All Right Reserved © SHENZHEN BAK POWER BATTERY CO., LTD
19
Integrated Lithium-ion Battery Pack
User Manual
3 INSTALLATION GUIDE
Lithium battery packs cannot be placed in or near garbage disposals, or accidentally
dropped or placed in smaller disposal units, as their interaction with metals is likely to
cause short circuits and endanger the system and personal safety.
2) Fire protection
The battery storage or installation room must not contain flammable, explosive and
other dangerous goods, and it should be equipped with effective fire equipment
(such as CO2 fire extinguishers).
3) Ventilation and heat dissipation
For optimum operation and maintenance access the equipment should be installed
with 30cm
– 50cm clearance all round, with preferably 50cm clearance above it. If
installed in a cabinet or cramped area, an exhaust fan should be installed to
maintain good indoor ventilation.
4) Installation requirements
Installation should be carried out as shown in figure 3-1 in order to avoid possible
risks.
Put the lithium battery on the ground (to avoid tilt, uneven ground).
Avoid placing in the sunlight, rain or wet surfaces.
Figure3-1 Requirements for installation scenarios
⚫
Environmental requirements
Ambient temperature: ( -10~+40)
℃
.
Relative humidity level: 0%RH~95%RH, no condensation.
Cooling method: air cooler.
Height above sea level: match to the standard requirement of GB3859.2-93.
Verticality: no vibration and the vertical inclination does not exceed 5º.
Pollution level: Level
ⅱ
.
Recommended operating temperature : (20~25)
℃
, humidity level control within 50%.