Chapter 2. Modbus Over Ethernet Communications 1
30
Communications Options User’s Guide
2.2.3 Changing IP Parameters
Example:
Change the DHCP-assigned IP address to static address 192.168.2.225 and disable DHCP for the module with
IP-assigned address 3.112.161.79 (see Figure 12 on page 31 and Figure 13 on page 32).
1.
Open a DOS command prompt.
2.
Type
telnet 3.112.161.79 10000
and hit
Enter
.
3.
Enter the current Login and Password.
Note:
The Login and Password are case sensitive.
4.
From the Main Menu select
1. IP Parameters.
5.
From the IP Parameters menu select
1. IP Address.
6.
Enter the new static IP address
192.168.2.225
.
Note:
If necessary, change the Subnet Main and a default Gateway by entering 2 and 3 in the IP parameters menu.
7.
Select
4
to return to the Main Menu.
8.
From the Main Menu select
3
. Enable DHCP Client.
9.
Enter
2
to disable the DHCP. Once the update has taken place, the new IP address will be shown.
10.
Select
4
. Main Menu and Quit.
11.
Cycle the power on the unit.