OPERATING PROCEDURES
START-UP PROCEDURES
I-E96-215A
4 - 3
For an explanation of these function codes and their specifica-
tions, or an explanation of function blocks and configurations,
refer to the
Function Code Application Manual
.
NOTE: The NVRAM should be initialized BEFORE entering a con-
figuration into the module. This can be done using the operator
interface console (OIC), engineering work station (EWS), or switch
S4.
To enter a function block configuration into memory, the mod-
ule must be in configure mode. After entering all values,
change the mode to execute. If any errors exist in the configu-
ration, the module will not go into execute. Instead, the status
LED will continue to blink green and the operator interface will
indicate error mode. The cause of the configuration error can
be determined by reading status information from the QRC.
Refer to the product instruction for the operator interface con-
sole being used for procedures to change mode, configure a
module and view status messages. Please note that the config-
uration lockout dipswitch (S4-3) should be set to OPEN (OFF)
to prevent unauthorized access to the configuration.
START-UP PROCEDURES
After the quick response controller has been prepared (i.e.,
defaults set, address set, input jumpers set), installed, and
configured, it is ready to be used. Using one of the INFI 90
interface units, put the module into the execute mode. The sta-
tus LED should be green. This means that the configuration
has valid parameters, and the module is performing as it
should. If the status LED is flashing green or red, refer to the
troubleshooting section for corrective action.