27 00 28 19 28 00 00 19 79 1 25 6 00 10 75 15 50 17 54 16 94 16 75 25mm 30mm 14mm 133mm 343mm 552mm 672mm 686mm 711mm 716mm Mounting hole locations for...

Page 108: ...ht 2 V1083992 Bracket Large top bottom 14 V6300710 Screw 10 32 x 5 8 14 V6420010 Lock Washer No 10 4 V6390205 Hex Bolt 5 16 18 x 5 8 4 V6420032 Lock Washer 5 16 4 V6410132 Flat Washer 5 16 1 C6990204...

Page 109: ...ce Mounting Flange 27 00 6 76 172mm 6 24 158mm 0 38 9 5mm 3 Places 45 00 22 75 577 9mm 11 38 28 9mm 11 38 28 9mm 1143mm 44 00 1117 6mm 686mm Air Inlet Air Outlet 4 06 Dia 103 12 mm 0 50 Dia 12 70 mm 0...

Page 110: ...99 11 11 12 99 20 99 28 99 30 86 36 99 40 74 43 01 42 24 A A A A A A B B B B A B A A B A B A B B B B B B A B A A B A B A B B Mounting hole locations for Thru Wall mounting or without thru wall mountin...

Page 111: ...t No Description 2 V1084002 Bracket small left right 2 V1084001 Bracket Large top bottom 34 V6300710 Screw 10 32 x 5 8 34 V6420010 Lock Washer No 10 1 C6990204 Tape Single coated vinyl 4 0 Yards 3 65m...

Page 112: ...nsions Continued Size G Control 3 72 94 6 2 66 67 6 Removable Conduit Mounting Plates Customer Power Connections 24 00 609 6 31 50 800 90 55 2300 93 00 2362 4 00 101 6 47 25 1200 23 63 600 Air Outlet...

Page 113: ...oduct Data MN715 Dimensions Continued Size G2 Control 31 42 798 65 98 1676 69 136 1756 31 60 803 3 94 100 21 81 554 23 49 597 26 40 671 6 488 165 7 025 179 2 390 61 Removable Conduit Mounting Plates C...

Page 114: ...inued Size G Control 24 00 609 6 3 72 94 6 8 63 219 12 41 315 8 63 219 2 66 67 6 Removable Conduit Mounting Plates Customer Power COnnections 23 63 600 63 00 1600 93 00 2362 90 55 2300 4 00 101 6 35 1...

Page 115: ...ed Size H Control 24 00 609 6 3 72 94 6 8 63 219 12 41 315 8 63 219 2 66 67 6 Removable Conduit Mounting Plates Customer Power Connections 23 63 600 94 37 2397 0 93 00 2362 90 75 2305 1 4 00 101 6 35...

Page 116: ...ng The drive braking torque is limited to the available peak current and peak current time rating of the control If the peak current or peak current time limit is exceeded during braking the control m...

Page 117: ...e deceleration torque TDecel RPM change Wk2 308 time Friction Lb Ft where TDecel Deceleration torque in Lb ft Wk2 Inertia in Lb ft 2 time In seconds 3 Calculate watts to be dissipated in dynamic braki...

Page 118: ...stors See RGA assemblies Rated HP Watts 1 300 2 5 330 7 10 400 15 450 15H Catalog Numbers with an ER or MR Suffix These controls include a factory installed dynamic braking transistor If dynamic braki...

Page 119: ...bly Refer to Section 3 Optional Dynamic Brake Hardware for wiring diagram Table A 2 Dynamic Braking Resistor Assemblies RGA Input HP Minimum Continuous Rated Watts Volts Ohms 600 1200 2400 4800 6400 9...

Page 120: ...DB resistor assemblies Refer to Section 3 Optional Dynamic Brake Hardware for wiring diagram Table A 3 Dynamic Braking Assemblies RBA MAXIMUM BRAKING TORQUE IN OF MOTOR RATING Cont Catalog HP 20 25 30...

Page 121: ...uired Use Table A 4 to select the RTA assembly Refer to Section 3 Optional Dynamic Brake Hardware for wiring diagram Table A 4 Dynamic Braking Transistor Assemblies RTA HP MAXIMUM BRAKING TORQUE IN OF...

Page 122: ...00Hz PRESET SPEED 13 1013 0 MAX Speed 0 00Hz PRESET SPEED 14 1014 0 MAX Speed 0 00Hz PRESET SPEED 15 1015 0 MAX Speed 0 00Hz ACCEL DECEL ACCEL TIME 1 1101 0 to 3600seconds 3 0s RATE DECEL TIME 1 1102...

Page 123: ...B PULSE FOL 10V EXB 4 20 mA EXB 3 15 PSI EXB Tachometer EXB None Potentio Meter ANA CMD INVERSE 1403 OFF ON OFF ANA CMD OFFSET 1404 20 0 to 20 0 where 0 5V 20 0 0 ANA CMD GAIN 1405 80 0 to 120 100 0 C...

Page 124: ...100 Cal AC Current ANALOG 1 SCALE 1510 10 160 100 0 ANALOG 2 SCALE 1511 10 160 100 0 V HZ AND BOOST CTRL BASE FREQUENCY 1601 50 00 400 00Hz 60 0Hz TORQUE BOOST 1602 0 0 15 0 2 5 DYNAMIC BOOST 1603 0...

Page 125: ...REF 2104 1 to 65535 Serial Only 00000 01000 UNITS OF MEASURE 2105 See Table 4 2 UNITS OF MEASURE 2 2106 See Table 4 2 Serial Only PROTECTION EXTERNAL TRIP 2202 OFF ON OFF LOCAL ENABLE INP 2205 OFF ON...

Page 126: ...ME 2609 0 0 to 60 0seconds 3 0s PROCESS CONTROL PROCESS FEEDBACK 2701 Potentiometer 0 10VOLTS 0 5 VOLTS 4 20mA 10V EXB 4 20mA EXB 3 15 PSI TACHOMETER EXB NONE NONE PROCESS INVERSE 2702 OFF ON OFF SETP...

Page 127: ...Starts OFF SYNC START FREQUENCY 2902 Max Frequency Set Frequency MAX Frequency SYNC SCAN V F 2903 5 0 100 0 10 0 SYNC SETUP TIME 2904 0 2 2 0seconds 0 2s SYNC SCAN TIME 2905 1 0 10 0seconds 2 0s SYNC...

Page 128: ...Appendix C Appendix C 1 MN715...

Page 129: ...nting Template Four Places Tapped mounting holes use 29 drill and 8 32 tap Clearance mounting holes use 19 or 0 166 drill 4 00 2 500 1 250 1 340 4 810 5 500 1 11 16 diameter hole Use 1 25 conduit knoc...

Page 130: ...SA 2 01 C J5000 CH TEL 41 52 647 4700 FAX 41 52 659 2394 D TEL 49 89 90 50 80 FAX 49 89 90 50 8491 UK TEL 44 1454 850000 FAX 44 1454 850001 I TEL 39 11 562 4440 FAX 39 11 562 5660 AU TEL 61 29674 5455...

Page 131: ...MN715 Series 15H Inverter Control...

Reviews: