Chapter 1. Modbus Communications
12
Communications Options User’s Guide
69, 70**
CH 1 DELTH
2
4 (32 bit Long Integer)
71, 72*
CH 2 Power
--
4 (IEEE 32 bit Float)
73, 74**
CH 2 +Energy
Register 77
4 (32 bit Long Integer)
75, 76**
CH 2 -Energy
Register 77
4 (32 bit Long Integer)
77
CH 2 # Energy Digits
0
2 (16 bit signed int)
78, 79**
CH 2 TempS
2
4 (32 bit Long Integer)
80, 81**
CH 2 TempR
2
4 (32 bit Long Integer)
82, 83**
CH 2 TS-TR
2
4 (32 bit Long Integer)
84, 85**
CH 2 DELTH
2
4 (32 bit Long Integer)
86, 87*
5
Slot 1 Input A
4 (IEEE 32 bit Float)
88, 89*
5
Slot 1 Input B
4 (IEEE 32 bit Float)
90, 91*
Slot 2 Input A
4 (IEEE 32 bit Float)
92, 93*
Slot 2 Input B
4 (IEEE 32 bit Float)
94, 95*
Slot 3 Input A
4 (IEEE 32 bit Float)
96, 97*
Slot 3 Input B
4 (IEEE 32 bit Float)
98, 99*
Slot 4 Input A
4 (IEEE 32 bit Float)
100, 101*
Slot 4 Input B
4 (IEEE 32 bit Float)
102, 103*
Slot 5 Input A
4 (IEEE 32 bit Float)
104, 105*
Slot 5 Input B
4 (IEEE 32 bit Float)
106, 107*
Slot 6 Input A
4 (IEEE 32 bit Float)
108, 109*
Slot 6 Input B
4 (IEEE 32 bit Float)
508
6
MODBUS baud rate
0
2 (16 bit signed int)
509
7
MODBUS parity
0
2 (16 bit signed int)
510
8
MODBUS stop bits
0
2 (16 bit signed int)
511
MODBUS meter addr
0
2 (16 bit signed int)
512
RESERVED
--
--
*
The complete floating point value is constructed by combining readings from the first register with
a second register. An eight Hex digits number will represent the IEEE-754 hexadecimal floating point
value. 32-bit Hexadecimal Representation To Decimal Floating-Point conversion can be performed
if needed.
Example: Reg 4 reading is 44d7, Reg 5 reading is 4000, Volumetric is 44d74000, which corresponds
to 1722.
**The complete Long integer value is constructed by combining readings from the first register with
the second register. Eight Hex digits will represent the Long integer value.
Example: Reg 2 is 0019, Reg 3 is ED30, Hexadecimal Velocity is 0019ED30, which is converted to
1699120 decimal. Taking into account that Velocity has 2 decimal places (from the map), it
corresponds to a value of 16991.20.
Table 5: MODBUS Registers for a 2-Channel Liquid Flowmeter
MODBUS Reg #
Description
Scaling
(decimal places)
Size in Bytes