LOW Calibration
a. Position valve in Low Position.
b. Press and hold LO/Select button to enter Low Calibration.
c. Left LED will flash RED-GREEN. Press LO/SELECT to confirm.
d. If Selection not confirmed in ~6 min it will time out.
e. Right LED will flash RED-GREEN while processing change.
f. Both LEDs will flash GREEN – for Pass.
g. Both LEDs will flash RED – for Fail.
h. If fail consult DS manual and repeat steps.
See Visual Below for Low Calibration.