c.
Enter the BASIC SETUP menu to display [COUPLNG:%].
d.
Look through the side orifice and verify that the screw (62) coupling end of the beam (54) is loose and that the spring arm
(242) is disengaged from the pin (243)
. Through the 3/4 ” NPT hole at the bottom of the case,
push the flexure (59) from left
to right with your finger to verify it is possible to move the beam (54). The value displayed should vary accordingly.
Pin (72)
must rotate freely inside the coupling end of the beam
.
e.
Look at the mechanism through the lateral orifice, and index the oval hole of the flexure towards the special conical ended
pin (53) by bending the flexure (59) toward the case front (see Figure 15). The value read on the LCD must be between
–
5%
and +5%.
NOTE:
Check there is no oscillation of the weight used to simulate the displacer.
f.
While holding the flexure (59) in that position, slightly but firmly tighten the screw (62) using a 2.5 mm Allen wrench.
g.
Bias (spring arm function) setting
g1.
Index again the flexure (59) on the conical ended pin (53).
g2.
Move the spring arm (242) below the pin (243) on the beam. The pin has a groove to position correctly the spring. Check
the spring arm is locating inside the pin groove.
g3.
Relax the flexible lamella, check the weight stability and control the value on the LCD is always /-5%.
53
59
243
242
72
62
54
CAUTION:
Do not over tighten. This can damage the instrument.
Figure 15
Indexing for coupling adjustment
Summary of Contents for Masoneilan 12400 Series
Page 46: ...44 BHGE 2017 Baker Hughes a GE company All rights reserved...
Page 62: ...60 BHGE 2017 Baker Hughes a GE company All rights reserved APPENDICES...
Page 68: ...66 BHGE 2017 Baker Hughes a GE company All rights reserved APPENDIX C see following pages...
Page 72: ...70 BHGE 2017 Baker Hughes a GE company All rights reserved APPENDIX D see following pages...