All Right Reserved © SHENZHEN BAK POWER BATTERY CO., LTD
37
Integrated Lithium-ion Battery Pack
User Manual
7 APPENDIX
Table7-1 Corresponds to AWG line number table
AWG
Diameter
cross-
sectional area
(
mm
2
)
Resistance
(
Ω/km
)
Rated
current
(
A
)
Maximum
current
(
A
)
mm
inches
0000
11.68
0.4600
107.22
0.17
423.2
482.6
000
10.40
0.4096
85.01
0.21
335.5
382.6
00
9.27
0.3648
67.43
0.26
266.2
303.5
0
8.25
0.3249
53.49
0.33
211.1
240.7
1
7.35
0.2893
42.41
0.42
167.4
190.9
2
6.54
0.2576
33.62
0.53
132.7
151.3
3
5.83
0.2294
26.67
0.66
105.2
120.0
4
5.19
0.2043
21.15
0.84
83.5
95.2
5
4.62
0.1819
16.77
1.06
66.2
75.5
6
4.11
0.1620
13.30
1.33
52.5
59.9
7
3.67
0.1443
10.55
1.68
41.6
47.5
8
3.26
0.1285
8.37
2.11
33.0
37.7
9
2.91
0.1144
6.63
2.67
26.2
29.8
10
2.59
0.1019
5.26
3.36
20.8
23.7
11
2.30
0.0907
4.17
4.24
16.5
18.8
12
2.05
0.0808
3.332
5.31
13.1
14.9
13
1.82
0.0720
2.627
6.69
10.4
11.8
14
1.63
0.0641
2.075
8.45
8.2
9.4
Installation steps are shown below:
1) Preparation before installing: insulation metal mounting tool (such as a cross
screwdriver, wrench), insulation tape and customized wiring cables.
2) Lithium-ion battery pack should be installed in a suitable location.
3) Connect each connector in turn with each of the output end of the lithium-ion
battery pack. First, connect all lithium-ion battery packs with to the positive
terminals (“+”), and then all the negative terminals of lithium-ion battery packs.