Becker Digital Natural Gas Positioner Instruction Manual | 59
© 2022 Baker Hughes Company. All rights reserved.
LEFT
UP
RIGHT
EXIT
ENTER
DOWN
▼
▼
Input Config
Valve Actions
Logging & Alarms
Firmware
▼
▼
Input Config Menu
Input Selections
Split Control
Positioner Action
▼
▼
Positioner Action
Close on Increase
Open on Increase
BTL5 Position Sensor Configuring DNGP Positioner Action
On the DNGP board, you need to select the position action to change the valve from
Close on Increase
to
Open on Increase,
or vice versa. Access the DNGP valve state menu and the linear position transmitter as
follows:
1.
Hit the
ENTER
button and go to the
Input Configuration Menu
.
2.
Select the
Positioner Action
option.
3.
Choose the desired
Positioner Action
mode. Hit
ENTER
. Press the
EXIT
button twice to
go back to the main screen.