® 2017 Baker Hughes, a GE company. All rights reserved.
Masoneilan 12400 Series Transmitter/Controller Instruction Manual | 57
Message on LCD /
ValVue (English)
Description
Device Action
(Warning message only or
Failsafe position)
Probable Cause
Recommended Action
T
EMPERATURE
SENS
O
R
OF MAIN
BOARD
Compensated temperature reading of
sensor circuit board was outside the -55 °C
(-67 °F) to +125 °C (+257 °F) for five reads in
a row
Failsafe position:
- Fail Low or High, user adjustable
- Fail Low only for a SIL device
Environment.
Ambient temperature exceeded
operating temperature range.
Take any action to ensure
temperature does not exceed
normal temperature range.
Return the unit if it fails.
T
EMPERATURE
SENS
O
R
OF
SENSOR BOARD
Compensated temperature reading of
sensor circuit board was outside the -55 °C
(-67 °F) to +125 °C (+257 °F) for five reads in
a row
Failsafe position:
- Fail Low or High, user adjustable
- Fail Low only for a SIL device
Environment.
Ambient temperature exceeded
operating temperature range.
Take any action to ensure
temperature does not exceed
normal temperature range.
Return the unit if it fails.
NVM
CHECKSUM
S
ENSOR
R
EA
D
Non Volatile Memory checksum error of
main circuit board
Failsafe position
Permanent corruption of the
content in non-volatile memory
occurred
Remove power to the device
for two minutes and restart
the device.
If the failure persists, replace
the device.
NVM M
ODULE
WR
ITE
Non Volatile Memory checksum error of
sensor circuit board
Failsafe position
Permanent corruption of the
content in non-volatile memory
occurred
Remove power to the device
for two minutes and restart
the device.
If the failure persists, replace
the device.
NVM S
ENSOR
WR
ITE
Non Volatile Memory error of main circuit
board module if write to FRAM failed or if
data repairing in FRAM failed
Warning message
A problem occurred when
attempting to write to the non-
volatile memory
Clear the condition using
ValVue software or HART
host.
If the failure persists, replace
the device.
NVM M
ODULE
T
E
ST
Non Volatile Memory error of sensor circuit
board if write to FRAM failed or if data
repairing in FRAM failed
Warning message
A problem occurred when
attempting to write to the non-
volatile memory
Clear the condition using
ValVue software or HART
host.
If the failure persists, replace
the device.
NVM S
ENSOR
T
E
ST
Non Volatile Memory error of main circuit
board module if both an FRAM record and
its copy have CRC errors
Warning message
A problem occurred when
testing the non-volatile
memory
Clear the condition using
ValVue software or HART
host
RAM
CHECKSUM
ERR
OR
RAM checksum error
Warning message
A corruption of the content in
non-volatile memory occurred
FLASH
CHECKSUM
ERR
OR
Flash checksum error
Failsafe position
The firmware checksum was
invalid due to data corruption
Remove power to the device
for 2 minutes and restart the
device.
If the failure persists, replace
the device.
RT
OS
SCHEDULING
ERR
OR
A RTOS task overran itself
Warning message
The micro-controller failed an
operation
STACK ERR
OR
Stack error.
A valid hidden record (in RAM) existing
upon reset indicating that a stack overflow
has occurred, as detected by the task
switching code.
Warning message
A problem with the memory
stack occurred
Clear the condition using
ValVue software or HART
host
F
A
CT
O
RY
WR
I
TE
Raw write to FRAM
Failsafe position
Raw write to FRAM.
Technical fault to indicate a
factory-only operation.
WATCHDOG
TIMEOUT
Device recovered after reset
Warning message
Device recovered after reset
Clear the condition using
ValVue software or HART
host
IRQ FAULT
Valid hidden record (in FRAM) existing upon
reset that indicates that an illegal
interrupt occurred
Warning message
An illegal circuit board interrupt
occurred
Clear the condition using
ValVue software or HART
host.
If the failure persists, replace
the device.
T
IMEOUT
FLASH
TEST
Time to complete the whole flashing
process is over
Warning message
This message appears if a
round of flash test is not
completed in 2 hours
Clear the condition using
ValVue software or HART
host.
If the failure persists, replace
the device.
Summary of Contents for Masoneilan 12400 Series
Page 46: ...44 BHGE 2017 Baker Hughes a GE company All rights reserved...
Page 62: ...60 BHGE 2017 Baker Hughes a GE company All rights reserved APPENDICES...
Page 68: ...66 BHGE 2017 Baker Hughes a GE company All rights reserved APPENDIX C see following pages...
Page 72: ...70 BHGE 2017 Baker Hughes a GE company All rights reserved APPENDIX D see following pages...