Distributed Control Systems Configurations
This section gives guidance for configuration in a DCS application. Figure 36 gives two general-
ized drawings that cover DCS applications to ensure switch safety.
Figure 36
DCS Switches Wiring Options
Configuration Considerations
A typical value for 24 AWG cable about 0.025 Ohm/ft (see Wiring Option #1)).
If IS barrier is a combination of fuse, resistor and Zener diode then the
connection is shown in Option #2. The barrier must have adequate
resistance to limit inrush current, as the fuse cannot limit inrush current (see
Wiring Option #2).
Power source requirements:
V
30 V. I
max
1 A.
SVI
Switch
Resistance
≥
30 Ohms +
wire resistance.
+
-
Negative switch pole
must be
directly wired to negative power supply.
+
-
Wiring Option #1
SVI
Switch
Resistance = Sized so that
circuit is limited < 50 mA
in-rush current.
+
-
Any load (no direct connection).
+
-
Wiring Option #2
Power source requirements:
V
30 V. I
max
1 A.
Summary of Contents for Masoneilan SVI II AP
Page 6: ...This page intentionally left blank...
Page 10: ...This page intentionally left blank...
Page 68: ...This page intentionally left blank...
Page 90: ...2018 Baker Hughes a GE company LLC All rights reserved 90 BHGE Spare Parts...
Page 92: ...2018 Baker Hughes a GE company LLC All rights reserved 92 BHGE...
Page 94: ...This page intentionally left blank...
Page 102: ...This page intentionally left blank...
Page 105: ...This page intentionally left blank...
Page 106: ...This page intentionally left blank...
Page 107: ...This page intentionally left blank...