Becker Digital Natural Gas Positioner Instruction Manual | 79
© 2022 Baker Hughes Company. All rights reserved.
7. Troubleshooting and Maintenance
This section discusses troubleshooting and maintenance issues.
Troubleshooting the Firmware Cold Restart
If any Firmware problems occur, cold restart the DNGP using the following steps:
1. Turn the DNGP power off.
2. Press and hold the
UP
,
DOWN
and
ENTER
buttons.
3. Apply power to the DNGP. The alarm light goes on and the D17 LED flashes.
Alarm and Fault Handling
Explosion Hazard: Do not disconnect equipment unless power has been switched off or the area is
known to be non-hazardous.
Table 13 - DNGP Alarm and Fault Handling
Condition
Response
Action
Loss of Control Signal 1
(Current Loop) in 4-20 mA
Input Mode
Displays
CTRL:
Fault
.
Check the RTU output
Check wires # 1 and 2 on Terminal Board 2
.
Loss of Feedback Signal
Displays
FDBK Fault.
Disconnect any other wires from #5 and 6 on TB 2 and jump
# 5 and 6 instead
.
Checks the SCADA for internal power or external power
.
Check the DNGP board JP1 for external or internal power.